Vertiv NetSure 731 A41-S2 Official White Background Photo View 1
VertivModel: NetSure 731 A41-S2

Vertiv NetSure 731 A41-S2 Subrack Telecom Power System -48 V 150 A 4U

A 19-inch -48 V DC power system combining distribution, up to four R48-3000e3 rectifier modules and an M221S or M222S controller.

Instant Engineer & Sales Quotation

Need to confirm a model, specification, or project configuration? Our team can follow up by email or phone.

WhatsApp

Clear support from selection to delivery

360°Technical support
N+Service commitment
3Steps shipping
100%Customer satisfaction
Rectifier module configuration
R48-3000e3, up to 4 modules
DC output voltage range
-43.2 to -57.6 Vdc
Maximum DC load output current
≤150 A
Efficiency
System: ≥94.5%; rectifier module peak: 95.5%
Subrack dimensions (W × D × H)
483 × 390 × 178 mm
Operating temperature
-5 to +40 °C

What this product is

What this product is

This 19-inch subrack power system integrates AC/DC conversion, DC distribution and system monitoring. The A41-S2 configuration uses an M221S or M222S controller and accommodates up to four R48-3000e3 rectifier modules.

What problem it solves

It provides a regulated -48 V DC supply and organized load and battery connections for telecommunications equipment, within a maximum DC load output of 150 A.

Who and where it is for

Suitable for telecommunications power installations requiring a 19-inch subrack, -48 V DC output and integrated distribution, with up to four R48-3000e3 rectifier modules.

Core advantages

  • Up to four R48-3000e3 rectifier modules
  • Maximum DC load output of 150 A and battery charging current up to 56 A
  • System efficiency at least 94.5%; rectifier module peak efficiency 95.5%
  • Integrated distribution and M221S/M222S monitoring in a 19-inch subrack

Technical specifications

Key specificationsValue
Product type19-inch subrack power system with distribution, rectifier modules and controller
Rectifier module configurationR48-3000e3, up to 4 modules
ControllerM221S / M222S
AC input configurationSingle-phase L+N+PE, 220 Vac
AC input voltage range85-300 Vac
AC input frequency45-65 Hz
Power factor≥0.99
Maximum AC input current≤74 A, including 10 A AC output
Nominal DC output voltage-48 Vdc
DC output voltage range-43.2 to -57.6 Vdc
Default output voltage-53.5 Vdc; -54 Vdc with an Emerson outdoor cabinet
Maximum DC load output current≤150 A
Maximum battery charging current≤56 A
EfficiencySystem: ≥94.5%; rectifier module peak: 95.5%
Voltage regulation accuracy≤1%
Parallel current-sharing imbalanceBetter than ±5%
Psophometric noise≤2 mV (300-3400 Hz)
Peak-to-peak noise≤200 mV (0-20 MHz)
Priority load branches (PL)32 A/1P × 2; 16 A/1P × 2
Non-priority load branches (NPL)63 A/1P × 2; 32 A/1P × 4; 16 A/1P × 2
Battery breakers2 × 125 A/1P
Surge protection devices1 AC and 1 DC
Dry contactsW2453X1 interface board: 1 standard board provides DO1-DO4; up to 2 boards for DO1-DO8
Communication interfaceRS232; M222S controller has no Ethernet interface
Hot-swapLossless hot-swap supported; replacement time <1 min
Subrack dimensions (W × D × H)483 × 390 × 178 mm
Subrack weight≤15 kg, excluding packaging, rectifier modules and controller
Operating temperature-5 to +40 °C
Storage temperature-40 to +70 °C
Relative humidity5%-95%
Operating altitude≤2000 m; derating required above this altitude
Mean time between failures>200000 h
Acoustic noise≤60 dB(A)
Electromagnetic compatibilityConducted emissions EN 55022 Class A; immunity EN/IEC 61000-4-2/-3/-4/-5/-6
Safety standardsIEC 60950-1; designed to UL, CE and NEBS safety requirements
Front service clearance≥800 mm

Applications

01

-48 V DC power and distribution for telecommunications equipment

02

19-inch subrack telecommunications power installations

Frequently asked questions

Continue exploring

Vertiv

Vertiv ER22005S Genuine Telecom Hardware Shot 1
VertivModel: ER22005S

Vertiv ER22005S Utility Substation High-Voltage DC Operating Power Rectifier (220V 5A 1100W)

Featuring full-bridge resonant soft-switching technology and digital DSP-driven control, the ER22005S achieves a peak conversion efficiency of ≥ 94.0%. With its advanced hybrid natural convection and thermal fan cooling, autonomous active current sharing, and hot-pluggable architecture, the unit ensures stable, transient-free high-voltage DC output under severe electromagnetic interference and harsh ambient temperatures.

View details

Technical and buying guides

Vertiv NetSure 531 A41 Subrack DC Power System Wiring, LLVD Configuration, and Commissioning Guide

An authoritative engineering manual for the Vertiv / Emerson NetSure 531 A41 series 19-inch 4U telecom embedded DC power subrack. Covers AC/DC distribution terminal schematics, battery and load cabling, M830B / M221S supervisory parameter setup, two-stage LLVD (Load Low Voltage Disconnect) and BLVD (Battery Low Voltage Disconnect) threshold programming, and full on-site commissioning procedures.