# Vertiv Liebert DataMate3000 DME12 12.5kW Precision Air Conditioner Unit (12.5kW)

RICEWIND · Vertiv

https://ricewind.com/en/products/liebert-datamate3000-dme12

Model: Liebert DataMate3000 DME12

The Vertiv Liebert DataMate3000 DME12 is an enterprise-grade 12.5 kW direct-expansion (DX) air-cooled precision environmental control system engineered for edge data centers and telecom stations, featuring a compliant scroll compressor, high SHF (≥0.90), and continuous 24/7 mission-critical thermal regulation capabilities.

## What this product is

A split-type precision cooling architecture comprising an indoor air handling evaporator unit and an outdoor air-cooled condenser, supporting flexible upflow or front-discharge airflow management.

## What problem it solves

Eliminates excessive dehumidification, parasitic latent heat loss, static electricity accumulation, and compressor burnouts associated with non-precision comfort air conditioners in critical IT spaces.

## Who and where it is for

Small-to-medium data centers, 5G base transceiver stations (BTS), rail transport signaling hubs, high-voltage transformer substation control rooms, and medical analytical laboratories.

## Core advantages

- Ultra-high Sensible Heat Ratio (SHF ≥ 0.90) optimizing 100% cooling power toward electronic hardware
- High-efficiency compliant scroll compressor providing liquid-slugging resistance and low vibration
- Intuitive LCD micro-controller supporting up to 32 units group-networking and auto-rotation
- Wide outdoor ambient tolerance with cold-start operation down to -30°C using optional low-ambient kit

## Applications

- Telecom operator central offices and remote 5G cell sites
- Power distribution automation control and secondary relay rooms
- High-speed railway signaling equipment and wayside substations
- Enterprise edge micro-computing infrastructure and server clusters

## Technical specifications

- Rated Humidification Capacity: 1.5 kg/h
- Refrigerant Type: R22
- Heating capacity: 4 kW
- Monitoring protocol: YDN23、MODBUS
- Storage temperature: －25～＋55 °C
- Storage relative humidity: 5～95 %RH
- Nominal Cooling Capacity: 12.5 kW
- Operating relative humidity: 30～80 %RH
- Indoor unit dimensions: 600×500×1975 mm
- Outdoor Operating Temperature: －15～＋45 °C
- Indoor Operating Temperature: 0～40 °C
- Operating Altitude: ＜1000 m
- Display Resolution: 128×64 dot matrix
- Input power: 4.15 kW
- Energy efficiency ratio: 3.0
- Operating voltage range: 380（－15％～＋15％） V
- Rated supply voltage: 380 Vac
- Power frequency: 50 Hz
- Power phases and wiring: 3P5W（3×L＋N＋PE）
- Temperature setting range: 15～35 °C
- Humidity setting range: 20～80 %RH
- Standard piping length: 5 m
- Gas-side pipe outer diameter: 5/8″（16） mm
- Liquid-side pipe outer diameter: 1/2″（12） mm
- Tested external static pressure: 150 Pa maximum
- Maximum equivalent horizontal distance between indoor and outdoor units: 50 m
- Permissible height difference between indoor and outdoor units: －5～20 m
- Maximum liquid pipe pressure drop: 40 kPa
- Indoor unit drain connection outer diameter: 22 mm
- Drain pipe inner diameter: 22 mm
- Humidifier drain temperature resistance: 90 °C
- Humidifier water supply connection outer diameter: 6.35 mm
- Humidifier water supply pressure range: 100～700 kPa
- Recommended cross-sectional area of indoor unit cable: 10AWG（6） mm²
- Standard length of outdoor unit power cable: 8 m
- Recommended cross-sectional area of outdoor unit cable: 18AWG（0.75） mm²
- Maximum number of energy-saving cards supported: 4
- Historical alarm record capacity: 200 records
- Monitoring address range: 1～254
- Monitoring baud rate range: 1200～19200 bps
- Sleep temperature setting range: 15～40 °C
- Primary/standby rotation cycle range: 1～7 days
- Power short-circuit ratio requirement: ≥250
- Indoor unit net weight: 155 kg
- Outdoor unit dimensions: 787×352×1240 mm (standard outdoor unit)
- Outdoor unit net weight: 60 kg (standard outdoor unit)
- Installation base height: ≥150 mm
- Minimum clearance from combustible materials: 150 mm
- Protection rating: IPX4
- Applicable standard for operating environment: GB/T 4798.3-2007
- Applicable standard for storage environment: GB/T 4798.1-2005
- Harmonic standard: IEC61000-3-12
- Heater configuration: 0 or 1
- Humidifier configuration: 0 or IF (infrared humidification)

## Frequently asked questions

### How do I choose the right Liebert DataMate3000 DME12 for my site?

Consider total sensible heat load, airflow configuration (upflow/downflow), ambient temperature limits, piping elevation and monitoring needs. Share your requirements with RICEWIND and we will compare suitable models from multiple brands for you.

### Is Liebert DataMate3000 DME12 compatible with my existing infrastructure?

Compatibility depends on power supply, refrigerant pipe dimensions and environmental monitoring protocols (RS-485/Modbus/SNMP). Our engineers can verify pipe sizing, wiring and BMS integration before you order.

### Does RICEWIND provide international shipping for Liebert DataMate3000 DME12?

Yes. Indoor and outdoor units are shipped globally with reinforced non-coniferous export wooden crates and nitrogen holding pressure. Freight options depend on destination port and urgency — contact us for a shipping quote.

### What warranty and technical support are available for Liebert DataMate3000 DME12?

Warranty follows the manufacturer policy for your region. RICEWIND provides installation drawings, commissioning documentation, OEM spare parts and engineer-level technical assistance throughout the project.

### Does RICEWIND supply Liebert DataMate3000 DME12?

Yes. RICEWIND supplies Liebert DataMate3000 DME12 from verified inventory, MOQ from 1 unit; in-stock units dispatch within 24-48 hours with worldwide shipping.

### Is there a cross-reference or equivalent for Liebert DataMate3000 DME12?

RICEWIND maintains a cross-reference database covering Vertiv (Liebert), Envicool, and Huawei thermal management systems. Contact us for direct equivalents or retrofit recommendations for Liebert DataMate3000 DME12.

### What are the rated cooling capacity, efficiency, and airflow specifications of the DME12?

The DME12 delivers a nominal cooling capacity of 12.5 kW under standard IT test conditions (24°C DB, 17°C WB indoor; 35°C outdoor), with a high airflow rate ranging from 3,200 to 3,600 m³/h. The Sensible Heat Ratio (SHF) is certified at ≥0.90. Standard electrical inputs accept 3-phase 380V/50Hz (or optional 1-phase 220V/50Hz) with maximum operating current ~16A-19A, utilizing R410A eco-refrigerant.

### How does the DME12 support group networking and DCIM telemetry interfaces?

The main controller features an integrated RS485 port operating on native Modbus-RTU protocol at 9600/19200 bps. Up to 32 units can be daisy-chained via proprietary local networking to achieve automated lead-lag rotation (settable from 1 to 999 hours), emergency failover cascade, and consolidated alarm polling for third-party BMS/DCIM platforms.

### What are the extreme ambient tolerance and surge protection capabilities?

The power module tolerates ±15% utility voltage variations and incorporates built-in surge suppression, phase-loss, and phase-reversal detection. Paired with variable-speed condenser fans, it maintains operational stability down to -15°C standard ambient, extendable to -30°C with an optional low-temperature kit, meeting IP20 electrical enclosure standards.

Content updated: 2026-09-12T15:17:13.700Z