# Zhongheng ZHR481800M Telecom-Grade Compact Switch-Mode Rectifier Module (53.5V 33.6A 1800W)

RICEWIND · Zhongheng

https://ricewind.com/en/products/zhongheng-zhr481800m-b30

Model: ZHR481800M

The Zhongheng ZHR481800M is a compact, high-power-density telecom switch-mode rectifier module delivering a nominal output of 53.5V DC (adjustable from 42V to 58V DC) with a maximum rated output current of 33.6A and a continuous power capacity of 1800W.

## What this product is

Architecturally, the ZHR481800M utilizes a two-stage power conversion topology. The front end incorporates a wide-range active PFC boost pre-regulator (PF ≥ 0.99, THD \< 5%), driving an isolated high-frequency DC-DC resonant LLC converter stage that delivers precision-regulated -48V/53.5V power to the DC busbar. Built-in digital control supervisory logic handles closed-loop regulation, CAN/RS485 bus telemetry, and autonomous hardware protection protocols compliant with IEC/EN 60950 and IEC 62368 safety standards.

## What problem it solves

This module mitigates common field power vulnerabilities, including severe utility voltage sags, phase spikes, and high-voltage grid fluctuations up to 300V AC. Its bumpless hot-swappable architecture prevents system downtime during capacity expansion or maintenance, while precision active load sharing eliminates circulating currents among parallel units and extends battery lifespan by suppressing output ripple voltage.

## Who and where it is for

Ideal for 4G/5G wireless macro and small cell base stations, outdoor telecommunications enclosures, optical transport/FTTx nodes, micro edge data center racks, and industrial 48V DC UPS configurations paired with VRLA or lithium-ion backup batteries.

## Core advantages

- Wide input voltage range of 85V~300V AC with active PFC (THD \< 5%, PF ≥ 0.99) ensures reliable operation in harsh grid conditions.
- Advanced two-stage topology combining PFC and full-bridge LLC resonant conversion delivers a peak efficiency of ≥ 94.0%.
- Supports live hot-swappable replacement and high-precision digital current sharing, eliminating parallel circulating currents and downtime.
- Integrated comprehensive protection logic and CSU communication bus fully compliant with IEC/EN 60950 and IEC 62368 safety standards.

## Applications

- 5G wireless macro base station outdoor integrated telecom power enclosures
- Broadband optical access (FTTx) central office racks and optical distribution nodes
- Embedded telecom DC distribution plant capacity expansion and N+1 redundancy systems
- Industrial SCADA communication terminals and railway signaling 48V emergency DC backup

## Technical specifications

- Rated Output Voltage: -48VDC (-42V ~ -58V)
- AC Input Voltage: 85V AC ~ 300V AC
- Maximum Output Current: 33.6A
- Rated Output Power: 1800W
- Maximum Efficiency: ≥ 94.0%
- Operating Temperature Range: -40°C ~ +75°C
- Cooling System: Forced Air Cooling with Intelligent Speed Fan
- Hot-Swappable Support: Yes (Live Hot-Pluggable / Plug-and-Play without Power Interruption)

## Frequently asked questions

### How do I select ZHR481800M for my power system?

Check output voltage, module power rating, efficiency class and compatibility with your existing rectifier shelf or controller. RICEWIND can verify fitment and propose the right quantity.

### Is ZHR481800M compatible with my existing system?

Compatibility depends on the rectifier shelf, controller and communication protocol. Send your current system model to RICEWIND and our engineers will confirm which modules fit.

### Does RICEWIND provide international shipping for ZHR481800M?

Yes. Power modules and systems are packed in anti-static, export-standard crates and shipped worldwide. Delivery time and freight options depend on stock and destination — contact RICEWIND for quotes and lead times.

### What warranty and technical support apply to ZHR481800M?

Warranty follows the manufacturer's policy for the specific equipment. RICEWIND supports testing guidance, replacement requests, spare parts and technical coordination per order terms.

### Does RICEWIND supply ZHR481800M from stock?

Yes. RICEWIND supplies ZHR481800M from verified stock with MOQ from 1 piece; in-stock units dispatch within 24-48 hours with global express air and sea freight.

### Is there a cross-reference or equivalent for ZHR481800M?

RICEWIND maintains a comprehensive cross-reference chart covering Huawei, Vertiv (Emerson), Eltek, ZTE and Delta 48V telecom rectifiers. Contact us for the direct equivalent of ZHR481800M.

### How does the ZHR481800M behave when AC utility input drops below 176V AC?

The ZHR481800M employs an integrated linear power derating algorithm under low AC conditions. It delivers its full 1800W rated capacity between 176V and 300V AC. Between 85V and 176V AC, the module does not trip or shut down; instead, it derates output power proportionately to protect input stage components while maintaining uninterrupted DC bus regulation.

### Does live hot-plugging the rectifier cause arcing or DC bus disturbance to running loads?

No. The module utilizes staggered gold-plated backplane connector pins alongside an inrush current suppression circuit. The grounding pins mate first and disengage last, while soft-start sequencing prevents arcing and voltage transients, ensuring zero disruption to live connected telecommunications equipment on the 53.5V bus.

### What is the troubleshooting procedure if the fan fault LED illuminates?

First inspect the module front intake and rear exhaust grills for debris or clogged air filters. Next, pull the module and verify that the fan blades spin freely without mechanical obstruction or bearing seizure. If the airflow path is clear and restarting the unit continues to trigger a fan lock alarm, the tachometer feedback circuit or brushless motor has failed, requiring unit swap and depot servicing.

### Can the module operate autonomously if communication with the Central Supervisory Unit (CSU) is lost?

Yes. Upon loss of supervisory communication, the ZHR481800M drops back to its autonomous hardware default state. It maintains a constant 53.5V DC output with default current limits, and its internal analog/digital current-sharing bus continues balancing load current evenly across adjacent parallel modules.

Content updated: 2026-09-16T13:39:46.245Z