Vertiv / UPS power

Liebert GXT5 3kVA Equipment information & support

The Vertiv Liebert GXT5 3kVA (GXT5-3000IRT2UXL) is a 2U rack/tower convertible online double-conversion UPS delivering unity power factor (3000VA/3000W) and zero transfer time for critical IT applications.

Equipment information

Brand
Vertiv
Equipment model
Liebert GXT5 3kVA
Equipment type
UPS power
Controller / software version
Confirm against the installed equipment
View full product specifications
Liebert GXT5 3kVA Official Product View 2

Information below comes from the current product catalogue. Confirm the controller, software version and configuration of the installed equipment separately.

Apparent Power
3000 VA
Active Power
3000 W
Output Power Factor PF
1.0
Topology
Online double-conversion, high-frequency pure sine wave
AC Input Voltage Range
115 ~ 288 VAC
Nominal DC Output Voltage
208/220/230/240 VAC

Alarms & troubleshooting

INV_FAULT (Inverter Fault / Bypass Active)
Alarm LED (Red solid), Bypass LED (Amber solid), Inverter LED (Off)
Inverter bridge IGBT short/breakdown, DC offset over-limit, or gate drive circuit failure forcing unit to bypass
1. Review LCD event log to retrieve the secondary fault code. 2. Verify the load is sustained by bypass; measure AC output voltage stability. 3. Attempt an alarm reset and manual inverter restart; if fault persists, isolate unit on maintenance bypass and replace internal power stage.
BATT_DISCON (Battery Disconnected / Open Circuit)
Battery LED (Red flashing), Alarm LED (Amber solid)
External Battery Cabinet (EBC) Anderson connector loose, DC breaker open, or internal DC fuse blown
1. Inspect external battery cabinet cable harness and Anderson connector for secure latching. 2. Verify the DC circuit breaker on the rear of the EBC is in the ON position. 3. Measure open-circuit DC bus voltage with a digital multimeter; check internal busbar fuses if 0V. 4. Execute a manual Battery Self-Test via LCD to clear the fault status.
OUTPUT_OVERLOAD (Output Overload Fault / Shutdown)
Alarm LED (Amber/Red solid), Continuous audible buzzer, LCD shows Load > 105%
Connected IT load exceeds the 3kVA/3kW rated capacity, or downstream PDU experiences inrush current/fault
1. Check LCD display to identify actual load percentage (VA/Watts). 2. Shed non-critical loads immediately by disabling programmable output receptacles. 3. Inspect downstream PDUs and branch circuits for localized inrush or ground faults. 4. Reduce overall load below 90% capacity; system will auto-recover from bypass or allow manual reset.
OVER_TEMP (Over-Temperature Protection)
Alarm LED (Red solid), Cooling fans running at 100% max speed, Bypass LED (On)
Air intake bezel blocked, ambient ambient temperature exceeds 40°C, or internal cooling fan locked/failed
1. Verify data center rack ambient temperature is maintained below 30°C. 2. Clear obstructions from front bezel intake and maintain minimum 100mm clearance at rear exhaust. 3. Check LCD diagnostics for fan RPM feedback; if a fan reports 0 RPM, replace the failed cooling fan assembly. 4. Allow heatsinks to cool below safety threshold; the unit will automatically resume inverter operation.
CHG_FAULT (Charger Failure / DC Bus Float Voltage Error)
Alarm LED (Amber flashing), Battery LED (Off), LCD displays 'Charger Failure'
Charger control loop feedback failure, power converter stage fault, or DC float overvoltage protection activated
1. Measure battery terminals using a DMM to determine if float voltage exceeds limits (~2.27V to 2.30V/cell). 2. Disconnect external battery packs, restart UPS logic power, and verify no-load charger output voltage. 3. If open-circuit charger voltage is 0V or out of spec, the internal charger module requires replacement. 4. Inspect battery strings for shorted or degraded cells and replace damaged battery modules.

Access Complete Maintenance & Full Alarm Troubleshooting Manual

This page lists high-frequency critical alarm codes commonly encountered in field maintenance. Comprehensive manufacturer troubleshooting matrices, board-level repair guides, detailed electrical schematics, and firmware commissioning manuals are delivered alongside equipment upon formal project procurement, accompanied by dedicated FAE technical support.

Share on-site information

  1. 01

    Identify the exact model

    Record the nameplate, system model and controller or module model.

  2. 02

    Keep the alarm details

    Record the full alarm text, indicator colour, timing and whether it persists.

  3. 03

    Describe recent changes

    Note recent replacements, software updates or configuration changes.

Record information visible in the existing interface. Electrical measurements, disassembly and replacement should follow the applicable manufacturer's manual and be performed by qualified personnel.

Your model and these details will be added to the enquiry form for you to review before sending.

Related technical articles

Browse the technical guides or send a question about this model.

View all articles