| Rated output power | 额定输出功率: 5.4 / 9 / 13.5 / 18 kW |
| Electrical Safety Protection | 电气安全防护等级: IP20 |
| Default charging current | Charge Current: ≤5 / ≤2 / ≤8 / ≤4 / ≤13 A |
| Mains mode efficiency | Mains Mode Efficiency: 最高95 / 最高95.5 % |
| Operating Temperature Range | 工作环境温度范围: 0~50 ℃ |
| ECO mode efficiency | ECO Mode Efficiency: 最高99 % |
| Input power factor | Input Power Factor: ≥0.99 |
| Input frequency range | Input Frequency Range: 40~70 Hz |
| Front and rear installation clearance | Installation Ventilation Clearance: 前后最小200;后方示意间距500 mm |
| Output voltage | 标称直流输出电压: 单相:220 / 230 / 240;三相:380 / 400 / 415 Vac |
| UPS Topology | UPS Topology: 在线式高频双变换,正弦波输出,全数字控制 |
| Earth leakage current | Earth Leakage Current: 3.5~100 mA |
| Input voltage range | 交流输入电压: 相电压:220 / 230 / 240;线电压:380 / 400 / 415 Vac |
| relative humidity | Relative Humidity: 5~95 %RH |
| Parallel Capacity and Redundancy | Parallel Capacity and Redundancy: N + X,1 ≤ N + X ≤ 3,X = 0或1;最高2 + 1冗余 台 |
| Dimensions | 物理结构外形尺寸: 160 × 400 × 350;160 × 500 × 420;160 × 530 × 420 mm |
| Rated battery voltage | Rated Battery Voltage: 192~240 Vdc |
| Display languages | Display Languages: 中文、英文 |
| Rated input frequency | Rated Input Frequency: 50 / 60 Hz |
| Installation method | Installation Method: 建议落地安装,安装于混凝土或其他不燃表面 |
| ECO Mode Applicable Configuration | ECO Mode Applicable Configuration: 单机且配置外部电池;旁路正常时由旁路供电,旁路异常时由逆变器供电 |
| Operating altitude | Operating Altitude: ≤2000 m |
| ECO Voltage Range | ECO Voltage Range: ±5 / ±10 / ±15;默认±10 % |
| Communication interface | Communication Interfaces: 智能卡接口、干接点、RS232、RS485 |
| ECO Frequency Range | ECO Frequency Range: ±1 / ±2 / ±3;默认±3 Hz |
| Battery cold start | Battery Cold Start: 支持 |
| Modbus address range | Modbus Address Range: 1~128;默认1 |
| Shared Battery Full-Load Runtime | Shared Battery Full-Load Runtime: 2~3 min |
| Dynamic Response Recovery Time | Dynamic Response Recovery Time: 60 / 40 ms |
| Dry contact port count | Dry Contact Port Quantity: 3个端口,共6针;标识REPO、1、2 |
| Control functions | Control Functions: 开机、关机、转旁路、告警静音、手动电池测试、故障清除、定时开关机 |
| Recommended Minimum Battery Modules | Recommended Minimum Battery Modules: 10 kVA:至少2组;20 kVA:至少4组 |
| Bypass Voltage Upper Limit | Bypass Voltage Upper Limit: +10 / +15 / +20;默认+20 % |
| Bypass Voltage Lower Limit | Bypass Voltage Lower Limit: -10 / -20 / -30 / -40;默认-40 % |
| Bypass Frequency Range | Bypass Frequency Range: ±5 / ±10;默认±10 Hz |
| Battery String Quantity | Battery String Quantity: 16 / 18 / 20;默认16 块 |
| Battery Backup Time | Battery Backup Time: 6.0 / 7.5 / 9.0 / 11.0 / 14.5 / 19.5 / 29.0 / 48.0 / 100.0 min |
| Battery Equalize Charge | Battery Equalize Charge: 可启用或禁用;默认禁用 |
| Battery Capacity Setting Range | Battery Capacity Setting Range: 7~3000 Ah |
| Battery Module Expansion | Battery Module Expansion: 建议扩展6个电池模块;15 / 20 kVA每次至少增加2个模块 |
| Battery Type | Battery Type: 密封免维护铅酸电池,12 V / 9 Ah |
| Battery Auto-Test Interval | Battery Auto-Test Interval: 禁用 / 8 / 12 / 16 / 20 / 26;默认禁用 周 |
| Output Voltage THD | Output Voltage THD: <2 % |
| Output Voltage Setting | Output Voltage Setting: 220 / 230 / 240;默认220 V |
| Output Current Crest Factor | Output Current Crest Factor: 3:1 |
| Output Overload Capacity | Output Overload Capacity: 105%~125%:10 min;125%~150%:1 min;150%:200 ms |
| Output Frequency Sync Range | Output Frequency Sync Range: 额定频率±3;可设置±0.5~±5 Hz |
| Output Frequency Setting | Output Frequency Setting: 自动频率且允许旁路;自动频率且禁止旁路;50 Hz且禁止旁路;60 Hz且禁止旁路 |
| Output Frequency Slew Rate | Output Frequency Slew Rate: 默认0.5;可设置0.2 / 0.5 / 1 Hz/s |
| Main and Bypass Backfeed Protection | Main and Bypass Backfeed Protection: 具备 |
| Low Battery Warning Time | Low Battery Warning Time: 2~30;默认2 min |
| Protection and Alarm Monitoring | Protection and Alarm Monitoring: 输出短路、旁路反灌、输入中性线缺失、输入异常、整流器过载、逆变器过载、旁路过流、系统过温、风扇故障;电池反接、低电量、电压异常、缺失、测试失败、过温及放电终止关机;内部通信及整流器、DC/DC、直流母线、充电器、辅助电源、逆变器故障;关机状态输出带电、逆变继电器粘连、中性线对地异常;并机通信、电缆、台数、过载、冗余丢失、均流及设置不一致监测;REPO及关机输入监测 |
| Noise Level | Noise Level: <55 / <58 dB |
| Storage Temperature | Storage Temperature: -40~+70 ℃ |
| Conditional Short-Circuit Current Rating | Conditional Short-Circuit Current Rating: 10 kA |
| Battery Discharge Protection Time | Battery Discharge Protection Time: 1~4320;默认4320 min |
| Battery Over-Temperature Alarm Threshold | Battery Over-Temperature Alarm Threshold: 40~60;默认50 ℃ |
| Battery Ambient Temperature | Battery Ambient Temperature: 15~25;标准工作温度20 ℃ |
| Emergency Power Off Function | Emergency Power Off Function: REPO立即关闭整流器、逆变器、逆变及旁路输出、充电与放电 |
| Expected Fan Life | Expected Fan Life: 20000~40000 h |
| Display | Display: 彩色LCD,320 × 240点阵;支持输入、输出、负载、电池、告警及历史记录显示 |
| Energy Saving Modes | Energy Saving Modes: ECO供电模式、智能休眠模式 |
| Operating Modes | Operating Modes: 正常、旁路、电池、ECO、故障、维护旁路 |
| LBS Role Setting | LBS Role Setting: 禁用、主机、从机;默认禁用 |
| RDU-SIC Network Management | RDU-SIC Network Management: IRM / 1-Wire温度、温湿度及干接点传感器接入;告警记录、Trap、电子邮件、短信;Web、SNMP NMS、TCP/IP RDU-Manager、Nform Velocity Server监控及Network Shutdown集成 |
| REPO Interface Supply | REPO Interface Supply: 5 Vdc / 100 mA |
| SIC Network Management | SIC Network Management: TCP/IP及Internet远程监控、计算机安全关机;扩展网络接口最多级联8个温湿度传感器 |
| UNITY-DP Communication Protocols | UNITY-DP Communication Protocols: Web、SNMP、Modbus、BACnet、YDN23 |
| AC Distribution Compatibility | AC Distribution Compatibility: 三相五线A / B / C / N / PE;TN、TT、IT系统 |
| Dual Bus Synchronization | Dual Bus Synchronization: 支持LBS;两套独立单机或并机系统组成主从系统;正常和/或旁路运行 |
| Rear Panel Ports | Rear Panel Ports: Intellislot、REPO、干接点、多功能接口、RS232、交流输入、电池输入、交流输出;部分面板另有并机接口 |
| Auto Restart on Mains Recovery | Auto Restart on Mains Recovery: 可启用或禁用;默认启用 |
| Dry Contact Rating | Dry Contact Rating: 125 Vdc / 0.5 A;30 Vdc / 1 A |
| Dry Contact Input Functions | Dry Contact Input Functions: 电池模式关机、任意模式关机、维护模式;默认维护模式 |
| Dry Contact Output Functions | Dry Contact Output Functions: 低电池、使用电池、使用旁路、UPS故障 |
| Parallel Compatibility Conditions | Parallel Compatibility Conditions: 同容量、同市电电源、公共输出母线、相同参数设置 |
| Parallel Function | Parallel Function: 环形通信冗余;正常与旁路无缝切换;过载消除后自动返回;各机LCD可查询系统总负载 |
| Parallel Communication Cable Quantity | Parallel Communication Cable Quantity: 1 + 1系统:2根;2 + 1系统:3根 |
| Recommended Battery Cable Length | Recommended Battery Cable Length: ≤3 m |
| Control Interface and Protocol | Control Interface and Protocol: 标准RJ45;Modbus / Jbus,或Vertiv温度、温湿度传感器 |
| Smart Card Compatibility | Smart Card Compatibility: SIC、RDU-SIC、RS485、UNITY-DP |
| Battery Sharing Capability | Battery Sharing Capability: 15 / 20 kVA可共享电池串或使用独立电池串;6 / 10 kVA仅可使用独立电池串 |
| Power Terminal Configuration | Power Terminal Configuration: 输入L / N / PE;输出L / N / PE;电池BAT+ / BAT- / PE |
| Auto Restart Delay | Auto Restart Delay: 0~999;默认10 s |
| Input/Output Phase Configuration | Input/Output Phase Configuration: 单进单出或三进单出 |
| Cooling Method | Cooling Method: 内置风扇强制风冷,前进风、后出风 |
| Net Weight | Net Weight: 10.9 / 16.10 / 23.5 kg |
| Mains to Battery Transfer Time | Mains to Battery Transfer Time: 0 ms |
| Inverter to Bypass Transfer Time | Inverter to Bypass Transfer Time: ≤0 ms |