# ZTE ZXDU58 B900 Floor-Standing Telecom DC Power Cabinet System (-48V 900A 2.0m)

RICEWIND · ZTE

https://ricewind.com/en/products/zxdu58-b900

Model: ZXDU58 B900

The ZTE ZXDU58 B900 is an enterprise-grade -48V floor-standing indoor telecom DC power system engineered to deliver up to 900A of high-reliability output power with hot-pluggable high-efficiency rectifiers and intelligent dual-stage Low Voltage Disconnect (LLVD/BLVD) battery management.

## What this product is

The ZXDU58 B900 is an integrated DC power plant comprising three-phase AC distribution, parallel rectifier module slots, a central supervisory unit (CSU), and multi-circuit DC breakers. It operates as the primary source of stable -48VDC power for carrier-grade network equipment while providing comprehensive battery charge/discharge control.

## What problem it solves

Eliminates power continuity loss caused by severe AC grid fluctuations, resolves online expansion risks via robust live hot-plug rectifiers, and prevents irreversible battery bank deep-discharge damage through programmable tiered load shedding.

## Who and where it is for

Carrier core central offices, large mobile transmission aggregation hubs, metro edge data facilities, and railway signaling telecom rooms.

## Core advantages

- High-efficiency rectifier topology achieving system conversion efficiency ≥96.0%.
- Ultra-wide input voltage tolerance (85VAC to 300VAC phase voltage) protecting against utility instability.
- Precision dual-stage LVD (LLVD/BLVD) distribution prevents deep battery depletion while safeguarding critical loads.
- Fully digital CAN-bus autonomous active current sharing with deviation controlled under ±3%.

## Applications

- Telecom operator core central offices and aggregation hub sites
- High-density baseband centralized pooling (C-RAN) hub centers
- Mission-critical railway signaling and dispatch telecommunication power systems
- Enterprise private cloud datacenters requiring resilient -48VDC infrastructure

## Technical specifications

- AC Input Voltage: 80VAC ~ 300VAC (3-Phase 5-Wire 380VAC) VAC
- Cooling System Architecture: Top exhaust fans and module smart thermal cooling
- Smart Monitoring Controller: CSU500B / CSU401S Central Monitoring System
- Nominal Output Voltage: -48VDC (-42V ~ -58V) VDC
- Managed Rectifier Capacity: 18 × ZXD2400 / ZXD3000 Rectifiers
- Rated DC Output Current: 900A (Cabinet Capacity 52.2kW)
- Peak Energy Efficiency: ≥96.2%
- Form Factor Dimensions (HxWxD): 2000 × 600 × 600 mm (2.0m Floor Cabinet)
- Operating Temperature Range: -15°C ~ +55°C

## Frequently asked questions

### How do I choose the right ZXDU58 B900 for my system?

Verify host model, electrical ratings, interface types and protocol requirements. Share your system details with RICEWIND and we will compare compatible options across brands.

### Is ZXDU58 B900 compatible with my existing equipment?

Compatibility depends on power input, pinout signals and rack mounting specifications. Our engineers can review interfaces and integration details before you order.

### Does RICEWIND provide international shipping for ZXDU58 B900?

Yes. RICEWIND ships worldwide; freight options depend on destination, weight and urgency. Contact us for a shipping quote to your site.

### What warranty and after-sales support are available for ZXDU58 B900?

Warranty follows the manufacturer policy for your region. RICEWIND provides technical documentation, firmware guidance and engineer-level assistance throughout the project.

### Does RICEWIND supply ZXDU58 B900?

Yes. RICEWIND supplies ZXDU58 B900 with MOQ from 1 unit; in-stock items dispatch within 24-48 hours with worldwide shipping.

### Is there a cross-reference or equivalent for ZXDU58 B900?

RICEWIND maintains a cross-reference database covering leading telecom and energy infrastructure brands. Contact us for the direct equivalent of ZXDU58 B900.

### How should AC input and DC output cable cross-sectional areas be engineered and calculated for the ZXDU58 B900?

For AC input: When the system operates at full 900A capacity (approx. 48kW at -48V) with phase voltage down to 176VAC, the nominal phase current reaches ~105A; copper conductors rated at not less than 50mm² per phase are required. For DC battery/load cables: Battery circuit breakers typically handle 400A–500A. Applying the DC loop drop formula S = (2 \* L \* I) / (γ \* ΔU) with a maximum permissible loop voltage drop of 0.5V, a 10-meter run at 400A requires dual 95mm² or single 185mm² copper cables with heavy-duty tinned compression lugs.

### How should LLVD (Load Low Voltage Disconnect) and BLVD (Battery Low Voltage Disconnect) thresholds be configured in the CSU to maximize battery life?

For standard 48V VRLA battery banks (24 cells in series): Set LLVD (which sheds non-critical auxiliary loads) to 46.5V–47.0V (approx. 1.94V–1.96V/cell) to preserve remaining capacity for primary core equipment. Set BLVD (which isolates the battery completely to avoid permanent deep-discharge damage) to 43.2V–44.0V (approx. 1.80V–1.83V/cell). If configuring Lithium Iron Phosphate (LiFePO4) batteries, align BLVD with BMS cut-off specifications (typically 44.0V for a 16S configuration).

### What is the operating principle of the Battery Temperature Compensation Coefficient, and how should it be verified in the field?

Electrolyte chemical reactivity increases with temperature; keeping a static float voltage in high ambient temperatures causes overcharging, dry-out, and thermal runaway, while low temperatures lead to undercharging. The CSU dynamically shifts output voltage based on V\_float(T) = V\_ref - (T - 25°C) \* N \* K using readings from external temperature probes. For standard 24-cell VRLA arrays, K is typically configured to -3.0mV to -3.5mV/°C/cell (overall system slope: -72mV/°C to -84mV/°C). The sensor probe must be mechanically attached to the negative terminal or casing midpoint of the warmest battery block in the bank.

### How does the ZXDU58 B900 implement parallel active current sharing across rectifiers, and what is the diagnostic procedure for current-sharing unbalance?

The ZXDU58 B900 employs autonomous digital CAN-bus current sharing. Each rectifier broadcasts its output current to the bus, and internal DSPs dynamically adjust individual PWM loops to maintain current imbalance under ±3% between 10% and 100% rated load. Troubleshooting procedure: 1. Reseat the module and verify that backplane blind-mate pins are intact and free of oxidation; 2. Check the CSU interface to verify that CAN communication with the module is healthy (no comms fault); 3. Verify that the module's target output voltage has not been overridden by software locks; 4. If current remains clipped at maximum or zero regardless of total bus demand, replace the rectifier due to an internal current-sense or DSP circuit defect.