# Vertiv NetSure 731 A61-S4 High-Capacity Subrack DC Power System (-48V 600A 6U)

RICEWIND · Vertiv

https://ricewind.com/en/products/netsure-731-a61-s4

Model: NetSure 731 A61-S4

The Vertiv NetSure 731 A61-S4 is a high-density 11U rack-mount -48VDC telecom power subrack engineered to house up to 10 high-efficiency R48-3200e or R48-3500e rectifiers, delivering up to 600A output.

## What this product is

It is a fully integrated telecom-grade subrack combining AC input distribution, DC power distribution, an intelligent supervisory controller (M530S or M830B), and rectifier slots into an 11U 19-inch form factor, designed for demanding telecom architectures.

## What problem it solves

Solves space-constrained macro site distribution issues, minimizes energy conversion losses with 96%+ efficiency, and prevents catastrophic battery depletion via independent LLVD and BLVD contactor schemes.

## Who and where it is for

Telecommunication central offices, wireless macro cellular base stations (4G/5G), optical transmission repeater hubs, and enterprise telecom rooms.

## Core advantages

- Ultra-High Density Integration: Compact 6U rack delivers up to 600A/28.8kW DC output, solving spatial constraints in high-density telecom rooms.
- Wide Grid Adaptability & High Efficiency: Supports 85VAC-300VAC ultra-wide input voltage with peak efficiency up to 96.5% for grid stability.
- Multi-Level Smart Load Shedding: Features dual-stage LLVD and BLVD low-voltage disconnect to prioritize critical loads and extend battery life.
- Comprehensive Intelligent Management: Equipped with advanced NCU/M830B controllers supporting remote SNMP management and automated O&M.

## Applications

- Telecom 4G/5G macro cellular base stations and distributed remote power sites
- Enterprise-grade cloud data center mission-critical -48V DC power distribution lineups
- Utility power grid dispatch centers and high-voltage substation DC switchgear rooms
- Railway transit signaling, automated train control, and communications equipment rooms

## Technical specifications

- Cooling System Architecture: Isolated duct forced air cooling
- AC Input Voltage: 85VAC ~ 300VAC (3-Phase 5-Wire 380VAC) VAC
- Smart Monitoring Controller: NCU / M830B Central Monitoring System
- Nominal Output Voltage: -48VDC (-42V ~ -58V) VDC
- Managed Rectifier Capacity: 6 Slots for R48-3200e / R48-3500e3 Modules
- Rated DC Output Current: 600A (System Capacity 28.8kW)
- Form Factor Dimensions (HxWxD): 266 (6U) × 482 × 380 mm
- Peak Energy Efficiency: ≥96.5%
- Operating Temperature Range: -40°C ~ +65°C

## Frequently asked questions

### How do I choose the right NetSure 731 A61-S4 for my system?

Verify host model, electrical ratings, interface types and protocol requirements. Share your system details with RICEWIND and we will compare compatible options across brands.

### Is NetSure 731 A61-S4 compatible with my existing equipment?

Compatibility depends on power input, pinout signals and rack mounting specifications. Our engineers can review interfaces and integration details before you order.

### Does RICEWIND provide international shipping for NetSure 731 A61-S4?

Yes. RICEWIND ships worldwide; freight options depend on destination, weight and urgency. Contact us for a shipping quote to your site.

### What warranty and after-sales support are available for NetSure 731 A61-S4?

Warranty follows the manufacturer policy for your region. RICEWIND provides technical documentation, firmware guidance and engineer-level assistance throughout the project.

### Does RICEWIND supply NetSure 731 A61-S4?

Yes. RICEWIND supplies NetSure 731 A61-S4 with MOQ from 1 unit; in-stock items dispatch within 24-48 hours with worldwide shipping.

### Is there a cross-reference or equivalent for NetSure 731 A61-S4?

RICEWIND maintains a cross-reference database covering leading telecom and energy infrastructure brands. Contact us for the direct equivalent of NetSure 731 A61-S4.

### How should DC output cables be sized for NetSure 731 A61-S4 to adhere to telecom voltage drop limits?

DC cross-sectional cable area (S) is calculated via S = (2 × L × I) / (γ × ΔV), where L is the single-run distance in meters, I is maximum branch circuit load in amps, γ is conductivity (copper = 57 m/(Ω·mm²)), and ΔV is allowable loop voltage drop (standard telecom standard is ≤ 0.5V total drop). Additionally, cable continuous ampacity must exceed 125% of the upstream circuit breaker rating.

### What are the recommended engineering thresholds for LLVD and BLVD settings on NetSure 731 A61-S4?

For standard 48V lead-acid strings (24 × 2V cells), LLVD (Load Low Voltage Disconnect) is configured at 46.0V–46.5V to disconnect non-critical branch circuits early. BLVD (Battery Low Voltage Disconnect) is configured at 43.2V–44.0V (approx. 1.80V–1.83V per cell) to avoid permanent sulfation or chemical collapse. For LiFePO4 battery systems, set BLVD to 44.5V–45.0V or control disconnection directly via BMS hardware contactor commands.

### How is battery temperature compensation programmed, and how does the system behave if the temperature sensor fails?

The coefficient is programmed in the controller (e.g., M830B) at typically -3mV/°C/cell for lead-acid strings (-72mV/°C total for a 24-cell string) referenced to 25°C, bounded by strict clamp voltages (e.g., maximum 56.4V, minimum 52.5V). If the temperature sensor exhibits an open or short circuit, the controller triggers a sensor failure alarm, immediately suspends dynamic compensation, and locks the float output at the nominal 25°C setpoint (typically 53.5V) to eliminate thermal runaway risks.

### How should excessive parallel current-sharing imbalance among R48-3200e rectifiers be debugged on-site?

Rectifier active current sharing imbalance should remain within ≤±5% between 50% and 100% of nominal load. Troubleshooting procedure: 1. Verify CAN-bus communication integrity and check for bus termination or framing errors on the controller interface; 2. Extract suspect rectifiers and inspect rear gold-finger connectors and subrack backplane pins for oxidation, damage, or poor seating; 3. Confirm matching firmware builds across all installed rectifiers; 4. Measure DC output contact resistance to the main busbar to isolate localized drop discrepancies; 5. If an individual rectifier cannot adjust its internal PWM regulation via CAN reference, replace the faulty rectifier module.