Vertiv / Power distribution units (PDU)

RP1V2001 Equipment information & support

The Vertiv RP1V2001 is a compact DIN-rail mounted power distribution telemetry module engineered for precision power distribution cabinets (PDC) and telecom DC frames. It features multi-channel high-precision AC/DC voltage/current analog acquisition and digital status inputs to track circuit breaker positions and fuse alarms in real time.

Equipment information

Brand
Vertiv
Equipment model
RP1V2001
Equipment type
Power distribution units (PDU)
Controller / software version
Confirm against the installed equipment
View full product specifications
Vertiv RP1V2001 Intelligent Power Distribution Monitoring Module (Multi-Circuit AC/DC Telemetry DIN-Rail) - Nameplate & Electrical Specifications

Information below comes from the current product catalogue. Confirm the controller, software version and configuration of the installed equipment separately.

Analog Acquisition Channels
Multi-Channel Voltage & Hall Effect Current Inputs
Upstream Telemetry Bus
Isolated RS485 Bus / Standard Modbus-RTU
Mechanical Mounting Standard
35mm Industrial DIN-Rail Snap-On
Auxiliary Power Supply Range
18Vdc - 60Vdc (Direct Telecom DC Bus Powered)
Measurement Accuracy Class
Voltage Class 0.2 / Current & Power Class 0.5
Auxiliary Digital Inputs
Multi-Channel Dry Contact Auxiliary Switch & Fuse Alarms

Alarms & troubleshooting

AC_IN_FAIL / Utility Grid Failure
Input Amber LED flashing, Master Alarm Red solid
Utility power outage, AC voltage outside tolerance (<85Vac or >300Vac), or tripped circuit breaker
1. Measure incoming AC line voltage to verify it has normalized; 2. Confirm that the input breaker on the distribution panel is closed; 3. Once AC grid recovers, the module soft-starts automatically to resume DC output.
DC_OV_LOCKOUT / DC Overvoltage Shutdown
Fault Red LED solid, module completely shut down
Internal voltage feedback loop failure, lightning surge ingress, or severe current-sharing imbalance
1. Probe DC bus voltage with a digital multimeter to rule out external spikes; 2. Open the input breaker, extract the module, wait 30s for capacitor discharge, and reinsert; 3. If overvoltage persists upon power-up, replace the internal control board.
FAN_FAIL_OTP / Fan Failure & Over-Temperature
Temp Amber LED solid, output power derated proportionally
HVAC failure in server room, clogged air intake filters, or seized ball-bearing cooling fan
1. Clean dust accumulation from front-panel intake grilles to ensure unrestricted airflow; 2. Confirm equipment room ambient temperature is maintained under 25°C; 3. Inspect fan rotor for mechanical obstruction; hot-swap replacement fan if seized.

Access Complete Maintenance & Full Alarm Troubleshooting Manual

This page lists high-frequency critical alarm codes commonly encountered in field maintenance. Comprehensive manufacturer troubleshooting matrices, board-level repair guides, detailed electrical schematics, and firmware commissioning manuals are delivered alongside equipment upon formal project procurement, accompanied by dedicated FAE technical support.

Share on-site information

  1. 01

    Identify the exact model

    Record the nameplate, system model and controller or module model.

  2. 02

    Keep the alarm details

    Record the full alarm text, indicator colour, timing and whether it persists.

  3. 03

    Describe recent changes

    Note recent replacements, software updates or configuration changes.

Record information visible in the existing interface. Electrical measurements, disassembly and replacement should follow the applicable manufacturer's manual and be performed by qualified personnel.

Your model and these details will be added to the enquiry form for you to review before sending.

Related technical articles

Browse the technical guides or send a question about this model.

View all articles

Need a replacement module or supporting equipment?

Confirm the full model, system configuration and compatibility requirements before enquiring about suitable products.

Ask about suitable products

Have a model and an on-site issue?

Share the exact model, alarm text and observed symptoms to help identify relevant information and compatibility requirements.

Request technical support