# Vertiv NetSure 212 C23-S1 Compact Subrack DC Power System (-48V 60A 2U)

RICEWIND · Vertiv

https://ricewind.com/en/products/netsure-212-c23-s1

Model: NetSure 212 C23-S1

The Vertiv NetSure 212 C23-S1 is a high-density 19-inch 2U subrack DC power system delivering a nominal -48VDC output up to 60A/3000W, engineered for telecom access nodes and edge infrastructure.

## What this product is

An integrated telecom-grade power subrack containing AC mains distribution, slots for hot-swappable high-efficiency switch-mode rectifiers, DC load distribution, dual low-voltage disconnects, and a centralized monitoring controller.

## What problem it solves

Resolves edge-site space limitations via a compact 2U form factor, eliminates outage risks from unstable grid voltages via an ultra-wide AC input range, and prevents battery damage using tiered load shedding.

## Who and where it is for

Telecom 4G/5G micro-sites, FTTx/OLT remote nodes, enterprise network rooms, and industrial SCADA communication stations.

## Core advantages

- Ultra-compact 2U integrated design, perfectly tailored for space-constrained edge telecom sites and outdoor cabinets.
- Wide AC input voltage range (85VAC to 300VAC) ensures stable operation and superior grid adaptability in harsh environments.
- Delivers up to 60A output with integrated intelligent LLVD/BLVD functions to safeguard critical network loads during outages.
- Powered by an advanced M221S controller for dynamic rectifier management and comprehensive remote monitoring capabilities.

## Applications

- Telecom 4G/5G macro cellular base stations and distributed remote power sites
- Enterprise-grade cloud data center mission-critical -48V DC power distribution lineups
- Utility power grid dispatch centers and high-voltage substation DC switchgear rooms
- Railway transit signaling, automated train control, and communications equipment rooms

## Technical specifications

- Cooling System Architecture: DC fan cooling with temperature control
- AC Input Voltage: 85VAC ~ 300VAC (Nominal 220VAC) VAC
- Smart Monitoring Controller: M221S Controller
- Nominal Output Voltage: -48VDC (-42V ~ -58V) VDC
- Managed Rectifier Capacity: 2 Slots for R48-1000e / R48-2000e3 Modules
- Rated DC Output Current: 60A (System Capacity 2.9kW)
- Form Factor Dimensions (HxWxD): 88 (2U) × 482 × 310 mm
- Peak Energy Efficiency: ≥96.0%
- Operating Temperature Range: -40°C ~ +65°C

## Frequently asked questions

### How do I choose the right NetSure 212 C23-S1 for my system?

Verify host model, electrical ratings, interface types and protocol requirements. Share your system details with RICEWIND and we will compare compatible options across brands.

### Is NetSure 212 C23-S1 compatible with my existing equipment?

Compatibility depends on power input, pinout signals and rack mounting specifications. Our engineers can review interfaces and integration details before you order.

### Does RICEWIND provide international shipping for NetSure 212 C23-S1?

Yes. RICEWIND ships worldwide; freight options depend on destination, weight and urgency. Contact us for a shipping quote to your site.

### What warranty and after-sales support are available for NetSure 212 C23-S1?

Warranty follows the manufacturer policy for your region. RICEWIND provides technical documentation, firmware guidance and engineer-level assistance throughout the project.

### Does RICEWIND supply NetSure 212 C23-S1?

Yes. RICEWIND supplies NetSure 212 C23-S1 with MOQ from 1 unit; in-stock items dispatch within 24-48 hours with worldwide shipping.

### Is there a cross-reference or equivalent for NetSure 212 C23-S1?

RICEWIND maintains a cross-reference database covering leading telecom and energy infrastructure brands. Contact us for the direct equivalent of NetSure 212 C23-S1.

### How should DC feeder cable cross-sectional area be sized based on telecom loop voltage drop standards?

In accordance with telecom engineering guidelines, the maximum total loop voltage drop (supply + return conductors) should not exceed 0.5V. The required cross-sectional area is calculated using: S = (2 \* L \* I) / (γ \* ΔU), where S is conductor cross-section (mm²), L is one-way cable length (m), I is maximum operating current (A), γ is copper conductivity (approx. 57 m/(Ω·mm²)), and ΔU is permissible loop voltage drop (0.5V). After calculating theoretical cross-section, engineers must verify mechanical terminal limits on the MCBs and apply standard derating factors for cable bunching in internal raceways.

### What are the correct threshold configuration parameters for LLVD and BLVD contactors?

For standard -48V VRLA battery banks, LLVD (Load Low Voltage Disconnect for non-critical loads) is typically set to -44.0VDC to -44.5VDC (approx. 1.83V to 1.85V/cell) to preserve capacity for core services. BLVD (Battery Low Voltage Disconnect protecting the cells from deep discharge damage) is configured between -43.0VDC and -43.2VDC (approx. 1.80V/cell). For LiFePO4 batteries, LLVD is typically set to -46.5VDC and BLVD to -44.0VDC. A reconnect hysteresis of 0.5V to 1.0V and a software debounce delay of 10 to 60 seconds must be configured in the controller to prevent contactor chattering caused by sudden load release.

### What is the operational mechanism of float temperature compensation, and how is it calibrated on site?

Temperature compensation adjusts output float voltage based on electrochemical activity changes to prevent undercharging or thermal runaway. The telecom baseline reference is 25°C, with a typical slope of -3.0mV/°C/cell for VRLA (-72mV/°C across a 24-cell -48V string). As temperature increases, the controller signals rectifiers to decrease float voltage; as it drops, float voltage increases. On-site installation requires securing the temperature probe (NTC/PT1000) directly to a negative terminal or center cell body. Clamping limits must be configured in the controller (e.g., maximum -56.4VDC, minimum -52.2VDC) to safeguard against sensor failure causing extreme float runaway.

### What are the common root causes of rectifier parallel load sharing imbalance, and how is it resolved?

The NetSure 212 system utilizes digital CAN bus active load sharing, ensuring output current variation within ±5% of rated capacity between 50% and 100% load. If one module bears disproportionate load: 1. Inspect controller telemetry to confirm all rectifiers communicate without CAN bus frame errors; 2. Check the mechanical backplane connectors for bent signal pins, high-resistance fretting, or improper insertion; 3. If CAN is healthy, disconnect the controller module; rectifiers should automatically revert to autonomous droop share mode. If balance restores in droop mode, the controller's software calibration offsets or slot configurations are corrupted and require controller slot re-enumeration and parameter recalibration.