# Huawei TP483000D Outdoor Telecom DC Power Cabinet System (3000A / -48V / 60×R4850G2 / IP55 Enclosure)

RICEWIND · Huawei

https://ricewind.com/en/products/huawei-tp483000d-outdoor

Model: Huawei TP483000D Outdoor Power Cabinet

Huawei TP483000D is a hub-level outdoor ultra-large capacity telecom DC power system delivering up to 3000A at -48V DC via up to 60 R4850G2 rectifiers, integrating IP55-rated dual-door heavy protection, plate heat exchanger thermal management, and an advanced SMU02C controller for mission-critical macro and aggregation sites.

## What this product is

Huawei TP483000D is a hub-level outdoor ultra-large capacity telecom DC power system delivering up to 3000A at -48V DC via up to 60 R4850G2 rectifiers, integrating IP55-rated dual-door heavy protection, plate heat exchanger thermal management, and an advanced SMU02C controller for mission-critical macro and aggregation sites.

## What problem it solves

The Huawei TP483000D Outdoor Power Cabinet System is engineered for telecommunication core aggregation hubs and mega macro sites. Featuring an N+X modular architecture, it supports up to 60 units of 50A ultra-efficient R4850G2 rectifier modules, delivering an aggregate output of 3000A at -48V DC. The enclosure adopts an IP55-rated heavy-duty double-door bayed structure with strict isolation between AC, DC, and control sections. DC distribution incorporates high-capacity molded case circuit breakers (MCCB) and intelligent two-stage load shedding (LLVD/BLVD). The advanced thermal system utilizes a high-duty plate heat exchanger combined with emergency DC fans to ensure seamless operation from -40°C to +55°C. Powered by the SMU02C monitoring controller, the system delivers complete remote telemetry and Northbound OSS integration via SNMP, Modbus, and Web interfaces.

## Who and where it is for

Huawei TP483000D is a hub-level outdoor ultra-large capacity telecom DC power system delivering up to 3000A at -48V DC via up to 60 R4850G2 rectifiers, integrating IP55-rated dual-door heavy protection, plate heat exchanger thermal management, and an advanced SMU02C controller for mission-critical macro and aggregation sites.

## Core advantages

- Hub-level 3000A DC output capacity supporting up to 60 R4850G2 rectifiers
- High rectifier conversion efficiency over 96% cutting operational OPEX
- Heavy-duty IP55 dual-door bayed cabinet impervious to sand, dust and moisture
- Industrial plate heat exchanger cooling ensures internal temperature stability
- SMU02C monitoring controller supports full SNMP, Modbus and Web telemetry
- Integrated LLVD and BLVD two-stage load shedding secures storage battery life

## Applications

- Telecom 5G core aggregation and super macro outdoor site power systems
- Shared infrastructure telecommunication towers with multi-carrier loads
- Harsh desert, maritime, and coastal high-humidity communication nodes
- Trans-regional optical fiber repeater hubs and microwave backbone sites
- Railway signaling, trackside telemetry, and radio communication outdoor hubs
- Remote oil and gas pipeline automation and mining radio network hubs

## Technical specifications

- Cabinet Dimensions & Type: Outdoor Integrated Weatherproof Floor-Standing Power Cabinet (IP55)
- System Integration Capacity: 3000A (-48V DC) Carrier-Class Telecom Hub Ultra-Capacity
- Heat Exchange Cooling System: High-Capacity Industrial Plate Heat Exchanger + Emergency DC Fans
- Environment Monitoring Unit: SMU02C Intelligent Supervisory Unit (SNMP, Web & Modbus)
- DC Distribution & LVD Protection: High-Current DC MCCBs + Intelligent Dual-Stage LVD (LLVD/BLVD)
- Battery Compartment: Thermally Controlled Battery Bay for High-Density LiFePO4 Strings
- Rectifier module configuration: 60x R4850G2 50A Ultra-HE Rectifiers in Parallel
- Operating Temperature Range: -40°C to +55°C

## Frequently asked questions

### Is Huawei TP483000D Outdoor Power Cabinet compatible with existing batteries, generators, and rectifiers?

Compatibility depends on DC bus voltage, telemetry protocols, and mechanical form factors. Describe your existing site setup and RICEWIND engineers can verify integration feasibility before you order.

### How is Huawei TP483000D Outdoor Power Cabinet delivered? Does RICEWIND provide international shipping?

Power systems are packed in heavy-duty export-standard wooden crates for sea or air transport. RICEWIND ships worldwide — contact us to confirm inventory, freight options, and delivery schedules.

### What warranty and engineering support are available for Huawei TP483000D Outdoor Power Cabinet?

Warranty follows the manufacturer policy for the specific configuration. RICEWIND supports wiring schematics, remote commissioning guidance, spare parts, and engineer-level technical assistance.

### Does RICEWIND supply Huawei TP483000D Outdoor Power Cabinet?

Yes. RICEWIND supplies Huawei TP483000D Outdoor Power Cabinet with MOQ from 1 system; in-stock units dispatch within 24-48 hours with global logistics coverage.

### Is there a cross-reference or equivalent replacement for Huawei TP483000D Outdoor Power Cabinet?

RICEWIND maintains a cross-reference matrix covering Huawei, Vertiv, Eltek, and ZTE telecom power systems. Contact us for direct equivalents and expansion options for Huawei TP483000D Outdoor Power Cabinet.

### How do I plan and configure Huawei TP483000D Outdoor Power Cabinet for my telecom site?

Consider total DC load, N+1 redundancy, battery autonomy backup time, surge protection, and cabinet footprint. Share your project requirements with RICEWIND and we will propose a matched configuration.

### What is the maximum load capacity, individual module efficiency, and energy performance of the Huawei TP483000D?

The system features a nominal output of -48V DC, supporting up to 60 Huawei R4850G2 50A rectifier modules running in parallel to provide a massive 3000A continuous output. R4850G2 modules achieve peak conversion efficiency exceeding 96% and maintain over 95% across a 20% to 80% load span. Combined with SMU02C intelligent rectifier sleep cycling, the system reduces site energy waste dramatically.

### How is the physical enclosure engineered, and what is the thermal heat exchange mechanism of the TP483000D?

The system utilizes a 2.1-meter outdoor heavy-duty dual-door bayed enclosure with IP55 rating, protecting against dust, rain, and snow. Cooling is driven by a high-duty closed-loop plate heat exchanger that physically isolates clean internal air from external contaminants while exchanging thermal energy efficiently. Top-mounted DC emergency fans automatically kick in during extreme thermal spikes or primary cooler faults to provide forced ventilation.

### What withstand capabilities does the TP483000D offer against temperature extremes, lightning surges, and electrical shocks?

Operating across a wide -40°C to +55°C range, the cabinet integrates optional PTC heaters and automatic thermal derating. The AC distribution is fortified with 20kA/40kA (8/20μs) Class C+D surge protective devices (SPD), while DC outputs have 10/20kA surge protection. With an ultra-wide input range of 85VAC to 300VAC per phase, it easily withstands grid instability and isolates severe transients via millisecond hardware interlocks.

### How does the system manage battery energy storage and execute intelligent two-stage (LLVD/BLVD) load shedding?

The system supports VRLA and advanced lithium-ion (such as Huawei SmartLi) batteries, featuring cell voltage tracking, temperature-compensated floating charge, and sleep-wake activation. The DC distribution includes independent LLVD and BLVD contactors. Upon grid outage, LLVD first disconnects non-essential loads such as secondary RRUs to sustain transmission equipment; once reaching the cut-off threshold, BLVD trips to prevent deep-discharge cell damage.