AC Input Voltage Range
85VAC ~ 300VAC (Nominal 220VAC) VAC
Smart Monitoring Controller
PSM-B2 / M221S Central Controller
Cooling Method
Temperature-regulated air cooling
Nominal Output Voltage
-48VDC VDC
Rated Output Current
100A (System Capacity 4.8kW)
Managed Rectifier Capacity
2 Slots for HD4850-2 / R48-2900U Modules

Alarms & troubleshooting

AC_MAINS_FAIL
System Red Alarm LED solid ON; AC distribution indicator OFF
AC mains blackout, upstream input circuit breaker tripped, or voltage out of operational limits (<80VAC or >305VAC)
1. Measure AC input terminal voltage with a DMM; 2. Inspect and reset upstream breaker or ATS transfer switch; 3. Verify that the AC Surge Protective Device (SPD) has not shorted out or failed.
DC_VOLT_HIGH
Controller Red Alarm LED flashing; continuous audible buzzer alarm
Rectifier voltage runaway, internal feedback loop breakdown, or misconfigured equalize voltage threshold > -58.0VDC
1. Hot-unplug rectifiers one by one to identify the runaway unit (bus voltage drops when faulty unit is removed); 2. Verify controller float/equalize setpoints (nominal: -53.5VDC to -56.4VDC); 3. Replace the defective rectifier.
LLVD_DISCONNECT
Controller Amber Major Alarm LED solid ON; priority-2 load contactor status OFF
Mains outage prolonged, battery discharged below LLVD threshold (default -44.0VDC), triggering load shed contactor
1. Confirm duration of mains outage and estimate remaining battery run-time; 2. Dispatch mobile emergency generator to restore AC feed; 3. Upon AC recovery, confirm automatic LLVD contactor re-engagement and battery recharge.
RECTIFIER_COMM_FAIL
Controller Amber LED ON; specific rectifier module Yellow Comm LED flashing or OFF
CAN bus communication loss between controller and rectifier, oxidized backplane pins, or damaged rectifier ID IC
1. Unseat rectifier and inspect backplane connector pins for physical damage or debris; 2. Firmly reinsert module and engage locking latch; 3. Run 'Rescan Nodes' on controller; 4. Swap slot to isolate backplane vs module defect.
BATT_TEMP_HIGH
Controller Amber Warning LED flashing; LCD displays battery temperature warning
Site cooling/HVAC failure, battery thermal runaway/internal short, or detached/defective NTC temperature probe
1. Scan individual battery blocks with an infrared thermometer to detect localized thermal hotspots or bulging; 2. Verify site cooling fans and air conditioning status; 3. Measure NTC probe resistance against temp-curve and re-affix firmly.

Access Complete Maintenance & Full Alarm Troubleshooting Manual

This page lists high-frequency critical alarm codes commonly encountered in field maintenance. Comprehensive manufacturer troubleshooting matrices, board-level repair guides, detailed electrical schematics, and firmware commissioning manuals are delivered alongside equipment upon formal project procurement, accompanied by dedicated FAE technical support.

Share on-site information

  1. 01

    Identify the exact model

    Record the nameplate, system model and controller or module model.

  2. 02

    Keep the alarm details

    Record the full alarm text, indicator colour, timing and whether it persists.

  3. 03

    Describe recent changes

    Note recent replacements, software updates or configuration changes.

Record information visible in the existing interface. Electrical measurements, disassembly and replacement should follow the applicable manufacturer's manual and be performed by qualified personnel.

Your model and these details will be added to the enquiry form for you to review before sending.

Related technical articles

Browse the technical guides or send a question about this model.

View all articles

Need a replacement module or supporting equipment?

Confirm the full model, system configuration and compatibility requirements before enquiring about suitable products.

Ask about suitable products

Have a model and an on-site issue?

Share the exact model, alarm text and observed symptoms to help identify relevant information and compatibility requirements.

Request technical support