Vertiv BMK1115601-006 Subrack Telecom DC Power System (-48V 200A 3U)
Standard 19-inch rack-mount embedded DC power system engineered for wide-range AC input, active rectifier redundancy, and tiered load/battery low-voltage disconnect.

A 19-inch -48 V DC power system combining distribution, up to four R48-3000e3 rectifier modules and an M221S or M222S controller.
Need to confirm a model, specification, or project configuration? Our team can follow up by email or phone.
This 19-inch subrack power system integrates AC/DC conversion, DC distribution and system monitoring. The A41-S2 configuration uses an M221S or M222S controller and accommodates up to four R48-3000e3 rectifier modules.
It provides a regulated -48 V DC supply and organized load and battery connections for telecommunications equipment, within a maximum DC load output of 150 A.
Suitable for telecommunications power installations requiring a 19-inch subrack, -48 V DC output and integrated distribution, with up to four R48-3000e3 rectifier modules.
| Key specifications | Value |
|---|---|
| Product type | 19-inch subrack power system with distribution, rectifier modules and controller |
| Rectifier module configuration | R48-3000e3, up to 4 modules |
| Controller | M221S / M222S |
| AC input configuration | Single-phase L+N+PE, 220 Vac |
| AC input voltage range | 85-300 Vac |
| AC input frequency | 45-65 Hz |
| Power factor | ≥0.99 |
| Maximum AC input current | ≤74 A, including 10 A AC output |
| Nominal DC output voltage | -48 Vdc |
| DC output voltage range | -43.2 to -57.6 Vdc |
| Default output voltage | -53.5 Vdc; -54 Vdc with an Emerson outdoor cabinet |
| Maximum DC load output current | ≤150 A |
| Maximum battery charging current | ≤56 A |
| Efficiency | System: ≥94.5%; rectifier module peak: 95.5% |
| Voltage regulation accuracy | ≤1% |
| Parallel current-sharing imbalance | Better than ±5% |
| Psophometric noise | ≤2 mV (300-3400 Hz) |
| Peak-to-peak noise | ≤200 mV (0-20 MHz) |
| Priority load branches (PL) | 32 A/1P × 2; 16 A/1P × 2 |
| Non-priority load branches (NPL) | 63 A/1P × 2; 32 A/1P × 4; 16 A/1P × 2 |
| Battery breakers | 2 × 125 A/1P |
| Surge protection devices | 1 AC and 1 DC |
| Dry contacts | W2453X1 interface board: 1 standard board provides DO1-DO4; up to 2 boards for DO1-DO8 |
| Communication interface | RS232; M222S controller has no Ethernet interface |
| Hot-swap | Lossless hot-swap supported; replacement time <1 min |
| Subrack dimensions (W × D × H) | 483 × 390 × 178 mm |
| Subrack weight | ≤15 kg, excluding packaging, rectifier modules and controller |
| Operating temperature | -5 to +40 °C |
| Storage temperature | -40 to +70 °C |
| Relative humidity | 5%-95% |
| Operating altitude | ≤2000 m; derating required above this altitude |
| Mean time between failures | >200000 h |
| Acoustic noise | ≤60 dB(A) |
| Electromagnetic compatibility | Conducted emissions EN 55022 Class A; immunity EN/IEC 61000-4-2/-3/-4/-5/-6 |
| Safety standards | IEC 60950-1; designed to UL, CE and NEBS safety requirements |
| Front service clearance | ≥800 mm |
Vertiv

Standard 19-inch rack-mount embedded DC power system engineered for wide-range AC input, active rectifier redundancy, and tiered load/battery low-voltage disconnect.

Featuring full-bridge resonant soft-switching technology and digital DSP-driven control, the ER22005S achieves a peak conversion efficiency of ≥ 94.0%. With its advanced hybrid natural convection and thermal fan cooling, autonomous active current sharing, and hot-pluggable architecture, the unit ensures stable, transient-free high-voltage DC output under severe electromagnetic interference and harsh ambient temperatures.

The Vertiv ER22010-T is a 220Vdc/10A high-voltage DC switch-mode rectifier module engineered for utility substations, power plants, and HVDC distribution systems. Utilizing advanced resonant soft-switching technology, it delivers >94% peak efficiency, hot-swappable reliability, and comprehensive electrical protection.

The Vertiv ER22020-T is a 4.4kW high-power switch-mode rectifier module delivering 220Vdc/20A for utility substations and critical industrial DC systems. Powered by full DSP digital control and LLC resonant conversion, it provides industry-leading electrical stability across extreme temperatures.
An authoritative engineering manual for the Vertiv / Emerson NetSure 531 A41 series 19-inch 4U telecom embedded DC power subrack. Covers AC/DC distribution terminal schematics, battery and load cabling, M830B / M221S supervisory parameter setup, two-stage LLVD (Load Low Voltage Disconnect) and BLVD (Battery Low Voltage Disconnect) threshold programming, and full on-site commissioning procedures.