# Vertiv R48-4000e High-Density Carrier-Grade High-Power Telecom Rectifier Module (-48V 83.3A 4000W)

RICEWIND · Vertiv

https://ricewind.com/en/products/vertiv-r48-4000e-b29

Model: R48-4000e

The Vertiv R48-4000e is a high-density, carrier-grade switch-mode telecom rectifier module rated at -48V DC, 83.3A with a maximum output capacity of 4000W. Designed for converting utility AC (85V AC to 300V AC) to regulated DC power with a peak efficiency exceeding 96.0%, it delivers robust, uninterrupted power for high-capacity telecom central offices and enterprise data hubs.

## What this product is

Architecturally, the R48-4000e utilizes full DSP-controlled conversion. The front-end power factor correction stage ensures near-unity power factor (\>0.99) and low total harmonic distortion (THD \<5%), feeding a resonant LLC full-bridge DC-DC converter for minimal switching losses. It connects to the subrack via an integrated blind-mate interface handling DC power, AC input, alarms, and dual CAN bus communications, compliant with international telecom EMC and safety standards.

## What problem it solves

It eliminates equipment vulnerability caused by AC utility sags and surges through a wide operating voltage window; cuts operational expenditure (OPEX) and cooling overhead via high-efficiency conversion (≥96.0%); maximizes subrack power density to reclaim costly rack units in space-constrained sites; and prevents system-level service outages via live hot-swappable active load sharing.

## Who and where it is for

Ideal for 5G macro core central offices, mobile switching centers (MSCs), high-density data center telecom rows, fiber optical transmission terminals, and Vertiv NetSure 701/801 series power cabinets demanding N+1 or N+M carrier-grade redundancy.

## Core advantages

- Bridgeless PFC and LLC resonant topology yield up to 96.0% peak efficiency, reducing data center PUE.
- Delivers 4000W (-48V/83.3A) high-density output, minimizing rack footprint and slot occupation.
- Supports live hot-swappable operation and CAN bus intelligent current sharing for zero downtime.
- Wide input voltage range and robust EMC protection withstand harsh grid surges and fluctuations.

## Applications

- Carrier 5G/4G central switching centers, telecom aggregation nodes, and transmission core sites
- Enterprise and colocation data center -48V DC power distribution cabinets and top-of-rack solutions
- Capacity upgrades, expansion, and spare-part maintenance in Vertiv NetSure 701 and 801 systems
- Rail transit signaling stations, electric utility substations, and industrial SCADA emergency DC power

## Technical specifications

- Maximum Output Current: 83.3A
- AC Input Voltage: 85V AC ~ 300V AC
- Rated Output Power: 4000W
- Rated Output Voltage: -48VDC (-42V ~ -58V)
- Maximum Efficiency: ≥ 96.0%
- Operating Temperature Range: -40°C ~ +75°C
- Cooling System: Forced Air Cooling with Intelligent Speed Fan
- Hot-Swappable Support: Yes (Live Hot-Pluggable / Plug-and-Play without Power Interruption)

## Frequently asked questions

### How do I select R48-4000e for my power system?

Check output voltage, module power rating, efficiency class and compatibility with your existing rectifier shelf or controller. RICEWIND can verify fitment and propose the right quantity.

### Is R48-4000e compatible with my existing system?

Compatibility depends on the rectifier shelf, controller and communication protocol. Send your current system model to RICEWIND and our engineers will confirm which modules fit.

### Does RICEWIND provide international shipping for R48-4000e?

Yes. Power modules and systems are packed in anti-static, export-standard crates and shipped worldwide. Delivery time and freight options depend on stock and destination — contact RICEWIND for quotes and lead times.

### What warranty and technical support apply to R48-4000e?

Warranty follows the manufacturer's policy for the specific equipment. RICEWIND supports testing guidance, replacement requests, spare parts and technical coordination per order terms.

### Does RICEWIND supply R48-4000e from stock?

Yes. RICEWIND supplies R48-4000e from verified stock with MOQ from 1 piece; in-stock units dispatch within 24-48 hours with global express air and sea freight.

### Is there a cross-reference or equivalent for R48-4000e?

RICEWIND maintains a comprehensive cross-reference chart covering Huawei, Vertiv (Emerson), Eltek, ZTE and Delta 48V telecom rectifiers. Contact us for the direct equivalent of R48-4000e.

### How does the Vertiv R48-4000e respond when the input AC voltage drops below 176V AC?

The module implements an intelligent input undervoltage derating profile. It provides its full rated 4000W power between 176V AC and 300V AC. When the input voltage drops into the 85V AC to 176V AC band, the internal controller limits output current linearly down to approximately 40%–50% of rated capacity. This shields input stage semiconductors from overcurrent while maintaining active DC bus regulation.

### What is indicated when the module front panel displays a steady yellow LED?

A solid yellow LED indicates an active alarm condition that has not yet caused an emergency shutdown. Common triggers include AC input over/undervoltage out of range, internal ambient over-temperature inducing thermal foldback, or fan speed tachometer errors. Query the NetSure NCU or M500S controller alarm log to retrieve the specific register code before conducting physical inspections.

### What is the recommended procedure for hot-swapping an R48-4000e module in a live system?

First, unfasten the locking screw and pull the module's extraction handle outward to disengage the internal retention latch. Slide the module smoothly out along the subrack guides. When inserting the new module, ensure the handle is open, align with the guide rails, slide firmly inward until the blind-mate backplane connector seats completely, then press and lock the handle. The module initializes within seconds via CAN negotiation.

### What root causes typically explain poor current sharing between multiple R48-4000e units in parallel?

Improper current sharing typically stems from: 1) CAN bus communication breakdown caused by bent backplane pins or address conflicts; 2) Misconfigured current-limit settings on the host controller; 3) Mismatched firmware revisions across rectifiers; or 4) Oxidation/dirt on the rear power blade contacts causing an abnormal localized contact resistance. Inspect the CAN link and clean connector surfaces.

Content updated: 2026-09-16T11:22:01.102Z