Shoto / UPS Power & Backup Systems

6-FMX-100B Equipment information & support

RICEWIND Shoto 6-FMX-100B Front Access VRLA Telecom Battery (12V 100Ah 19-Inch Rack Narrow)

Equipment information

Brand
Shoto
Equipment model
6-FMX-100B
Equipment type
UPS Power & Backup Systems
Controller / software version
Confirm against the installed equipment
View full product specifications
RICEWIND Shoto 6-FMX-100B Front Access VRLA Telecom Battery (12V 100Ah 19-Inch Rack Narrow) - View 1

Information below comes from the current product catalogue. Confirm the controller, software version and configuration of the installed equipment separately.

NOMINAL VOLTAGE
12V DC (6-Cell High-Purity Lead Structure)
Rated System Capacity
100Ah @ 10hr-rate (10.8V @ 25°C)
DESIGN LIFE
12-Year Long Design Floating Life (25°C Standard Ambient)
INTERNAL RESISTANCE
≤ 4.5 mΩ (Fully Charged at 25°C Ultra-Low IR)
CASING MATERIAL
High-Strength Flame-Retardant ABS (UL94-V0 Flame Rating)
Physical Form Factor
Front Access Terminal Narrow Form-Factor (19"/23" Cabinets)

Alarms & troubleshooting

BATT_THERMAL_RUNAWAY (Battery Enclosure Bulging & Thermal Runaway Risk)
Power cabinet controller red alarm, temperature sensor triggers high temperature (>50°C) with acid smell
Float voltage temperature compensation unconfigured (-3mV/°C/cell); high ambient heat causes uncontrolled current surge
1. Immediately lower float voltage setting from -53.5V to -51.0V on DC power system and terminate boost charging; 2. Wear safety gloves, trip battery disconnect breaker to isolate bank, and ventilate enclosure; 3. Inspect plastic case for bulging once cooled down; deformed blocks must be permanently decommissioned and replaced.
BATT_INTER_RES_HIGH (Excessive Internal Resistance on Battery Unit)
Monitoring system triggers premature low-voltage drop alert on this specific unit during load discharge
Internal plate grid corrosion, terminal strap micro-fracture, or loose terminal busbar bolt (>6.5 mOhm)
1. Torque all front terminal copper inter-connectors to manufacturer spec (M6 bolt: 11 N*m); 2. Measure internal conductance with calibrated micro-ohmmeter, comparing with baseline (<=4.5 mOhm); 3. If resistance remains >40% above baseline, isolate and replace degraded block with spare unit.
BATT_FLOAT_VOLT_UNBALANCE (Float Charge Voltage Imbalance Across String)
Yellow OBSERVATION LED lit on controller; Battery Monitoring System logs cell voltage delta alarm
Self-discharge variance accumulation across 4S 48V bank, causing some blocks to overcharge (>13.8V) and others to undercharge (<13.2V)
1. Measure open-circuit and float voltage on all 4 blocks, record delta between highest and lowest (norm <= 0.15V); 2. Initiate manual boost equalizing charge cycle (2.35V/cell = 14.1V/block) for 10-12 hours to balance plates; 3. If delta remains >0.3V after equalization, install active Battery Balancer or reorder blocks in series string.

Access Complete Maintenance & Full Alarm Troubleshooting Manual

This page lists high-frequency critical alarm codes commonly encountered in field maintenance. Comprehensive manufacturer troubleshooting matrices, board-level repair guides, detailed electrical schematics, and firmware commissioning manuals are delivered alongside equipment upon formal project procurement, accompanied by dedicated FAE technical support.

Share on-site information

  1. 01

    Identify the exact model

    Record the nameplate, system model and controller or module model.

  2. 02

    Keep the alarm details

    Record the full alarm text, indicator colour, timing and whether it persists.

  3. 03

    Describe recent changes

    Note recent replacements, software updates or configuration changes.

Record information visible in the existing interface. Electrical measurements, disassembly and replacement should follow the applicable manufacturer's manual and be performed by qualified personnel.

Your model and these details will be added to the enquiry form for you to review before sending.

Related technical articles

Browse the technical guides or send a question about this model.

View all articles

Need a replacement module or supporting equipment?

Confirm the full model, system configuration and compatibility requirements before enquiring about suitable products.

Ask about suitable products

Have a model and an on-site issue?

Share the exact model, alarm text and observed symptoms to help identify relevant information and compatibility requirements.

Request technical support