Server racks and overhead DC busway inside an AI data center aisle with a containerised power conversion unit beyond

RICEWIND / Industry insights

Vertiv Extends 800 VDC Power to Rack, Pod and Data Hall: What Changes for AI Builds

Vertiv added 800 VDC systems for the AI compute pod and the data hall on 25 November 2026, extending a portfolio that started with the PowerDirect 5000 power rack. Here is what each of the three tiers actually does, where the battery sits, and what to verify before specifying.

PublishedAuthor: RICEWIND

Vertiv (NYSE: VRT) said on 25 November 2026 that it has extended its 800 VDC power portfolio from the rack to two further deployment levels: the AI compute pod and the data hall. What began in May 2026 as a single PowerDirect 5000 power rack is now presented as one architecture spanning 480 VAC facility input, rack-level DC conversion, 1.5 MW row power centres and a 5 MW medium-voltage solid-state transformer that produces 800 VDC in a single stage.

Three tiers, three different electrical boundaries

The three levels are not three sizes of the same box. Each one moves the AC-to-DC boundary to a different place in the building, and that choice determines cable counts, floor space and who owns the battery.

At rack level the PowerDirect 5000 sits beside one or two IT racks, accepts facility 480 VAC and delivers 800 VDC or ±400 VDC, configurable up to 800 kW. It holds 30 hot-pluggable 30 kW power supply units and an integrated battery backup unit designed for at least 50 seconds of hold-up. Inside the compute rack, the 1U PowerDirect 3000 shelf converts 800 VDC to 54 VDC at up to 98.5% peak efficiency and supports 180% pulse power for 0.5 ms. Moving conversion and storage out of the IT rack frees 8 to 16 rack units for compute, which is the commercial argument for brownfield sites that cannot rebuild their upstream AC plant.

At pod level the PowerDirect 9000 converts 480 VAC to 800 VDC for a whole row at 1.5 MW, scaling in 60 kW steps across 27 hot-pluggable units, and distributes through the PowerBar Track DC busway. The EnergyCore Li5 800 VDC battery cabinet connects directly to that bus with 200 kW of continuous backup at up to 98% conversion efficiency, and up to six cabinets run in parallel with active current sharing.

At data hall level the PowerNexus MV SST takes medium-voltage AC straight to 800 VDC in one conversion stage, removing two to three intermediate steps. It is outdoor, liquid-cooled and containerised, rated up to 98% AC-to-DC efficiency with galvanic isolation, and a single unit is stated to support a 4.8 MW super pod reference architecture without chaining. Bidirectional power flow allows the unit to support grid power quality rather than only consume from the grid.

  • Rack: 800 kW configurable, 30 × 30 kW PSUs, at least 50 s hold-up, 8–16 RU freed

  • Pod: 1.5 MW power centre, 60 kW increments, 200 kW battery cabinet, six in parallel

  • Hall: 5 MW SST, single-stage MV AC to 800 VDC, 4.8 MW super pod per unit

Why the battery moves onto the DC bus

In a conventional double-conversion UPS the battery hangs on a DC link inside the UPS, and the inverter is always in the path to the load. In the pod and hall tiers described here, the battery cabinet connects directly to the 800 VDC bus, so the load rides through on DC and the inverter stage disappears from the critical path.

That shift changes what a buyer has to specify. Cell chemistry, continuous C-rate and cabinet-level current sharing become primary numbers, because the battery is now sized for a power profile rather than a fixed discharge window. DC protection coordination, arc-flash prevention and ground-fault detection become safety deliverables rather than accessories. The rack tier keeps a shorter, different job: 50 seconds is a ride-through window for generator start or an orderly transfer, not a long-duration reserve.

How much backup time does 800 VDC actually give you?

The answer depends entirely on which tier the battery sits in, and the published figures are easy to misread as one another.

What is the difference between 800 VDC at rack, pod and data hall level?

Rack level converts 480 VAC to 800 VDC in a power rack next to one or two IT racks. Pod level consolidates that conversion into a 1.5 MW power centre that feeds a whole row over DC busway. Data hall level converts medium-voltage AC directly to 800 VDC in a 5 MW solid-state transformer, removing two to three conversion stages from the power train.

How much hold-up time does a rack-level 800 VDC power rack provide?

Vertiv specifies the integrated battery backup unit in the PowerDirect 5000 as designed for at least 50 seconds. That covers generator start or an orderly load transfer. Longer autonomy requires the pod-level battery cabinets or separate long-duration storage, and the rack unit should not be read as a substitute for either.

Does 800 VDC replace the AC UPS in an existing data center?

Not as a forced replacement. Vertiv states that AC and DC architectures will coexist and adoption will not follow a single timeline, and the rack-level design explicitly keeps existing upstream AC infrastructure. Mixed AC and DC loads within the same facility are supported at pod level.

Independent read on timing

Trade outlet Compare the Cloud reported the same 25 November expansion and noted that pilot programmes, technical validation and joint development with customers are under way, rather than volume deployment. A separate announcement the same day introduced the PowerNexus MV UPS for outdoor medium-voltage protection, with shipments expected to begin in mid-2027.

Read together, the two announcements put the realistic first shipment window for hall-level medium-voltage equipment in 2027, while rack-level hardware is positioned as available now. For a project with a 2026 energisation date, that timing matters more than the efficiency figures: the architecture can be designed in, but the equipment lead time has to be planned against mid-2027, not against an immediate order.

What to verify before you specify

The published architecture is detailed enough to design against, but a few items should be nailed down in the RFQ rather than assumed from the headline numbers.

  • Voltage form: 800 VDC and ±400 VDC change insulation, touch protection and PSU selection. State which one you are buying.

  • Protection study: ask for DC arc-flash, midpoint grounding and ground-fault coordination calculations, not only a datasheet.

  • Busway capacity: tap-off count per row and spare 60 kW slots in the power centre decide how much headroom you really have.

  • Battery behaviour at N+1: cabinet count and current sharing under partial load, not only at rated output.

  • Site services for the SST: outdoor pad space, liquid-cooling service access, noise limits and container lifting plan.

Where to go next

DC power systems catalogue — rectifiers, subracks and DC distribution for telecom and data centre sites

Technical background: high-density HVDC rectifier topologies for AI data centres

All news and industry analysis

Engineering Procurement & Technical Desk

For technical datasheets, custom power topology design, or volume export quotations, reach out to RICEWIND engineers.

Read the RICEWIND editorial policy to see how we verify technical content