ZTE / DC Power Systems (-48V)

ZXD3000 (V5.1) Equipment information & support

The ZTE ZXD3000 (V5.1) is a renowned classic 50A telecom rectifier module deployed in carrier networks globally, supplying -48V 50A (3000W) with extreme electrical durability, low field RMA, and precise digital current sharing.

Equipment information

Brand
ZTE
Equipment model
ZXD3000 (V5.1)
Equipment type
DC Power Systems (-48V)
Controller / software version
Confirm against the installed equipment
View full product specifications
ZTE ZXD3000 (V5.1) High-Frequency Telecom Rectifier Module (48V 50A 3000W Classic Subrack Module) - Official Front View

Information below comes from the current product catalogue. Confirm the controller, software version and configuration of the installed equipment separately.

Rated Output VA / Wattage
3000W Continuous Output
AC Input Voltage
80V - 300V AC Wide Tolerance
Chassis Form Factor
132 × 85 × 290 mm
Rated DC Output Current
-48VDC (-42V ~ -58V)
Nominal DC Output Voltage
-48VDC (-42V ~ -58V)
Peak Energy Efficiency
≥ 96.0%

Alarms & troubleshooting

AC_IN_FAIL / MAINS_LOST
Input Amber / Alarm Red solid
Utility grid failure, AC breaker tripped, or line voltage out of range
1. Measure incoming AC voltage with a multimeter; 2. Check input circuit breaker and upstream distribution; 3. System automatically soft-starts upon power restoration.
DC_OV_SHUTDOWN / LOCKOUT
Alarm Red solid, module output locked out
DC bus overvoltage or internal feedback sensor fault
1. Measure actual DC bus terminal voltage; 2. Cycle AC supply breaker to discharge capacitors and reboot; 3. Replace power module if fault recurs persistently.
FAN_FAIL / OVER_TEMP
Temp Yellow solid, fan halted or derated
Air intake dust blockage or fan bearing obstruction
1. Clean dust accumulation from intake grilles and filters; 2. Verify ambient room air conditioning is operational; 3. Replace cooling fan if rotation remains stalled.

Access Complete Maintenance & Full Alarm Troubleshooting Manual

This page lists high-frequency critical alarm codes commonly encountered in field maintenance. Comprehensive manufacturer troubleshooting matrices, board-level repair guides, detailed electrical schematics, and firmware commissioning manuals are delivered alongside equipment upon formal project procurement, accompanied by dedicated FAE technical support.

Share on-site information

  1. 01

    Identify the exact model

    Record the nameplate, system model and controller or module model.

  2. 02

    Keep the alarm details

    Record the full alarm text, indicator colour, timing and whether it persists.

  3. 03

    Describe recent changes

    Note recent replacements, software updates or configuration changes.

Record information visible in the existing interface. Electrical measurements, disassembly and replacement should follow the applicable manufacturer's manual and be performed by qualified personnel.

Your model and these details will be added to the enquiry form for you to review before sending.

Related technical articles

View all articles

Need a replacement module or supporting equipment?

Confirm the full model, system configuration and compatibility requirements before enquiring about suitable products.

Ask about suitable products

Have a model and an on-site issue?

Share the exact model, alarm text and observed symptoms to help identify relevant information and compatibility requirements.

Request technical support