# ZTE ZXDU98 B601 (V5.0) Embedded HVDC Power System (240V 60A Subrack)

RICEWIND · ZTE

https://ricewind.com/en/products/zte-zxdu98-b601-v5-0

Model: ZXDU98 B601 (V5.0)

The ZTE ZXDU98 B601 (V5.0) is a 240V High Voltage DC (HVDC) embedded subrack system delivering 60A/15kW output, engineered for next-generation data centers to minimize power transmission losses.

## What this product is

The ZTE ZXDU98 B601 (V5.0) is a 240V High Voltage DC (HVDC) embedded subrack system delivering 60A/15kW output, engineered for next-generation data centers to minimize power transmission losses.

## What problem it solves

Resolves power grid instability, excessive OPEX energy dissipation, battery degradation, and rack footprint constraints.

## Who and where it is for

5G cellular cell sites, core telecom DC plants, AI data centers, transport networks, and critical industrial DC UPS.

## Core advantages

- 240V HVDC High Efficiency: Slashes transmission line losses by \>80% compared to traditional -48V busbars.
- Carrier-Grade Insulation Safety: Integrated ground-fault insulation monitoring detects micro-leakages instantly.
- Modular Hot-Swap Architecture: Online hot-pluggable HVDC rectifiers ensure zero downtime for critical servers.
- Unified DCIM Integration: Full Ethernet and RS485 telemetry integrates smoothly into data center infrastructure.

## Applications

- Telecom 4G/5G macro cellular base stations and distributed remote power sites
- Enterprise-grade cloud data center mission-critical -48V DC power distribution lineups
- Utility power grid dispatch centers and high-voltage substation DC switchgear rooms
- Railway transit signaling, automated train control, and communications equipment rooms

## Technical specifications

- Rated Distribution Capacity: 60A / 15kW High Voltage Capacity
- AC Input Voltage: 260V - 485V AC (3-Phase Utility)
- System Energy Efficiency: 96%
- Chassis Form Factor: Floor-Standing High-Capacity DC Power System Cabinet
- Insulation Monitoring: Built-in DC Bus Insulation Monitor
- Nominal DC Output Voltage: -48VDC (-42V ~ -58V)
- Overall System Efficiency: Up to 96.2% (Gold Standard)
- Acoustic Noise: ≤ 55 dBA (at 25°C ambient load)
- Ingress Protection Rating: IP20 (Indoor Dust & Finger Proof)
- Dielectric Withstand Voltage: 3000VAC Input to Ground (\< 5mA)

## Frequently asked questions

### What types of IT load equipment are compatible with the ZXDU98 B601 (V5.0)?

It powers 240V HVDC-compliant rack servers, storage arrays, high-density core switches, and telecom core network rigs.

### What special safety protocols apply to wiring 240V HVDC systems?

Certified high-voltage electricians must perform wiring using insulated tools and PPE. Always confirm DC capacitors are discharged.

### How does the hardware protection engage during DC output overvoltage or short circuit?

Features dual sub-millisecond hardware latching: overvoltage triggers immediate output shutdown and latching alarm; short circuits trigger self-recovering hiccup constant current limiting.

Content updated: 2026-09-20T07:45:33.980Z