# Huawei ETP48200-C2A6 2U 12 kW Embedded DC Power System with SMU11B

RICEWIND · Huawei

https://ricewind.com/en/products/huawei-etp48200-c2a6

Model: Huawei ETP48200-C2A6

The Huawei ETP48200-C2A6 is a 19-inch 2U embedded telecommunications DC power system. Manual version 03 lists 12 kW output power, a -42 V DC to -58 V DC output range, a -53.5 V DC default and the SMU11B monitoring module.

## What this product is

The system integrates AC input, DC distribution, battery branches, rectifier positions and SMU11B monitoring. Its dimensions including mounting ears are 86.1 x 482.6 x 330 mm. It supports horizontal or vertical 19-inch mounting, front maintenance and IP20 protection.

## What problem it solves

It consolidates AC input, -48 V-class DC output, load and battery distribution and monitoring within rack space. Usable capacity must be calculated from continuous and peak load, battery charging, input type and the actual rectifier configuration; neither 12 kW nor appearance alone proves project compatibility.

## Who and where it is for

For telecommunications cabinets, transmission nodes and industrial communication facilities requiring 19-inch embedded DC power. Project suitability still depends on input, load, backup, installation and environmental conditions.

## Core advantages

- 12 kW system output power with -53.5 V DC default output
- SMU11B monitoring; manual-identified R4850G2, R4850G5 and R4875G5 positions
- LLVD: 2 x 125 A and 6 x 32 A; BLVD: 1 x 80 A, 3 x 32 A and 1 x 16 A
- Horizontal or vertical 19-inch mounting, front maintenance and IP20

## Applications

- Telecommunications base-station and transmission cabinets
- Fiber aggregation and edge communication nodes
- Industrial IoT communications power
- -48 V-class DC systems requiring battery backup

## Technical specifications

- AC Input Voltage: Rated 200–240 V AC, 45–66 Hz; input topology depends on AC input unit
- System Output Capacity: 12 kW; -42 V DC to -58 V DC (default -53.5 V DC)
- Form Factor: 19-Inch Rackmount
- Rectifier Module Slots: R4850G2 / R4850G5 / R4875G5 rectifier positions
- System Monitoring Controller: SMU11B monitoring module
- DC Distribution Branches: LLVD: 2 x 125 A, 6 x 32 A; BLVD: 1 x 80 A, 3 x 32 A, 1 x 16 A; battery: 2 x 125 A
- Operating Temperature Range: -40°C to +65°C

## Frequently asked questions

### Is Huawei ETP48200-C2A6 compatible with existing batteries, generators, and rectifiers?

Compatibility depends on DC bus voltage, telemetry protocols, and mechanical form factors. Describe your existing site setup and RICEWIND engineers can verify integration feasibility before you order.

### How is Huawei ETP48200-C2A6 delivered? Does RICEWIND provide international shipping?

Power systems are packed in heavy-duty export-standard wooden crates for sea or air transport. RICEWIND ships worldwide — contact us to confirm inventory, freight options, and delivery schedules.

### What warranty and engineering support are available for Huawei ETP48200-C2A6?

Warranty follows the manufacturer policy for the specific configuration. RICEWIND supports wiring schematics, remote commissioning guidance, spare parts, and engineer-level technical assistance.

### Does RICEWIND supply Huawei ETP48200-C2A6?

Yes. RICEWIND supplies Huawei ETP48200-C2A6 with MOQ from 1 system; in-stock units dispatch within 24-48 hours with global logistics coverage.

### Is there a cross-reference or equivalent replacement for Huawei ETP48200-C2A6?

RICEWIND maintains a cross-reference matrix covering Huawei, Vertiv, Eltek, and ZTE telecom power systems. Contact us for direct equivalents and expansion options for Huawei ETP48200-C2A6.

### How do I plan and configure Huawei ETP48200-C2A6 for my telecom site?

Consider total DC load, N+1 redundancy, battery autonomy backup time, surge protection, and cabinet footprint. Share your project requirements with RICEWIND and we will propose a matched configuration.

### What are the core electrical parameters, output capability, and rectifier compatibility for the ETP48200-C2A6?

The ETP48200-C2A6 has an adjustable DC output range of -42V to -58V and a rated system output capability of 12 kW. Actual current and AC input conditions depend on the configuration. Rectifier modules, the monitoring unit, and battery distribution should be verified against the applicable configuration and manufacturer documentation before ordering.

### Can different rectifier models be mixed, and how should the internal communication topology be verified?

Whether different rectifier models can be mixed or operated in parallel, and how they communicate internally, depends on the specific configuration and manufacturer documentation. Do not infer compatibility from form factor alone; RICEWIND can verify the proposed module and monitoring-unit combination before ordering.

### How does the system handle harsh environmental conditions, lightning surges, and temperature extremes?

Engineered for harsh deployments, the ETP48200-C2A6 features an operating temperature range of -40°C to +65°C (with thermal derating above +55°C). The subrack integrates a Class C AC surge protective device (SPD) rated at 20kA nominal / 40kA maximum (8/20μs) with failure indicator signaling, alongside 10/20kA DC surge suppression and conformal-coated internal electronics resistant to condensation and dust.

Content updated: 2026-11-23T07:19:10.078Z