# Potevio DMA14-4850A Industrial Carrier-Grade Telecom Rectifier Module (-48V 50A 2900W)

RICEWIND · Potevio

https://ricewind.com/en/products/potevio-dma14-4850a-b31

Model: DMA14-4850A

The Potevio DMA14-4850A is an industrial carrier-grade high-frequency switch-mode telecom rectifier module delivering a rated -48V DC output (adjustable from -43V to -58V DC) with a maximum current of 50A and a rated output capacity of 2900W. Engineered for central offices, cellular base stations, and demanding industrial networking enclosures, it converts erratic single-phase AC utility or diesel generator feeds into clean, regulated DC bus power for sensitive telecommunication loads and battery float/boost management.

## What this product is

Architecturally, the DMA14-4850A is structured around a two-stage conversion platform. The front-end active PFC stage boosts single-phase AC input into a stabilized high-voltage DC intermediate rail while maintaining a power factor greater than 0.99 and minimizing total harmonic distortion (THD). The isolated rear stage utilizes a high-frequency full-bridge/half-bridge resonant DC-DC converter with planar transformer technology and synchronous rectification to achieve tight output regulation and dynamic load response. Internal management is handled by a dedicated Digital Signal Controller (DSC) that handles pulse-width modulation, thermal feedback, autonomous active bus sharing, and comprehensive reporting over an integrated serial interface in compliance with global telecom standards like YD/T 731 and IEC 60950.

## What problem it solves

This unit eliminates operational downtime caused by severe grid brownouts, utility sags, and transient line surges typical in peripheral rural sites. It mitigates module-to-module circulating currents and thermal stress imbalances common in large parallel rectifier banks through precision active load sharing. Furthermore, its ultra-low ripple voltage and rigorous EMI filtering prevent high-frequency carrier-band noise from corrupting RF transceivers and optical line terminals while protecting lead-acid or lithium battery systems against uncontrolled overvoltage spikes.

## Who and where it is for

Tailored for mobile base transceiver stations (macro 3G/4G/5G and distributed RRU sites), optical transport network (OTN/DWDM) nodes, microwave transmission hubs, utility substation SCADA/teleprotection setups, and industrial -48V DC plant racks requiring hot-swappable N+1 redundant architectures.

## Core advantages

- Wide AC input range (90V-290V) with integrated active PFC achieves \>0.99 power factor, reliably combating severe grid voltage sags and surges in remote sites.
- Advanced two-stage topology (APFC + resonant DC-DC) driven by digital control delivers \>92.5% peak efficiency for stable 2900W continuous output.
- Precision digital current-sharing and isolated CAN/RS485 communication eliminate parallel circulating currents, strictly complying with YD/T 731 standards.
- Rugged industrial design (-25°C to +65°C) with superior EMI suppression ensures zero-interruption power for telecom loads during extreme lightning and grid faults.

## Applications

- Carrier-grade 4G/5G macro cell sites and distributed antenna systems (DAS) embedded power subracks
- Central telecom switching centers, optical transmission equipment rooms, and core router DC power distributions
- Railway signaling, trackside communications, and wayside automated control systems requiring robust -48V backup
- Electric power utility substations providing isolated telecom and RTU control bus supply under harsh high-EMC environments

## Technical specifications

- AC Input Voltage: 90V AC ~ 290V AC
- Maximum Output Current: 50A
- Rated Output Power: 2900W
- Rated Output Voltage: -48VDC (-42V ~ -58V)
- Maximum Efficiency: ≥ 92.5%
- Operating Temperature Range: -40°C ~ +75°C
- Cooling System: Forced Air Cooling with Intelligent Speed Fan
- Hot-Swappable Support: Yes (Live Hot-Pluggable / Plug-and-Play without Power Interruption)

## Frequently asked questions

### How do I select DMA14-4850A for my power system?

Check output voltage, module power rating, efficiency class and compatibility with your existing rectifier shelf or controller. RICEWIND can verify fitment and propose the right quantity.

### Is DMA14-4850A compatible with my existing system?

Compatibility depends on the rectifier shelf, controller and communication protocol. Send your current system model to RICEWIND and our engineers will confirm which modules fit.

### Does RICEWIND provide international shipping for DMA14-4850A?

Yes. Power modules and systems are packed in anti-static, export-standard crates and shipped worldwide. Delivery time and freight options depend on stock and destination — contact RICEWIND for quotes and lead times.

### What warranty and technical support apply to DMA14-4850A?

Warranty follows the manufacturer's policy for the specific equipment. RICEWIND supports testing guidance, replacement requests, spare parts and technical coordination per order terms.

### Does RICEWIND supply DMA14-4850A from stock?

Yes. RICEWIND supplies DMA14-4850A from verified stock with MOQ from 1 piece; in-stock units dispatch within 24-48 hours with global express air and sea freight.

### Is there a cross-reference or equivalent for DMA14-4850A?

RICEWIND maintains a comprehensive cross-reference chart covering Huawei, Vertiv (Emerson), Eltek, ZTE and Delta 48V telecom rectifiers. Contact us for the direct equivalent of DMA14-4850A.

### Why does the DMA14-4850A limit its output current or power when the AC mains drop below 176V AC? Is this an internal defect?

This is an intentional design safeguard known as linear input-voltage derating, not a defect. Between 176V AC and 290V AC, the module delivers its full 2900W (50A at -58V DC) capacity. When line voltage falls between 90V AC and 176V AC, internal input current would naturally surge to maintain output power, exposing the PFC inductors and primary MOSFETs to excessive thermal stress. The controller linearly clamps output power to protect these internal power semiconductors while keeping the connected loads fully online without dropping the DC bus.

### What primary diagnostics should be executed if the rectifier triggers an amber Alarm LED and indicates a current-sharing failure?

First, visually inspect the rear blind-mate multi-pin connector for bent pins, physical contaminants, or an incomplete seating latch inside the subrack slot. Second, verify the integrity of the analog/CAN current-share bus printed trace on the backplane, confirming that no termination resistor is missing or shorted. Third, measure the standalone output float voltages using an accurate digital multimeter; a calibration drift exceeding 300mV between modules will force the active sharing loop into saturation. If a single module fails to supply its share of current on a bench test, the internal current-sense amplifier or control daughterboard has likely degraded.

### The module enters a locked-out state with a solid red fault LED and zero DC output following an overvoltage event. How is it properly reset?

The DMA14-4850A utilizes a redundant, hardware-enforced output overvoltage protection (OVP) circuit that latches off the gate drive pulses to prevent catastrophic overvoltage onto connected communication hardware (typically set between 59V and 60V DC). To reset the module, isolate it completely by opening its corresponding AC input breaker or hot-extracting it from the shelf. Allow at least 3 minutes for the internal high-voltage bulk electrolytic capacitors to discharge fully (verified when all LEDs extinguish), then reinsert or power up. If the latch reappears immediately upon power-up, an internal optocoupler feedback loop or secondary synchronous stage has failed, requiring unit depot repair.

### In dusty or humid field enclosures, the cooling fan produces abnormal noise or trips an internal fan fail alarm. What is the correct field procedure?

The integrated brushless DC fan features an internal tachometer (FG signal) monitored directly by the digital microcontroller. If dust accumulation causes bearing seizure or increases aerodynamic resistance such that RPM falls below safety thresholds, the module safely throttles or trips to prevent thermal runaway. Field personnel should pull the module out under hot-swap protocol, blow low-pressure dry industrial air through the heatsink channels from rear to front, and verify the impeller spins freely without mechanical runout. If the bearing is dry, noisy, or electrical tachometer output remains missing, replace the modular fan tray with an original OEM-rated component.

Content updated: 2026-09-17T01:30:13.714Z