Vertiv / UPS power

Liebert GXT5 10kVA Equipment information & support

The Vertiv Liebert GXT5 10kVA (GXT5-10KIRT5UXLN) is a 5U rack/tower convertible online double-conversion UPS delivering unity power factor (10kVA/10kW) and zero transfer time for mission-critical IT racks.

Equipment information

Brand
Vertiv
Equipment model
Liebert GXT5 10kVA
Equipment type
UPS power
Controller / software version
Confirm against the installed equipment
View full product specifications
Liebert GXT5 10kVA Official Product View 3

Information below comes from the current product catalogue. Confirm the controller, software version and configuration of the installed equipment separately.

Apparent Power
10000 VA
Active Power
10000 W
Output Power Factor PF
1.0
Topology
Online double-conversion pure sine-wave high-frequency UPS
AC Input Voltage Range
176 ~ 288 VAC (full load)
Nominal DC Output Voltage
220/230/240 VAC

Alarms & troubleshooting

INV_FAULT (Inverter Fault - Bypass Active)
Fault LED solid red, Bypass LED solid amber, Inverter LED off, continuous buzzer
Inverter bridge IGBT driver failure, internal hardware self-test fault, or direct output short circuit forcing transfer to static bypass
1. Review LCD control panel to record active internal fault codes (e.g., Code 02/08). 2. Isolate downstream load branches and inspect distribution panels for dead shorts. 3. Perform a cold reboot after 5 minutes unpowered; if fault persists, replace the power module assembly.
BATT_DISCONN (Battery Disconnected / Breaker Open)
Warning LED solid amber, Battery status LED flashing at 1Hz, 1-second intermittent beep
External battery cabinet (EBC) DC breaker tripped open, battery DC power cable unseated, or internal string DC fuse blown
1. Verify rear panel and external battery cabinet (EBC) circuit breakers are switched to 'ON'. 2. Ensure DC power connectors (Anderson/heavy-duty connectors) are fully mated and secured. 3. Measure open-circuit DC bus voltage across battery terminals; if within range, initiate a manual 'Battery Test' via LCD to clear the alarm.
OUTPUT_OVERLOAD (Output Overload Alarm)
Fault LED solid red, Bypass LED solid amber, LCD load bar full red, rapid 0.5-second buzzer
Total connected load exceeds 100% rated kVA/kW capacity (or exceeded inverse-time curve limits: 105%/130%/150%), triggering bypass transfer
1. Check LCD display to identify actual real-time phase load percentages (L-N kW/kVA). 2. Immediately shed non-essential IT loads until total capacity drops below 80%. 3. Navigate to LCD control menu and select 'Transfer to Inverter' to restore normal on-line operation.
OVERTEMP (Internal Over-Temperature)
Warning LED amber or Fault LED red, LCD displays temperature warning icon, 1-second interval buzzer
Ambient operating temperature exceeds 40°C, front bezel air filter clogged, restricted chassis clearance, or DC cooling fan tachometer failure/stall
1. Remove front bezel and clear dust from air grilles, ensuring minimum 100mm clearance front and rear for unrestricted airflow. 2. Verify datacenter precision cooling status to lower ambient ambient room temperature below 25°C. 3. Check fan RPM status via LCD 'Status - Fan' menu; if RPM is zero or stalled, replace cooling fan module.
BUS_OVERVOLT (DC Bus Overvoltage Lockout)
Fault LED solid red, Inverter LED off, system transfers to bypass or shuts down output, continuous buzzer
Regenerative energy feedback from inductive/capacitive loads, PFC boost rectifier feedback loop failure, or open-circuit failure of DC bus electrolytic capacitors
1. Inspect and isolate downstream regenerative equipment such as motors, dynamic drives, or heavy laser printing loads. 2. Disconnect AC input and battery string; allow 10 minutes for internal high-voltage capacitors to fully discharge. 3. Restart unit in no-load condition; if bus overvoltage recurs immediately, replace the internal PFC rectifier / power stage board.

Access Complete Maintenance & Full Alarm Troubleshooting Manual

This page lists high-frequency critical alarm codes commonly encountered in field maintenance. Comprehensive manufacturer troubleshooting matrices, board-level repair guides, detailed electrical schematics, and firmware commissioning manuals are delivered alongside equipment upon formal project procurement, accompanied by dedicated FAE technical support.

Share on-site information

  1. 01

    Identify the exact model

    Record the nameplate, system model and controller or module model.

  2. 02

    Keep the alarm details

    Record the full alarm text, indicator colour, timing and whether it persists.

  3. 03

    Describe recent changes

    Note recent replacements, software updates or configuration changes.

Record information visible in the existing interface. Electrical measurements, disassembly and replacement should follow the applicable manufacturer's manual and be performed by qualified personnel.

Your model and these details will be added to the enquiry form for you to review before sending.

Related technical articles

Browse the technical guides or send a question about this model.

View all articles

Need a replacement module or supporting equipment?

Confirm the full model, system configuration and compatibility requirements before enquiring about suitable products.

Ask about suitable products

Have a model and an on-site issue?

Share the exact model, alarm text and observed symptoms to help identify relevant information and compatibility requirements.