# Huawei ETP48600-C11A1 High-Capacity Subrack DC Power System (-48V 600A 11U)

RICEWIND · Huawei

https://ricewind.com/en/products/etp48600-c11a1

Model: ETP48600-C11A1

The ETP48600-C11A1 is an 11U subrack -48VDC embedded telecom power system delivering up to 600A rated output, accommodating up to eight high-efficiency rectifiers and a smart monitoring controller.

## What this product is

Huawei ETP48600-C11A1 is a high-density subrack DC power system engineered for core switching sites, aggregation base stations, and optical transport hubs. It consolidates AC distribution, DC distribution, high-efficiency rectifier slots (such as R4850G2/R4875G1), and the SMU02 series advanced monitoring unit within a compact 11U form factor, converting AC mains into regulated -48V DC power while intelligently managing energy storage batteries.

## What problem it solves

Resolves vertical footprint constraints in telecom cabinets, eliminates excessive busbar voltage drops under high ampere conditions, and safeguards battery banks from deep discharge through staged load shedding.

## Who and where it is for

4G/5G macro sites, regional transport hubs, metro optical switching rooms, edge data centers, and power utility substations requiring high-reliability -48VDC power.

## Core advantages

- Delivers up to 600A DC output within an 11U compact subrack, optimizing cabinet footprint.
- Integrated multi-stage load disconnection (LLVD and BLVD) ensures priority mission-critical payload survival.
- Full hot-swappable architecture for rectifiers and controller eliminates maintenance downtime.
- Wide AC input range (85VAC to 300VAC) with high grid surge withstand capability.

## Applications

- Telecom 4G/5G macro cellular base stations and distributed remote power sites
- Enterprise-grade cloud data center mission-critical -48V DC power distribution lineups
- Utility power grid dispatch centers and high-voltage substation DC switchgear rooms
- Railway transit signaling, automated train control, and communications equipment rooms

## Technical specifications

- Smart Monitoring Controller: SMU02C Central Network Controller Unit
- AC Input Voltage: 85VAC ~ 300VAC (3-Phase 380V / 220V Dual Source) VAC
- Cooling System Architecture: Zoned front-to-rear air cooling
- Nominal Output Voltage: -48VDC (-42V ~ -58V) VDC
- Rated DC Output Current: 600A (System Capacity 34.8kW)
- Managed Rectifier Capacity: 12 × 50A
- Peak Energy Efficiency: ≥96.8%
- Form Factor Dimensions (HxWxD): 488 (11U) × 482 × 400 mm
- Operating Temperature Range: -40°C ~ +65°C

## Frequently asked questions

### How do I choose the right ETP48600-C11A1 for my system?

Verify host model, electrical ratings, interface types and protocol requirements. Share your system details with RICEWIND and we will compare compatible options across brands.

### Is ETP48600-C11A1 compatible with my existing equipment?

Compatibility depends on power input, pinout signals and rack mounting specifications. Our engineers can review interfaces and integration details before you order.

### Does RICEWIND provide international shipping for ETP48600-C11A1?

Yes. RICEWIND ships worldwide; freight options depend on destination, weight and urgency. Contact us for a shipping quote to your site.

### What warranty and after-sales support are available for ETP48600-C11A1?

Warranty follows the manufacturer policy for your region. RICEWIND provides technical documentation, firmware guidance and engineer-level assistance throughout the project.

### Does RICEWIND supply ETP48600-C11A1?

Yes. RICEWIND supplies ETP48600-C11A1 with MOQ from 1 unit; in-stock items dispatch within 24-48 hours with worldwide shipping.

### Is there a cross-reference or equivalent for ETP48600-C11A1?

RICEWIND maintains a cross-reference database covering leading telecom and energy infrastructure brands. Contact us for the direct equivalent of ETP48600-C11A1.

### How should DC output power cables be sized and calculated for the ETP48600-C11A1 operating at a 600A full load?

At 600A continuous rating, cable sizing must satisfy thermal ampacity and loop voltage drop limits (telecom standards enforce a round-trip drop of ≤0.5V). Using the loop formula: Cross-section S = (I × L) / (γ × ΔU), where I=600A, L is total round-trip cable length (meters), γ is copper conductivity (~57 m/(Ω·mm²)), and ΔU is allowable drop (0.5V). For a 10-meter one-way run (20m total loop), S = (600 × 20) / (57 × 0.5) ≈ 421 mm². In telecom site practice, dual runs of 240 mm² or triple runs of 150 mm² class-5/6 flexible copper cables are run in parallel, terminated with heavy-duty compression lugs, and torqued to specified busbar bolt ratings.

### What are the typical voltage threshold settings for LLVD (Load Low Voltage Disconnect) and BLVD (Battery Low Voltage Disconnect) in the SMU02 controller?

For standard 48V VRLA battery banks (24 cells in series with an end-of-discharge limit of 1.80V/cell), standard settings in the SMU02 are: LLVD1 (non-priority loads) is configured at 47.0VDC to 47.5VDC (approx. 1.96V–1.98V/cell) to shed non-essential loads like comfort climate or secondary carriers during early outage stages. BLVD (Battery Low Voltage Disconnect, or LLVD2 for critical loads) is set between 43.2VDC and 44.0VDC (1.80V–1.83V/cell) to prevent destructive deep discharge and plate sulfation. When using LiFePO4 telecom batteries, BLVD is typically raised to 44.5VDC–45.0VDC to harmonize with the battery pack BMS disconnect curves.

### What is the operating principle of battery temperature compensation in the ETP48600-C11A1, and how is it verified on site?

Lead-acid electrochemical potential is inversely proportional to electrolyte temperature: elevated temperatures increase charge acceptance and risk thermal runaway or dry-out if voltage is unadjusted, while lower temperatures increase internal resistance requiring higher float voltage. The SMU02 measures battery post temperature via an NTC probe and dynamically shifts system float voltage using: V\_float = V\_ref - (T\_actual - 25°C) × N × K\_comp, where N=24 cells and K\_comp is typically 3.0 to 5.0 mV/(°C·cell). For K\_comp = 3.5mV, the overall system adjustment is -84mV/°C. Verification: Measure the DC bus voltage with a calibrated DMM against the displayed SMU02 temperature; applying mild heat/cooling to the NTC probe must trigger an inverse shift in the rectifiers' regulated float voltage output without sensor fault alarms.

### What is the tolerance standard and troubleshooting procedure for rectifier current sharing imbalance when running multiple units (e.g., R4850G2) in the ETP48600-C11A1?

Huawei rectifiers utilize autonomous digital CAN/RS485 communication for active current sharing. Standard specifications mandate that within a 50% to 100% load range, the current unbalance between active rectifiers must remain within ≤ ±5% of the module's rated current (within ±2.5A for 50A rectifiers). Troubleshooting sequence: 1. Confirm overall system load is above 10%; at extremely light loads, the sharing loop does not operate linearly, which is normal. 2. Verify there are no CAN communication failure alarms in the SMU02 controller. 3. Inspect the subrack backplane slot pins for physical bending, dust buildup, or oxidation. 4. Check rectifier firmware versions in SMU02 and align them to the same release. 5. If a specific module remains clamped at 0A or locked at maximum output under load, its internal current-sense circuit is defective; hot-swap the faulty rectifier module.