# Vertiv NetSure 212 C23-S2 Embedded DC Power System 40A

RICEWIND · Vertiv

https://ricewind.com/en/products/netsure-212-c23-s2

Model: NetSure 212 C23-S2

The NetSure 212 C23-S2 is a 2U, 19-inch rack-mounted -48VDC subrack power system engineered to deliver up to 120A output using high-efficiency hot-swappable rectifiers and an advanced controller.

## What this product is

The Vertiv NetSure 212 C23-S2 is an integrated DC subrack designed for telecommunications applications requiring reliable -48V power. It consolidates AC input connections, DC distribution breakers, low-voltage disconnects (LLVD and BLVD), R48-series rectifier slots, and the M221S/M222S supervision unit within a space-efficient 2U chassis.

## What problem it solves

Eliminates operational downtime caused by space constraints in outdoor edge enclosures, extreme AC voltage spikes/sags, and unmanaged battery depletion during extended power outages.

## Who and where it is for

4G/5G small cells, optical access network huts, enterprise enterprise networks, rural telecom repeater sites, and utility transport comms rooms.

## Core advantages

- High-power-density 2U compact design optimizes vertical rack space, perfectly fitting standard telecom cabinets.
- Ultra-wide input voltage range (85VAC to 300VAC) ensures stable power output in harsh grid environments.
- Supports R48-2000e3 high-efficiency rectifiers with peak efficiency exceeding 96.2%, significantly reducing operating energy costs.
- Integrated M225S/NCU controller with intelligent LLVD/BLVD battery management guarantees robust operational reliability.

## Applications

- Telecom 4G/5G macro cellular base stations and distributed remote power sites
- Enterprise-grade cloud data center mission-critical -48V DC power distribution lineups
- Utility power grid dispatch centers and high-voltage substation DC switchgear rooms
- Railway transit signaling, automated train control, and communications equipment rooms

## Technical specifications

- 3-Phase AC Input Voltage Range: 三相交流输入电压范围: IEC60320 C14国标插座
- Substation SCADA Protocols: 电力规约后台通信接口: RS232、USB、网口、智能干接点
- Module efficiency: Module Efficiency: \>93%
- AC input voltage range: 交流输入电压: 80~300 Vac
- Input frequency range: Input Frequency: 45~65 Hz
- Output voltage range: 标称直流输出电压: -42~-58 Vdc
- Output current range: Output Current Range: 0~21 A
- Storage temperature range: Storage Temperature: -40~+70 ℃
- Power factor: 输出功率因数 PF: ≥0.99
- Fan speed control: Fan Speed Control: 具备智能调速功能
- Walk-in function: Walk-in Function: 具有
- Dimensions: 物理结构外形尺寸: 483×290×44 mm
- Operating Temperature Range: 工作环境温度范围: -40~+65 ℃
- Configuration model: Configuration Model: NetSure 212 C23-S1/S2
- Subrack weight: 设备重量: ≤10 kg
- Monitoring module: Monitoring Module: M225S
- Relative humidity: Relative Humidity: 5~95 %RH
- Installation method: Installation Method: 19英寸嵌入式安装
- Maintenance access: Maintenance Access: 全正面维护
- System Capacity: System Capacity: 40 A
- System Efficiency: System Efficiency: \>92%
- Sleep Energy Saving: Sleep Energy Saving: 具备休眠及高效-普效模块混插节能技术
- Rectifier Module Rated Current: Rectifier Module Rated Current: 20 A
- AC Surge Protection: AC Surge Protection: C级
- AC, DC and Signal Surge Protection: AC, DC and Signal Surge Protection: 交流侧、直流侧、信号侧防雷设计
- Operating Altitude: Operating Altitude: ≤4000 m
- DC Surge Protection: DC Surge Protection: ≥10 kA
- Product Composition: Product Composition: 交直流配电单元、整流模块、监控模块和防雷单元
- ID Recognition: ID Recognition: 具备独立ID识别功能
- AC Output Configuration: AC Output Configuration: 1×16A/1P断路器
- Battery Low Voltage Disconnect: Battery Low Voltage Disconnect: 2×20A、6×10A熔断器
- Battery Distribution Branch: Battery Distribution Branch: 1×30A熔断器
- Battery Management: Battery Management: 具备
- Load Low Voltage Disconnect: Load Low Voltage Disconnect: 2×63A/1P、2×32A/1P断路器
- Rack Size: Rack Size: 19英寸1U高

## Frequently asked questions

### How do you calculate and select the DC cable cross-sectional area for the NetSure 212 C23-S2 -48V distribution loops?

Cable sizing must satisfy both continuous ampacity and maximum permissible loop voltage drop. Telecom engineering standards require total round-trip DC loop drop between the system busbar and load terminals to stay below 0.5V (absolute maximum 1.0V). The cross-sectional area is determined by: S = (2 \* L \* I) / (K \* ΔV), where S is conductor area in mm², L is one-way route length in meters, I is maximum branch current in Amperes, K is conductivity (approx. 57 m/(Ω·mm²) for copper), and ΔV is allowable voltage drop in Volts. Select the nearest higher standard metric wire gauge and verify that its thermal current-carrying capacity under site ambient temperature exceeds 125% of the branch protective breaker rating.

### How should the Load Low Voltage Disconnect (LLVD) and Battery Low Voltage Disconnect (BLVD) thresholds be coordinated on the NetSure 212 C23-S2?

Coordinating two-stage Low Voltage Disconnects maximizes runtime for mission-critical radios while preventing permanent sulfation of batteries. For standard 48V VRLA battery strings (24 cells nominal), LLVD should be configured between 44.5V and 45.0V (approx. 1.85V to 1.88V per cell). When mains AC is lost and battery voltage drops to this trigger, auxiliary non-critical loads are disconnected. BLVD must be set strictly to 43.2V (1.80V per cell, the absolute end-of-discharge threshold for VRLA), opening the main battery contactor to prevent destructive deep discharge. Upon AC restoration, the controller re-engages contactors sequentially once the bus voltage recovers above the configured re-connect hysteresis (typically 48.0V).

### How do you configure the battery temperature compensation coefficient and baseline parameters on the NetSure 212 controller?

Access the M221S/M222S controller menu under: \[Settings\] -\> \[Battery Settings\] -\> \[Temp Compensation\]. Set the baseline temperature to 25°C. For standard AGM VRLA batteries, configure the compensation slope to -3.0 mV/°C/cell (amounting to -72 mV/°C for a 24-cell 48V string); for GEL batteries, configure -3.5 mV/°C/cell (-84 mV/°C per string). Set clamping voltage limits (e.g., minimum float clamping at 51.5V, maximum float clamping at 56.0V) to prevent over-voltage or under-voltage conditions on connected telecom hardware during seasonal temperature extremes. Verify that the physical temperature probe is attached to the center of the battery string at mid-height and calibrated.

### How do you troubleshoot and resolve active load current sharing imbalance (\> 10%) between parallel rectifiers?

Step 1: Check the total system load ratio. If aggregate load is below 10%–15% of a single rectifier rating, autonomous current sharing circuits cannot maintain tight tolerances; this is expected behavior. Step 2: If load exceeds 30% and imbalance persists (\> 10%), inspect the CAN communication status LED on the rectifiers and controller. A communication loss forces the rectifier to fallback to its autonomous default setpoint. Step 3: Measure individual AC input phases to confirm balanced input without severe voltage sags. Step 4: Reseat the offending rectifier and inspect the rear blind-mate connector for bent pins, debris, or thermal contact discoloration. Step 5: Swap slots with a healthy module; if the fault follows the module, its internal current-sensing shunt or PWM feedback loop is damaged, requiring rectifier replacement.