# Vertiv NetSure 211 C12-S1 Compact Embedded DC Power System (-48V 120A 2U)

RICEWIND · Vertiv

https://ricewind.com/en/products/netsure-211-c12-s1

Model: NetSure 211 C12-S1

The Vertiv NetSure 211 C12-S1 is a high-density, 19-inch rack-mounted 2U subrack -48V DC power system engineered for telecom access nodes, hosting up to three high-efficiency rectifiers and a centralized controller.

## What this product is

A comprehensive telecom-grade embedded power plant combining AC input distribution, rectifier slots, configurable DC load breakers, battery disconnect contactors, and digital monitoring into a standardized 2U frame.

## What problem it solves

Mitigates severe space constraints in telecom enclosures, prevents equipment downtime across unstable utility grids (85-300VAC), and prevents irreversible battery damage via tiered low-voltage disconnection.

## Who and where it is for

Telecom 4G/5G edge sites, FTTx optical access points, microwave repeaters, transmission shelters, and roadside outdoor cabinets.

## Core advantages

- Ultra-compact 2U footprint delivers up to 120A DC output without sacrificing front-access serviceability.
- Extended AC input tolerance (85VAC to 300VAC) reduces diesel generator runtime in rural regions.
- Integrated dual Low Voltage Disconnect (LLVD for loads, BLVD for battery reserves) maximizes reserve runtime.
- Fully hot-swappable rectifiers and NCU controller enable hitless field expansions.

## Applications

- Wireless cellular base station BBU cabinets
- FTTH/FTTC outside plant nodes
- Utility substations and railway trackside signaling power
- Industrial SCADA and enterprise telecom networks

## Technical specifications

- Smart Monitoring Controller: M221S / M222S Smart Controller
- Cooling System Architecture: Temperature-controlled Forced Air Cooling
- AC Input Voltage: 85VAC ~ 300VAC (Nominal 220VAC) VAC
- Nominal Output Voltage: -48VDC (-42V ~ -58V) VDC
- Managed Rectifier Capacity: 4 × R48-1000e / R48-2000e3 Modules
- Rated DC Output Current: 120A (Rated Capacity 5.8kW)
- Form Factor Dimensions (HxWxD): 88 (2U) × 482 × 330 mm
- Peak Energy Efficiency: ≥96.0%
- Operating Temperature Range: -40°C ~ +65°C

## Frequently asked questions

### How do I choose the right NetSure 211 C12-S1 for my system?

Verify host model, electrical ratings, interface types and protocol requirements. Share your system details with RICEWIND and we will compare compatible options across brands.

### Is NetSure 211 C12-S1 compatible with my existing equipment?

Compatibility depends on power input, pinout signals and rack mounting specifications. Our engineers can review interfaces and integration details before you order.

### Does RICEWIND provide international shipping for NetSure 211 C12-S1?

Yes. RICEWIND ships worldwide; freight options depend on destination, weight and urgency. Contact us for a shipping quote to your site.

### What warranty and after-sales support are available for NetSure 211 C12-S1?

Warranty follows the manufacturer policy for your region. RICEWIND provides technical documentation, firmware guidance and engineer-level assistance throughout the project.

### Does RICEWIND supply NetSure 211 C12-S1?

Yes. RICEWIND supplies NetSure 211 C12-S1 with MOQ from 1 unit; in-stock items dispatch within 24-48 hours with worldwide shipping.

### Is there a cross-reference or equivalent for NetSure 211 C12-S1?

RICEWIND maintains a cross-reference database covering leading telecom and energy infrastructure brands. Contact us for the direct equivalent of NetSure 211 C12-S1.

### How do you calculate DC output cable sizing to ensure acceptable loop voltage drop in NetSure 211 C12-S1?

Calculate cable cross-sectional area using S = (2 \* L \* I) / (γ \* ΔV), where L is one-way cable length in meters, I is maximum branch current in amperes, γ is copper conductivity (57 m/(Ω·mm²)), and ΔV is allowable loop voltage drop (typically ≤ 0.5V per telecom standards). Ensure the chosen cross-section complies with breaker terminal lug dimensions and thermal current carrying limits.

### What are the recommended LLVD and BLVD disconnection thresholds in the NetSure 211 controller?

For standard 24-cell VRLA battery strings, set Load Low Voltage Disconnect (LLVD) to -44.0VDC (~1.83V/cell) to shed non-essential loads, extending runtime for core traffic. Set Battery Low Voltage Disconnect (BLVD) to between -43.2VDC and -43.0VDC (~1.80V/cell) to halt terminal discharge and prevent plate sulfation. For lithium (LiFePO4) installations, align BLVD with BMS parameters, typically between -40.5VDC and -42.0VDC.

### How is battery temperature compensation configured, and how does the system behave during a sensor fault?

For standard VRLA (AGM/GEL) batteries, the reference base is 25°C, and the float voltage compensation slope is typically set to -3.0 mV/°C/cell (-72 mV/°C across a 24-cell string). If the NCU detects an open, shorted, or out-of-range NTC sensor, it triggers a sensor failure alarm, falls back to the baseline 25°C nominal float voltage (e.g., -53.5VDC), and disables compensation to prevent thermal runaway or chronic undercharge.

### What is the physical mechanism for parallel current sharing, and does it operate if the controller goes offline?

Rectifiers in the NetSure 211 employ autonomous active current sharing. Each module's internal DSP communicates instantaneous current data over an inter-module bus and adjusts its internal PWM loop, achieving current imbalance under ±5% across 50% to 100% rated load. This process runs at the power stage firmware level independently of the NCU controller. If the NCU is removed or unpowered, rectifiers continue autonomous parallel current sharing uninterrupted.

Content updated: 2026-09-12T10:40:50.865Z