# Vertiv NetSure 731 A41-S2 Subrack Telecom Power System -48 V 150 A 4U

RICEWIND · Vertiv

https://ricewind.com/en/products/netsure-731-a41-s2

Model: NetSure 731 A41-S2

A 19-inch -48 V DC power system combining distribution, up to four R48-3000e3 rectifier modules and an M221S or M222S controller.

## What this product is

This 19-inch subrack power system integrates AC/DC conversion, DC distribution and system monitoring. The A41-S2 configuration uses an M221S or M222S controller and accommodates up to four R48-3000e3 rectifier modules.

## What problem it solves

It provides a regulated -48 V DC supply and organized load and battery connections for telecommunications equipment, within a maximum DC load output of 150 A.

## Who and where it is for

Suitable for telecommunications power installations requiring a 19-inch subrack, -48 V DC output and integrated distribution, with up to four R48-3000e3 rectifier modules.

## Core advantages

- Up to four R48-3000e3 rectifier modules
- Maximum DC load output of 150 A and battery charging current up to 56 A
- System efficiency at least 94.5%; rectifier module peak efficiency 95.5%
- Integrated distribution and M221S/M222S monitoring in a 19-inch subrack

## Applications

- -48 V DC power and distribution for telecommunications equipment
- 19-inch subrack telecommunications power installations

## Technical specifications

- Product type: 19-inch subrack power system with distribution, rectifier modules and controller
- Rectifier module configuration: R48-3000e3, up to 4 modules
- Controller: M221S / M222S
- AC input configuration: Single-phase L+N+PE, 220 Vac
- AC input voltage range: 85-300 Vac
- AC input frequency: 45-65 Hz
- Power factor: ≥0.99
- Maximum AC input current: ≤74 A, including 10 A AC output
- Nominal DC output voltage: -48 Vdc
- DC output voltage range: -43.2 to -57.6 Vdc
- Default output voltage: -53.5 Vdc; -54 Vdc with an Emerson outdoor cabinet
- Maximum DC load output current: ≤150 A
- Maximum battery charging current: ≤56 A
- Efficiency: System: ≥94.5%; rectifier module peak: 95.5%
- Voltage regulation accuracy: ≤1%
- Parallel current-sharing imbalance: Better than ±5%
- Psophometric noise: ≤2 mV (300-3400 Hz)
- Peak-to-peak noise: ≤200 mV (0-20 MHz)
- Priority load branches (PL): 32 A/1P × 2; 16 A/1P × 2
- Non-priority load branches (NPL): 63 A/1P × 2; 32 A/1P × 4; 16 A/1P × 2
- Battery breakers: 2 × 125 A/1P
- Surge protection devices: 1 AC and 1 DC
- Dry contacts: W2453X1 interface board: 1 standard board provides DO1-DO4; up to 2 boards for DO1-DO8
- Communication interface: RS232; M222S controller has no Ethernet interface
- Hot-swap: Lossless hot-swap supported; replacement time \<1 min
- Subrack dimensions (W × D × H): 483 × 390 × 178 mm
- Subrack weight: ≤15 kg, excluding packaging, rectifier modules and controller
- Operating temperature: -5 to +40 °C
- Storage temperature: -40 to +70 °C
- Relative humidity: 5%-95%
- Operating altitude: ≤2000 m; derating required above this altitude
- Mean time between failures: \>200000 h
- Acoustic noise: ≤60 dB(A)
- Electromagnetic compatibility: Conducted emissions EN 55022 Class A; immunity EN/IEC 61000-4-2/-3/-4/-5/-6
- Safety standards: IEC 60950-1; designed to UL, CE and NEBS safety requirements
- Front service clearance: ≥800 mm

## Frequently asked questions

### What is the maximum DC load output of the Vertiv NetSure 731 A41-S2?

The maximum DC load output current is 150 A.

### Which rectifier modules are supported by the Vertiv NetSure 731 A41-S2?

It supports up to four R48-3000e3 rectifier modules.

### What is the DC output voltage range of the Vertiv NetSure 731 A41-S2?

The output voltage range is -43.2 to -57.6 Vdc; the nominal output is -48 Vdc.

### What AC input does the Vertiv NetSure 731 A41-S2 require?

It uses single-phase L+N+PE, 220 Vac, accepts 85-300 Vac at 45-65 Hz, and has a maximum AC input current of 74 A including the 10 A AC output.

### What are the dimensions and weight of the Vertiv NetSure 731 A41-S2 subrack?

The subrack measures 483 × 390 × 178 mm and weighs up to 15 kg excluding packaging, rectifier modules and controller.

Content updated: 2026-09-15T02:09:46.789Z