# Vertiv Liebert CRV4 In-Row Precision Air Conditioner 25-60kW

RICEWIND · Vertiv

https://ricewind.com/en/products/liebert-crv4-precision-ac

Model: Liebert CRV4 Precision AC

The Vertiv Liebert CRV4 is a row-based precision cooling solution designed for high-density data center environments, utilizing 380V 3-phase AC input, a DC inverter brushless scroll compressor, and premium EC centrifugal fans to deliver horizontal airflow directly neutralizing cabinet hot spots with an SHF exceeding 0.95.

## What this product is

CRV4 is an advanced in-row precision cooling module with 300mm/600mm widths, deployed between standard IT racks in cold/hot aisle containment setups. It integrates inverter compressors, electronic expansion valves, backward-curved EC fans, and the iCOM intelligent control platform.

## What problem it solves

Eliminates high-density cabinet hotspots and air recirculation issues without the airflow inefficiencies of raised-floor downflow units, preventing short-cycling and driving down the power usage effectiveness (PUE) of mission-critical compute rows.

## Who and where it is for

Enterprise and hyperscale cloud data centers, modular aisle containment solutions, edge computing edge facilities, and critical telecommunication switching centers.

## Core advantages

- Ultra-high Sensible Heat Ratio (SHF ≥ 0.95) engineered specifically for dry IT heat dissipation
- Full inverter architecture (DC scroll compressor + EC fans) smoothly modulating from 20% to 100%
- 100% full frontal maintenance access requiring zero side or rear service clearance
- iCOM multi-unit teamwork algorithm coordinating up to 32 units to prevent operational fighting

## Applications

- Modular data center cold/hot aisle containment systems
- High-power AI training clusters and supercomputing server rows exceeding 15kW/rack
- Carrier-grade 5G core network equipment rooms and telco central offices
- Financial colocation data centers demanding high-availability Tier III/IV thermal stability

## Technical specifications

- Compressor type: Compressor Type: 直流无刷变容量压缩机
- AC Operating Voltage: 工作交流供电电压: 380～415 V
- Filter efficiency: Filter Efficiency: 30 %
- Full-load current: Full Load Current: 21.7 A
- Refrigerant: 制冷剂类型: R410A
- Product series: Product Series: Liebert.CRV4 系列风冷精密空调
- Nominal Cooling Capacity: Nominal Cooling Capacity: 25 kW
- Outdoor Operating Temperature: Outdoor Operating Temperature: −20～＋45 ℃
- Dimensions: 物理结构外形尺寸: 300×1100×2000 mm
- Communication Interface and Protocol: Communication Interface and Protocol: RS485；MODBUS-RTU
- Main Circuit Breaker Model: Main Circuit Breaker Model: NDM1-63C40/3
- Refrigerant Oil Type: Refrigerant Oil Type: POE型（32-3MAF）
- Indoor Unit Refrigerant Charge: Indoor Unit Refrigerant Charge: 2.47 kg
- Maximum Design Suction Pressure: Maximum Design Suction Pressure: 12.4 bar
- Source Short-Circuit Ratio Requirement: Source Short-Circuit Ratio Requirement: ≥350
- Filter Dust Retention: Filter Dust Retention: 90 %
- Applicable Supply System: Applicable Supply System: TN、TT星形接法
- Suction Pressure Upper Limit: Suction Pressure Upper Limit: 13.4 bar
- Suction Pressure Switch Lower Limit: Suction Pressure Switch Lower Limit: 4.5 bar
- Indoor Operating Temperature: Indoor Operating Temperature: 18～40 ℃
- Indoor Operating Relative Humidity: Indoor Operating Relative Humidity: 20～60 %RH
- Indoor Unit IP Rating: Indoor Unit IP Rating: IP20
- Minimum Outdoor Operating Temperature: Minimum Outdoor Operating Temperature: −34 ℃
- Operating Altitude: Operating Altitude: ＜1000 m
- High Pressure Switch Setting: High Pressure Switch Setting: 3900 kPa
- Cooling Form: Cooling Form: 风冷单冷源系统（压缩机制冷系统）
- Compressor Cooling System Configuration: Compressor Cooling System Configuration: 变速压缩机，R410A制冷剂；单压缩机单系统
- Indoor Fan Type: Indoor Fan Type: EC风机
- Heat Exchanger Type: Heat Exchanger Type: V型高效翅片管换热器；表面亲水处理
- Electric Heater Type: Electric Heater Type: PTC
- Expansion Valve Type: Expansion Valve Type: 电子膨胀阀
- Upper Drain Copper Pipe OD: Upper Drain Copper Pipe OD: 12.7 mm
- Humidifier Inlet Water Pressure: Humidifier Inlet Water Pressure: 100～700 kPa
- Humidifier Inlet Thread: Humidifier Inlet Thread: 3/4"GAS
- Humidifier Hose Temperature Requirement: Humidifier Hose Temperature Requirement: ＞90 ℃
- Alarm History Storage Capacity: Alarm History Storage Capacity: 1000 条
- Maximum Indoor-Outdoor Height Difference: Maximum Indoor-Outdoor Height Difference: +30 m
- Maximum Recommended Pipe Length: Maximum Recommended Pipe Length: 50 m
- Outdoor Fan Speed Control Method: Outdoor Fan Speed Control Method: 通过压力调节风机转速
- Extension Kit Consultation Threshold: Extension Kit Consultation Threshold: ＞30 m
- Drain Port Thread: Drain Port Thread: 1/2"-BSP
- Drain Hose Inner Diameter: Drain Hose Inner Diameter: 9 mm
- Control Interface and Terminal Definition: Control Interface and Terminal Definition: 51/24漏水；37/38远程开关机；70/71室外机控制；75/76公共告警；61/62 CAN；63/64液路电磁阀；A2/B2/12V/GND SIC卡
- Recommended Refrigerant Pipe Diameter: Recommended Refrigerant Pipe Diameter: 气管D 19；液管L 12.7 mm
- Display Resolution: 128×64 dot matrix
- Maximum Rack Temperature Sensors: Maximum Rack Temperature Sensors: 6 个
- Drain Pan Hose Inner Diameter: Drain Pan Hose Inner Diameter: 16 mm
- Temperature/Humidity History Range: Temperature/Humidity History Range: 0～48 小时
- Power Terminal Block: Power Terminal Block: L1、L2、L3、N、PE
- Fan Speed Control Signal: Fan Speed Control Signal: 0～10 VDC
- Front Service Clearance: Front Service Clearance: 600 mm
- Cabinet Mounting Hole Diameter: Cabinet Mounting Hole Diameter: 13.5 mm
- Equipment Net Weight: Equipment Net Weight: 235 kg

## Frequently asked questions

### How do I choose the right Liebert CRV4 Precision AC for my site?

Consider total sensible heat load, airflow configuration (upflow/downflow), ambient temperature limits, piping elevation and monitoring needs. Share your requirements with RICEWIND and we will compare suitable models from multiple brands for you.

### Is Liebert CRV4 Precision AC compatible with my existing infrastructure?

Compatibility depends on power supply, refrigerant pipe dimensions and environmental monitoring protocols (RS-485/Modbus/SNMP). Our engineers can verify pipe sizing, wiring and BMS integration before you order.

### Does RICEWIND provide international shipping for Liebert CRV4 Precision AC?

Yes. Indoor and outdoor units are shipped globally with reinforced non-coniferous export wooden crates and nitrogen holding pressure. Freight options depend on destination port and urgency — contact us for a shipping quote.

### What warranty and technical support are available for Liebert CRV4 Precision AC?

Warranty follows the manufacturer policy for your region. RICEWIND provides installation drawings, commissioning documentation, OEM spare parts and engineer-level technical assistance throughout the project.

### Does RICEWIND supply Liebert CRV4 Precision AC?

Yes. RICEWIND supplies Liebert CRV4 Precision AC from verified inventory, MOQ from 1 unit; in-stock units dispatch within 24-48 hours with worldwide shipping.

### Is there a cross-reference or equivalent for Liebert CRV4 Precision AC?

RICEWIND maintains a cross-reference database covering Vertiv (Liebert), Envicool, and Huawei thermal management systems. Contact us for direct equivalents or retrofit recommendations for Liebert CRV4 Precision AC.

### What are the core cooling capacity, energy efficiency, and Sensible Heat Ratio (SHF) ratings of the CRV4?

The Liebert CRV4 delivers a modulating cooling capacity of 25kW to 45kW with a Sensible Heat Ratio (SHF) equal to or exceeding 0.95 under standard data center operating conditions (37°C dry bulb / 24°C wet bulb). Through its DC inverter compressor and high-efficiency backward-curved EC centrifugal fans, the unit achieves an operational COP improvement of up to 30% across the 20% to 100% capacity range.

### Which clustering and building management system (BMS) protocols are supported by the iCOM controller?

The integrated iCOM system features native multi-unit clustering via CAN/RS-485 bus, synchronizing up to 32 units in master/slave modes with auto-failover, load balancing, and anti-competition routines. For BMS/DCIM integration, it provides an onboard 10/100 Ethernet interface and RS-485 serial ports supporting Modbus RTU, Modbus TCP, SNMP v1/v2c/v3, and BACnet IP protocols.

### What are the environmental tolerance and electrical surge suppression capabilities of the system?

The CRV4 is equipped with built-in Class II (C-level) surge protective devices rated at 20kA nominal discharge per IEC 61643-11. Its control electronics comply with high-level EMC/EMI standards. Paired with Vertiv low-ambient outdoor condensers featuring stepless fan speed control, the system operates reliably across outdoor temperatures from -30°C to +48°C and sustains grid voltage variations of ±15%.

Content updated: 2026-09-12T16:52:25.468Z