Vertiv / Power management

NetSure 212 C23-S1 Equipment information & support

The Vertiv NetSure 212 C23-S1 is a high-density 19-inch 2U subrack DC power system delivering a nominal -48VDC output up to 60A/3000W, engineered for telecom access nodes and edge infrastructure.

Equipment information

Brand
Vertiv
Equipment model
NetSure 212 C23-S1
Equipment type
Power management
Controller / software version
Confirm against the installed equipment
View full product specifications
Vertiv NetSure 212 C23-S1 Official White Background Photo View 1

Information below comes from the current product catalogue. Confirm the controller, software version and configuration of the installed equipment separately.

AC Input Voltage Range
85VAC ~ 300VAC (Nominal 220VAC) VAC
Smart Monitoring Controller
M221S Controller
Cooling Method
DC fan cooling with temperature control
Nominal Output Voltage
-48VDC VDC
Rated Output Current
60A (System Capacity 2.9kW)
Managed Rectifier Capacity
2 Slots for R48-1000e / R48-2000e3 Modules

Alarms & troubleshooting

AC_MAINS_FAIL
Rectifier yellow LED steady/flashing, controller red alarm LED steady
Total commercial AC mains blackout, upstream AC circuit breaker tripped, or input voltage dropped below 85VAC.
Measure L-N voltage at the AC input terminal block. If zero, inspect the upstream distribution board and surge protection breaker; if within spec, verify AC screw terminals are torqued and breaker contacts are closed.
DC_UNDER_VOLT
Controller yellow/red alarm LED steady, audible buzzer active
Prolonged battery discharge during mains outage causing DC bus voltage to fall below the undervoltage threshold (typically below -45.0VDC).
Deploy emergency mobile generator to restore AC mains immediately; verify total DC load and manually isolate non-critical circuits; ensure operational rectifiers are not locked out or in current-limit state.
RECT_COMM_FAIL
Controller yellow alarm LED flashing, faulty rectifier green power LED flashing
CAN bus communication loss, physical backplane signal contact oxidation/displacement, or rectifier internal interface circuit failure.
Reseat the faulted rectifier module, inspecting the backplane connector for dust or damage; swap the module to an adjacent empty slot to isolate whether the fault is in the slot or module; verify controller seating.
RECT_FAN_FAIL
Rectifier red LED steady, controller yellow alarm LED steady
Rectifier cooling fan mechanically jammed by foreign objects, dust accumulation, or tachometer feedback loss causing power derating/shutdown.
Disconnect AC and slide the rectifier out; inspect fan grill and remove foreign debris; blow clean with compressed air; if rotor spins freely by hand but the alarm persists upon power-up, replace the fan assembly or entire rectifier.
BATT_TEMP_HIGH
Controller red alarm LED steady, intermittent acoustic warning beeping
Battery compartment air conditioner outage, ambient thermal runaway, or internal cell micro-short causing extreme thermal accumulation (exceeding safety threshold, typically 50°C to 55°C).
Scan each battery cell immediately using an infrared thermometer; if all cells show uniform high temp, check/restart site HVAC cooling; if a single cell exhibits abnormal localized heat or swelling, open the battery circuit breaker to isolate the bank and lower float voltage.

Access Complete Maintenance & Full Alarm Troubleshooting Manual

This page lists high-frequency critical alarm codes commonly encountered in field maintenance. Comprehensive manufacturer troubleshooting matrices, board-level repair guides, detailed electrical schematics, and firmware commissioning manuals are delivered alongside equipment upon formal project procurement, accompanied by dedicated FAE technical support.

Share on-site information

  1. 01

    Identify the exact model

    Record the nameplate, system model and controller or module model.

  2. 02

    Keep the alarm details

    Record the full alarm text, indicator colour, timing and whether it persists.

  3. 03

    Describe recent changes

    Note recent replacements, software updates or configuration changes.

Record information visible in the existing interface. Electrical measurements, disassembly and replacement should follow the applicable manufacturer's manual and be performed by qualified personnel.

Your model and these details will be added to the enquiry form for you to review before sending.

Related technical articles

Browse the technical guides or send a question about this model.

View all articles