Eltek / DC power systems

Flatpack S 48/1800 HE Equipment information & support

The Eltek Flatpack S 48/1800 HE (Part No. 241122.125) is an ultra-compact shallow-depth high-efficiency telecom rectifier module delivering 1800W (-48V/37.5A) with over 95.5% peak conversion efficiency for space-constrained telecom applications.

Equipment information

Brand
Eltek
Equipment model
Flatpack S 48/1800 HE
Equipment type
DC power systems
Controller / software version
Confirm against the installed equipment
View full product specifications
Flatpack S 48/1800 HE Official Product View 3

Information below comes from the current product catalogue. Confirm the controller, software version and configuration of the installed equipment separately.

AC Input Voltage Range
100 ~ 250 V AC
Physical Dimensions Spec
41.5 (1U) × 109 × 210 mm
Operating Temperature
-40 ~ +85 °C

Alarms & troubleshooting

AC_FAIL (AC Mains Failure / Undervoltage)
Green LED OFF, Yellow LED ON or OFF (Red LED ON on controller if system on battery)
Utility mains blackout; upstream AC MCB tripped; input voltage below 85VAC; damaged chassis AC blind-mate connector pin.
1. Measure AC input terminal voltage using a true-RMS DMM; verify it is within 85–300VAC. 2. Check upstream AC circuit breakers and AC surge protective devices (SPD). 3. Reseat the rectifier module to verify proper engagement with the rear backplane connector.
HVSD / OVP (High Voltage Shutdown / Output Overvoltage)
Green LED OFF, Red Alarm LED Solid ON
Internal voltage loop failure or shorted power components; DC bus transient >59.5VDC; compromised current share causing voltage run-away.
1. Unseat the faulted module from the power shelf for at least 30 seconds to discharge and reset the latch. 2. Measure DC bus voltage to ensure it is within normal float limits (<56.5VDC). 3. Reinsert the module; if the Red LED immediately latches ON, replace the defective rectifier unit.
OVER_TEMP (High Temperature / Thermal Shutdown)
Yellow LED Solid ON (derating); Green LED OFF and Red/Yellow LED ON (shutdown)
Ambient temperature exceeding +65°C; clogged air intake grill or dust filter; chassis ventilation obstructed; HVAC failure.
1. Verify site HVAC operational status to bring ambient temperature below 45°C. 2. Clean front-panel intake perforations and air filters using a vacuum or compressed air. 3. Ensure minimum 100mm clearance front/rear for airflow; unit will auto-recover once heatsink cools down.
FAN_FAIL (Cooling Fan Fault / Speed Error)
Green LED ON, Yellow LED Flashing (1Hz) or Solid ON
Fan rotor mechanically blocked by debris; internal fan connector loose; damaged tachometer Hall sensor; fan bearing degradation causing low RPM.
1. Extract the module and visually inspect the fan rotor for obstructions; manually spin blades to ensure free rotation. 2. Reinsert unit into chassis and verify fan spins up during the initial power-on self-test. 3. If fan remains stationary or continues reporting tachometer faults, replace the fan assembly or rectifier.
CAN_COMM_FAIL (CAN Bus Communication Loss / Comm Timeout)
Green LED ON, Yellow LED Flashing slowly (0.5Hz, autonomous failsafe mode)
Smartpack S controller offline or unresponsive; bent or corroded CAN-H/CAN-L pins on power backplane; missing 120-ohm bus terminator; defective internal CAN transceiver.
1. Verify Smartpack S controller is fully booted, healthy, and showing active rectifiers on the UI. 2. Eject the module and inspect signal contacts for corrosion, debris, or bent pins. 3. Insert into an alternate shelf slot; if communication remains unestablished, replace the module.

Access Complete Maintenance & Full Alarm Troubleshooting Manual

This page lists high-frequency critical alarm codes commonly encountered in field maintenance. Comprehensive manufacturer troubleshooting matrices, board-level repair guides, detailed electrical schematics, and firmware commissioning manuals are delivered alongside equipment upon formal project procurement, accompanied by dedicated FAE technical support.

Share on-site information

  1. 01

    Identify the exact model

    Record the nameplate, system model and controller or module model.

  2. 02

    Keep the alarm details

    Record the full alarm text, indicator colour, timing and whether it persists.

  3. 03

    Describe recent changes

    Note recent replacements, software updates or configuration changes.

Record information visible in the existing interface. Electrical measurements, disassembly and replacement should follow the applicable manufacturer's manual and be performed by qualified personnel.

Your model and these details will be added to the enquiry form for you to review before sending.

Related technical articles

Browse the technical guides or send a question about this model.

View all articles

Need a replacement module or supporting equipment?

Confirm the full model, system configuration and compatibility requirements before enquiring about suitable products.

Ask about suitable products

Have a model and an on-site issue?

Share the exact model, alarm text and observed symptoms to help identify relevant information and compatibility requirements.