# Vertiv Emerson PSS48100-2 Embedded Switch-Mode DC Power System (-48V 100A 2U)

RICEWIND · Vertiv

https://ricewind.com/en/products/pss48100-2

Model: PSS48100-2

The Vertiv PSS48100-2 is a compact 19-inch 2U embedded -48VDC power supply system delivering up to 100A continuous output, engineered for telecom access networks, base stations, and outdoor enclosures.

## What this product is

The Vertiv PSS48100-2 integrates AC input distribution, DC load distribution, an advanced system monitoring unit, and modular rectifier slots to convert unstable grid power into regulated -48VDC while maintaining optimal battery backup operation.

## What problem it solves

Resolves spatial constraints in edge telecom cabinets, system degradation caused by wide grid voltage sags/surges, and battery pre-aging caused by inaccurate charge temperature compensation.

## Who and where it is for

4G/5G mobile edge sites, Radio Access Networks (RAN), optical line terminals (OLT), enterprise telecom shelters, and industrial outdoor power enclosures.

## Core advantages

- Wide AC input range (85VAC to 300VAC) ensuring continuous operation in unstable grids
- High conversion efficiency (≥96.0%) reducing system thermal load and power dissipation
- Compact 2U form factor integrating AC/DC distribution and hot-pluggable rectifiers
- Independent LLVD and BLVD dual-priority low-voltage disconnect circuits to safeguard batteries

## Applications

- Cellular base station BBU/RRU power distribution
- FTTH/FTTx optical transmission and aggregation nodes
- Outdoor integrated telecom power cabinets
- Railway communication, signaling, and remote telemetry points

## Technical specifications

- Smart Monitoring Controller: PSM-B2 / M221S Central Controller
- Cooling System Architecture: Temperature-regulated air cooling
- AC Input Voltage: 85VAC ~ 300VAC (Nominal 220VAC) VAC
- Nominal Output Voltage: -48VDC (-42V ~ -58V) VDC
- Managed Rectifier Capacity: 2 Slots for HD4850-2 / R48-2900U Modules
- Rated DC Output Current: 100A (System Capacity 4.8kW)
- Form Factor Dimensions (HxWxD): 88 (2U) × 482 × 320 mm
- Peak Energy Efficiency: ≥95.5%
- Operating Temperature Range: -40°C ~ +65°C

## Frequently asked questions

### How do I choose the right PSS48100-2 for my system?

Verify host model, electrical ratings, interface types and protocol requirements. Share your system details with RICEWIND and we will compare compatible options across brands.

### Is PSS48100-2 compatible with my existing equipment?

Compatibility depends on power input, pinout signals and rack mounting specifications. Our engineers can review interfaces and integration details before you order.

### Does RICEWIND provide international shipping for PSS48100-2?

Yes. RICEWIND ships worldwide; freight options depend on destination, weight and urgency. Contact us for a shipping quote to your site.

### What warranty and after-sales support are available for PSS48100-2?

Warranty follows the manufacturer policy for your region. RICEWIND provides technical documentation, firmware guidance and engineer-level assistance throughout the project.

### Does RICEWIND supply PSS48100-2?

Yes. RICEWIND supplies PSS48100-2 with MOQ from 1 unit; in-stock items dispatch within 24-48 hours with worldwide shipping.

### Is there a cross-reference or equivalent for PSS48100-2?

RICEWIND maintains a cross-reference database covering leading telecom and energy infrastructure brands. Contact us for the direct equivalent of PSS48100-2.

### How do you correctly size the DC load and battery loop cables for the Vertiv PSS48100-2?

Sizing must satisfy both current-carrying capacity and maximum voltage drop limits. Per telecom standards, total loop voltage drop must remain below 0.5V at full load (100A) over a typical one-way run. Calculated via S = (2 \* L \* I) / (γ \* ΔU), where γ is copper conductivity (~57 m/(Ω·mm²)), battery connections for 100A service require multi-strand copper cables of at least 25 mm² to 35 mm² with properly crimped, heat-shrink-insulated lugs.

### What are the recommended engineering setpoints for LLVD and BLVD thresholds on the PSS48100-2 controller?

For standard 48V VRLA battery strings (24 cells), configure LLVD (Load Low Voltage Disconnect for non-critical loads) to -44.0VDC (~1.83V/cell) with a 5-10 second debounce delay. Set BLVD (Battery Low Voltage Disconnect for total system isolation) to -43.2VDC (~1.80V/cell). If using LiFePO4 batteries, set BLVD to -40.5VDC ~ -42.0VDC to harmonize with the onboard BMS cut-off curve and prevent irreversible cell undervoltage locking.

### How is battery temperature compensation calculated and configured, and how does it differ across chemistries?

Electrochemical activity in VRLA batteries increases with temperature; float voltage must decrease to avoid thermal runaway: V\_float = V\_nominal - (T\_actual - 25°C) \* N\_cells \* Coeff. For 24-cell VRLA strings, typical coefficients are -3.0 to -5.0 mV/°C/cell (amounting to -72 to -120 mV/°C across the -48V bus). When lithium (LiFePO4) batteries with internal BMS communication are used, disable temperature compensation completely (set to 0 mV/°C/cell) to prevent DC bus drift from tripping battery BMS protection thresholds.

### How should field engineers troubleshoot active current sharing imbalances exceeding 5% between rectifier modules?

Step 1: Verify CAN bus communication health and check for duplicate rectifier slot addresses on the controller. Step 2: Inspect module backplane blind-mate connectors for mechanical misalignment, bent pins, or high contact resistance, then reseat modules firmly. Step 3: Isolate modules into standalone mode and verify that their unadjusted DC output float potentials match within ±50mV using a calibrated DMM. Step 4: Swap problematic rectifiers into known good slots to isolate whether the failure stems from a damaged backplane share bus or a compromised internal current-share operational amplifier circuit.