# ZTE ZXD2400 Switch Mode Telecom Rectifier Module (48V 50A)

RICEWIND · ZTE

https://ricewind.com/en/products/zxd2400

Model: ZXD2400

The ZXD2400 is a high-efficiency power system designed for telecommunication facilities and industrial infrastructure.

## What this product is

ZTE ZXD2400 Switch Mode Telecom Rectifier Module -48V 50A features a modular architecture and high-reliability components for simplified maintenance and monitoring.

## What problem it solves

Resolves power conversion inefficiency, confined space constraints, and complex battery lifecycle management.

## Who and where it is for

Suitable for telecom base stations, data centers, edge computing aggregation nodes, and industrial DC applications.

## Core advantages

- Wide AC input range (80-300VAC) with high conversion efficiency exceeding 91% for unstable grids.
- High power density delivering a stable -48VDC output at 2400W/50A to support heavy telecommunication loads.
- Advanced thermal management using variable-speed front-to-rear forced cooling fans for optimal longevity.
- Modular hot-swappable architecture with intelligent remote monitoring to overcome spatial and maintenance constraints.

## Applications

- Telecom 4G/5G macro cellular base stations and distributed remote power sites
- Enterprise-grade cloud data center mission-critical -48V DC power distribution lineups
- Utility power grid dispatch centers and high-voltage substation DC switchgear rooms
- Railway transit signaling, automated train control, and communications equipment rooms

## Technical specifications

- AC input operating range: 80VAC ~ 300VAC (wide-range adaptive)
- DC output voltage: -48VDC (-42V ~ -58V)
- Output power: 2400W
- Conversion efficiency: ≥ 92.5%
- Cooling method: Forced-air cooling with front-intake, rear-exhaust stepless variable-speed fan
- Overall System Efficiency: Up to 96.2% (Gold Standard)
- Acoustic Noise: ≤ 55 dBA (at 25°C ambient load)
- Ingress Protection Rating: IP20 (Indoor Dust & Finger Proof)
- Dielectric Withstand Voltage: 3000VAC Input to Ground (\< 5mA)
- Maximum DC output current: 50A (adjustable current limit)

## Frequently asked questions

### Which ZTE power subracks are compatible with the ZXD2400, and how does it manage mixed-version expansion and current sharing?

The ZXD2400 is fully compatible with ZTE ZXDU68 and ZXDU58 power cabinets as well as standard 19-inch embedded subracks. It supports true live hot-plugging without service interruption. Utilizing an internal autonomous active current-sharing bus, current imbalance is kept within ≤±3% under 50% to 100% load conditions. Both V4.0 and V4.3 hardware versions can be deployed in parallel under unified CSU (Central Supervision Unit) control, facilitating seamless capacity expansion and coordinated battery float/equalize charging routines.

### What are the core electrical specifications and power conversion efficiency of the ZTE ZXD2400 (V4.0/V4.3) rectifier module?

The ZTE ZXD2400 provides a rated output power of 2400W with a nominal -48VDC output (adjustable from -42VDC to -58VDC) and a rated current of 50A (current limit adjustable up to 53A). It accommodates an ultra-wide AC input range of 80VAC to 300VAC, providing full 2400W capacity between 150VAC and 300VAC with linear derating below 150VAC. Powered by a resonant soft-switching topology, it delivers a power factor (PF) ≥ 0.99 and a peak conversion efficiency ≥91%, effectively minimizing thermal dissipation and lowering site PUE.

### What interfaces, networking methods, and autonomous sharing/start-up features are supported by the ZTE ZXD2400 (ZXDU68 T601 system)?

According to the official ZXDU68 T601 system technical documentation: 1. Communication and Monitoring Interfaces: The system supports multiple monitoring networking modes including RS232, RS485, dry contacts, and IP interfaces, along with dry contact and communication alarm signals; 2. Autonomous Operation and Digital Current Sharing: The ZXD2400 rectifier utilizes advanced digital active current-sharing technology, enabling automatic current sharing among modules without requiring a central supervisory unit (CSU); 3. Hot-swap and Soft-start Capabilities: Rectifiers feature non-destructive hot-swapping with integrated input and output soft-start circuits, allowing hot replacement in under 1 minute without causing voltage disturbance on the DC bus.

Content updated: 2026-09-09T16:48:20.154Z