# ZTE ZXD3000 (V5.8) (50A High-Efficiency Telecom Rectifier Module)

RICEWIND · ZTE

https://ricewind.com/en/products/zte-zxd3000-v5-8

Model: ZXD3000 (V5.8)

The ZXD3000 (V5.8) is a single-phase hot-swappable 3000W -48V DC high-efficiency switch-mode telecom rectifier designed for broad AC input conversions.

## What this product is

A modular power conversion unit embedded within standard telecom DC rack enclosures, combining active PFC with resonant soft-switching topology and CAN communication.

## What problem it solves

Mitigates power disruptions caused by unstable rural grids, high thermal losses in telecom cabinets, and active current share imbalances across parallel arrays.

## Who and where it is for

Cellular base stations, central office transmission facilities, enterprise communication closets, and industrial DC control backup plants.

## Core advantages

- Utilizes advanced PFC and soft-switching resonant topology to achieve a titanium-grade efficiency of up to 96.0%, significantly reducing site power consumption and carbon emissions.
- Supports an ultra-wide AC input voltage range (85VAC to 295VAC) to reliably withstand severe grid fluctuations and ensure power continuity for remote base stations.
- Features built-in intelligent CAN bus communication and advanced current-sharing algorithms for high-precision parallel operation and remote smart O&M.
- Engineered with a -40℃ to +75℃ wide operating temperature range and intelligent front-to-back forced air cooling to seamlessly adapt to extreme outdoor cabinet environments.

## Applications

- Telecom 4G/5G macro cellular base stations and distributed remote power sites
- Enterprise-grade cloud data center mission-critical -48V DC power distribution lineups
- Utility power grid dispatch centers and high-voltage substation DC switchgear rooms
- Railway transit signaling, automated train control, and communications equipment rooms

## Technical specifications

- AC Input Voltage: 85VAC ~ 295VAC
- Operating Efficiency Rating: ≥ 96.0%
- Rated Output Power Capacity: 3000W (60A @ 50VDC)
- Cooling System: Intelligent Front-to-Rear Forced Air Cooling
- Operating Temperature Range: -40°C ~ +75°C
- Nominal DC Output Voltage: -48VDC (-42V ~ -58V)
- Overall System Efficiency: Up to 96.2% (Gold Standard)
- Acoustic Noise: ≤ 55 dBA (at 25°C ambient load)
- Ingress Protection Rating: IP20 (Indoor Dust & Finger Proof)
- Dielectric Withstand Voltage: 3000VAC Input to Ground (\< 5mA)

## Frequently asked questions

### How do I choose the right ZXD3000 (V5.8) for my system?

Verify host model, electrical ratings, interface types and protocol requirements. Share your system details with RICEWIND and we will compare compatible options across brands.

### Is ZXD3000 (V5.8) compatible with my existing equipment?

Compatibility depends on power input, pinout signals and rack mounting specifications. Our engineers can review interfaces and integration details before you order.

### Does RICEWIND provide international shipping for ZXD3000 (V5.8)?

Yes. RICEWIND ships worldwide; freight options depend on destination, weight and urgency. Contact us for a shipping quote to your site.

### What warranty and after-sales support are available for ZXD3000 (V5.8)?

Warranty follows the manufacturer policy for your region. RICEWIND provides technical documentation, firmware guidance and engineer-level assistance throughout the project.

### Does RICEWIND supply ZXD3000 (V5.8)?

Yes. RICEWIND supplies ZXD3000 (V5.8) with MOQ from 1 unit; in-stock items dispatch within 24-48 hours with worldwide shipping.

### Is there a cross-reference or equivalent for ZXD3000 (V5.8)?

RICEWIND maintains a cross-reference database covering leading telecom and energy infrastructure brands. Contact us for the direct equivalent of ZXD3000 (V5.8).

### How should an engineer troubleshoot an illuminated steady red ALM indicator with no DC output on the ZXD3000 (V5.8)?

A steady red ALM LED indicates a critical self-protection latch-out state. Primary causes include: 1) Output Overvoltage Protection (OVP): Triggered when output exceeds ~59.5V DC, latching the converter off; reset by completely de-energizing the AC input breaker for at least 3 minutes to discharge internal bus capacitors. 2) Thermal trip-out: Heatsink thermistors exceed safety thresholds (\>85°C); inspect intake air filters and check for internal fan rotation blockages. 3) AC input anomalies out of the safe window (\<80V AC or \>305V AC). If persistent after re-seating and cold cycling, interrogate the Central Supervision Unit (CSU) for internal hardware fault codes indicating primary PFC or LLC switch degradation.

### What electrical verification procedure must be performed when the CSU reports a CAN communication loss with a ZXD3000 (V5.8)?

1) Physical interface: Unseat the module and inspect the rear hot-plug gold-finger connector pins for mechanical bending, thermal pitting, or contamination. 2) Bus termination impedance: De-energize the rack and measure resistance across CAN\_H and CAN\_L at the backplane test pins; the equivalent resistance should measure between 55Ω and 65Ω (two 120Ω end-of-line resistors in parallel). A reading of ~120Ω signifies a missing termination resistor, while near 0Ω indicates a line short. 3) Signal line voltages: When energized, measure differential DC voltages against chassis ground; CAN\_H should hover around 2.5V–3.5V and CAN\_L around 1.5V–2.5V with dynamic delta toggling. 4) Addressing conflict: Check physical backplane address ID slot identification pins to ensure the module is not reporting an address identical to another parallel node.

### What triggers thermal output derating in the ZXD3000 (V5.8) under high ambient loads, and what are the field mitigation procedures?

Trigger Mechanism: The ZXD3000 (V5.8) delivers 100% rated output (3000W / 50A) up to an ambient intake of +55°C. Between +55°C and +75°C, the DSP implements linear power derating based on NTC readings attached to primary PFC/LLC MOSFET heat bridges to protect semiconductor junction barriers. Complete thermal shutdown trips above +75°C. Corrective Field Actions: 1) Clean or replace intake/exhaust cabinet air filters to eliminate airflow restriction. 2) Verify whether the internal PWM fan scales to maximum RPM under elevated temperature; replace the fan assembly if tachometer feedback fails or bearings drag. 3) Inspect total bus load; if total site demand exceeds the N+1 continuous rating at elevated ambient temperatures, install additional parallel modules in unpopulated shelf slots.

### What is the operational protection and recovery behavior of the ZXD3000 (V5.8) during AC low-voltage dips and phase-loss events?

Operational behavior: The ZXD3000 (V5.8) utilizes single-phase AC input (L/N/PE). From 176V AC to 300V AC, it delivers full 3000W output. When input voltage drops between 80V AC and 176V AC, the unit avoids tripping by initiating a linear input-undervoltage power derating, sustaining roughly 40% to 50% load (~1200W–1500W) at 80V AC. If voltage drops below 80V AC or complete phase loss occurs on its branch feed, the module disconnects via internal soft-stop control, illuminating the yellow mains fault indicator. Recovery: Protection is fully non-latching and autonomous. Once AC input returns above ~85V AC for a continuous 3 to 5-second stabilization window, the internal soft-start routine engages, ramping output voltage smoothly to mitigate inrush currents.

Content updated: 2026-09-15T02:10:10.907Z