# Huawei TP48600T-N20A6 Indoor Telecom Power Cabinet -48 V 600 A

RICEWIND · Huawei

https://ricewind.com/en/products/huawei-tp48600t-n20a6-b27

Model: TP48600T-N20A6

The Huawei TP48600T-N20A6 is an indoor telecom power system that converts 220/380 V AC three-phase four-wire input into -48 V DC for -48 V-series telecom equipment; rectification, distribution and monitoring are combined in one 2000 × 600 × 600 mm cabinet with a maximum output of 600 A.

## What this product is

The system combines rectifier modules, AC/DC distribution and the SMU06C2 controller in one cabinet measuring 2000 mm high, 600 mm wide and 600 mm deep. The AC input is 220/380 V three-phase four-wire with a phase-voltage range of 85 - 300 V AC, 45 - 66 Hz, with 50/60 Hz rated and a power factor of at least 0.99 at full load. The DC output spans -42 to -58 V, defaulting to -53.5 V, at up to 600 A; voltage regulation is within ±1 %, current-sharing imbalance stays below ±5 % at 20 - 100 % load, and psophometric noise is at or below 2 mV. Distribution is split into BLVD (important loads) and LLVD (secondary load) branches per user, supporting shared feeding of four users with independent per-user DC metering.

## What problem it solves

It centralizes -48 V DC feeding for equipment rooms: one cabinet holds rectification, distribution, monitoring and the battery branch, delivering up to 600 A; four users share the supply with independent metering and load-shedding control, which suits multi-tenant sites and operator transmission nodes.

## Who and where it is for

Suited to indoor telecom equipment rooms, operator transmission and aggregation nodes, and multi-user shared rooms that need -48 V DC feeding with independent metering and load-shedding control for four users.

## Core advantages

- Up to 600 A output, adjustable from -42 to -58 V DC with -53.5 V default
- Space for up to 12 R4850N6 or R4850G2 rectifier modules, hot-swappable, mixed high-efficiency and standard modules supported
- 220/380 V AC three-phase four-wire input, 85 - 300 V phase voltage, 45 - 66 Hz, power factor ≥ 0.99 at full load
- Shared feeding for four users with independent metering, per-user BLVD/LLVD branches and load-shedding control
- 2000 × 600 × 600 mm cabinet, floor or raised-floor mounting, front service, wall-adjacent placement, natural cooling
- Operates from -20 °C to +50 °C, at altitudes of 0 - 4000 m, with an MTBF of 200000 h at 25 °C

## Applications

- Centralized -48 V feeding in indoor telecom equipment rooms
- Operator transmission and aggregation nodes
- Multi-user shared rooms with per-user feeding and metering
- Core equipment rooms needing high-current -48 V output

## Technical specifications

- Model: TP48600T-N20A6
- Product type: Indoor telecom power system (cabinet)
- AC input configuration: 220/380 V AC, three-phase four-wire
- AC input voltage range: 85 - 300 V AC (phase voltage)
- Input frequency: 45 - 66 Hz (rated 50/60 Hz)
- Power factor: ≥ 0.99 (rated input, full load)
- Input total harmonic distortion: ≤ 5 % (input 208/220/230 V AC, 50 - 100 % load)
- Maximum output current: 600 A
- Output voltage range: -42 to -58 V DC
- Default output voltage: -53.5 V DC
- Output power: Sum of the rectifier module powers (depends on configuration)
- Voltage regulation accuracy: ≤ ±1 %
- Current-sharing imbalance: \< ±5 % (20 - 100 % load)
- Psophometric noise: ≤ 2 mV
- Ripple and noise: ≤ 200 mVp-p
- Rectifier module configuration: Up to 12 R4850N6 or R4850G2 rectifier modules
- Monitoring unit: SMU06C2
- Multi-user feeding: Shared feeding for four users with independent per-user DC metering
- Important load branches (BLVD): Users 1-3 each have four 100 A fuses; user 4 has two 16 A 1-pole breakers
- Secondary load branches (LLVD): Users 1-3 each have four 160 A fuses plus three 63 A 1-pole breakers; user 4 has three 63 A breakers
- Battery branch: Two 500 A fuses
- Communication interfaces: RS485/RS232 ×1 (NetEco, DND or MODBUS protocol); COM ×1 (master/slave or MODBUS)
- Cabinet dimensions (H×W×D): 2000 × 600 × 600 mm
- Cabinet weight: ≤ 120 kg (without rectifier modules and optional parts)
- Installation and maintenance: Floor-standing or raised-floor; front service; wall-adjacent (≥ 100 mm)
- Cable entry: Top cable entry and exit
- Cooling: Natural cooling
- Protection rating: IP20
- Operating temperature: -20 °C to +50 °C
- Storage/transport temperature: -40 °C to +70 °C
- Operating humidity: 5 % - 95 % RH (non-condensing)
- Operating altitude: 0 - 4000 m (above 2000 m, reduce the maximum permissible operating temperature by 1 °C for every additional 200 m)
- MTBF: 200000 h (25 °C)
- AC lightning discharge current: Nominal 20 kA, maximum ±40 kA (8/20 μs waveform)
- Certifications and standards: IEC/EN 60950-1; EN 300386 Class A; ETSI EN 300 019-1-4 Class 4.1; IEC 61000-4-2/-3/-4/-5/-6

## Frequently asked questions

### What output does the Huawei TP48600T-N20A6 provide?

Maximum output current is 600 A, with the output voltage adjustable from -42 to -58 V DC and -53.5 V as the default. Output power is the sum of the fitted rectifier modules and depends on the configuration; up to 12 R4850N6 or R4850G2 modules can be installed.

### Which rectifier modules and monitoring unit does the Huawei TP48600T-N20A6 use?

The rectifier section takes up to 12 R4850N6 or R4850G2 modules, hot-swappable, with mixed high-efficiency and standard modules supported; the monitoring unit is the SMU06C2 with a bilingual Chinese/English LCD. Rectifier modules can enter sleep mode automatically according to load.

### What are the dimensions of the Huawei TP48600T-N20A6 cabinet, and how is it installed?

The cabinet is 2000 mm high, 600 mm wide and 600 mm deep, weighing at most 120 kg without rectifier modules and optional parts. It installs on the floor or a raised floor, is serviced from the front, can stand against a wall (≥ 100 mm clearance), uses top cable entry and exit, natural cooling, and has an IP20 rating.

### Does the Huawei TP48600T-N20A6 support shared multi-user feeding? How is metering done?

Yes. Four users share the supply with independent per-user DC metering; distribution is split into important-load (BLVD) and secondary-load (LLVD) branches per user, and load-shedding control works in time or voltage mode with per-user thresholds adjustable independently.

### What grid and environmental conditions does the Huawei TP48600T-N20A6 need?

The AC input is 220/380 V three-phase four-wire with a phase-voltage range of 85 - 300 V and 45 - 66 Hz; AC-side lightning arresters handle a nominal 20 kA and maximum ±40 kA (8/20 μs). It operates from -20 °C to +50 °C at 5 - 95 % RH (non-condensing) and at altitudes of 0 - 4000 m (above 2000 m the maximum permissible operating temperature drops by 1 °C per 200 m).

Content updated: 2026-09-16T06:32:36.752Z