# Eltek Flatpack2 48/3000 WOR HE Rectifier Module (241115.705)

RICEWIND · Eltek

https://ricewind.com/en/products/eltek-flatpack2-241115-705

Model: Flatpack2 48/3000 WOR HE (241115.705)

SKU: ELT-ELTEK-FLATPACK2-241115-7-36F904

The Flatpack2 48/3000 WOR HE (241115.705) is a carrier-grade, switch-mode AC/DC power rectifier offering Wide Output Range (WOR) and High Efficiency (HE) performance.

## What this product is

A high-density switch-mode rectifier integrating advanced resonant topology and microprocessor control. Operating as an autonomous, hot-pluggable unit within Flatpack2 multi-module power racks, it interfaces via CAN bus with Smartpack controllers to provide regulated DC power and intelligent battery charging.

## What problem it solves

Eliminates operational downtime under unstable AC grid profiles, accommodates wide battery voltage windows, and reduces cooling loads and overall site energy OPEX through optimized thermal dissipation.

## Who and where it is for

Cellular base transceiver stations, fixed telecom central offices, data communication nodes, utility substations, and enterprise DC power distribution frames.

## Core advantages

- Supports 85-300VAC ultra-wide AC input with WOR capability, eliminating downtime from severe grid fluctuations.
- Achieves peak conversion efficiency up to 96.5%, significantly reducing site energy consumption and OPEX.
- Features CAN bus digital communication and an embedded microprocessor for seamless integration with Smartpack controllers.
- Operates reliably from -40°C to +75°C with intelligent variable-speed cooling fans for extreme thermal environments.

## Applications

- Telecom 4G/5G macro cellular base stations and distributed remote power sites
- Enterprise-grade cloud data center mission-critical -48V DC power distribution lineups
- Utility power grid dispatch centers and high-voltage substation DC switchgear rooms
- Railway transit signaling, automated train control, and communications equipment rooms

## Technical specifications

- Cooling System: Internal Temperature-Controlled Intelligent Variable Speed Fan
- AC Input Voltage: 85VAC ~ 300VAC (WOR Wide Operating Range)
- Operating Efficiency Rating: ≥96.5%
- Operating Temperature Range: -40°C ~ +75°C
- Rated Output Power Capacity: 3000W (62.5A @ 48VDC)
- Nominal DC Output Voltage: -48VDC (-42V ~ -58V)
- Overall System Efficiency: Up to 96.2% (Gold Standard)
- Acoustic Noise: ≤ 55 dBA (at 25°C ambient load)
- Ingress Protection Rating: IP20 (Indoor Dust & Finger Proof)
- Dielectric Withstand Voltage: 3000VAC Input to Ground (\< 5mA)

## Frequently asked questions

### How do I select Flatpack2 48/3000 WOR HE (241115.705) for my power system?

Check output voltage, module power rating, efficiency class and compatibility with your existing rectifier shelf or controller. RICEWIND can verify fitment and propose the right quantity.

### Is Flatpack2 48/3000 WOR HE (241115.705) compatible with my existing system?

Compatibility depends on the rectifier shelf, controller and communication protocol. Send your current system model to RICEWIND and our engineers will confirm which modules fit.

### Does RICEWIND provide international shipping for Flatpack2 48/3000 WOR HE (241115.705)?

Yes. Power modules and systems are packed in anti-static, export-standard crates and shipped worldwide. Delivery time and freight options depend on stock and destination — contact RICEWIND for quotes and lead times.

### What warranty and technical support apply to Flatpack2 48/3000 WOR HE (241115.705)?

Warranty follows the manufacturer's policy for the specific equipment. RICEWIND supports testing guidance, replacement requests, spare parts and technical coordination per order terms.

### Does RICEWIND supply Flatpack2 48/3000 WOR HE (241115.705) from stock?

Yes. RICEWIND supplies Flatpack2 48/3000 WOR HE (241115.705) from verified stock with MOQ from 1 piece; in-stock units dispatch within 24-48 hours with global express air and sea freight.

### Is there a cross-reference or equivalent for Flatpack2 48/3000 WOR HE (241115.705)?

RICEWIND maintains a comprehensive cross-reference chart covering Huawei, Vertiv (Emerson), Eltek, ZTE and Delta 48V telecom rectifiers. Contact us for the direct equivalent of Flatpack2 48/3000 WOR HE (241115.705).

### How do you troubleshoot a flashing/solid yellow alarm LED and a 'CAN Comm Failure / Module Lost' alarm reported by the controller?

1. Verify the module is fully seated into the backplane connector and the mechanical latch is locked, inspecting pins for bent contacts or oxidation. 2. Measure CAN bus termination resistance with DC bus de-energized; across CAN\_H and CAN\_L, total resistance must be ~60 ohms (two parallel 120-ohm terminators). 3. If only one module fails to communicate, swap slots with a working unit: if the fault follows the module, the internal CAN transceiver/isolated interface is defective; if the fault remains at the slot, inspect backplane traces and connector pins.

### What is the operating logic during an Output Overvoltage Protection (OVP) shutdown, and what is the exact reset procedure?

The rectifier employs selective OVP: a primary software shutdown via CAN and an independent secondary hardware analog latch comparator (typically preset to 59.0V ±0.5V). When hardware OVP trips, PWM switching stops immediately, and the unit latches off with a solid red LED. Reset procedure: 1. Confirm whether external power sources caused bus voltage rise or an internal feedback loop failed. 2. Disconnect AC input power completely by opening the branch breaker or unlatching the rectifier from the shelf. 3. Wait at least 60 seconds for bulk DC link capacitors to bleed down below 5V. 4. Re-apply AC mains to release the hardware latch.

### When operating in harsh ambient conditions, if the rectifier triggers an Over-Temperature (OT) alarm and thermal shutdown, how should airflow and cooling faults be diagnosed?

1. Inspect the front intake grille and rear exhaust for dust or debris blockages; clean with low-pressure dry compressed air if clogged. 2. Verify fan operation via controller diagnostics: the internal PWM fan must scale linearly up to ~7000 RPM at high temperatures; a locked or tachometer-faulty fan will force thermal trip. 3. Ensure air baffles in the subrack are correctly installed to eliminate hot air re-circulation from exhaust back to intake. 4. Note that full power is maintained up to 55°C ambient; derating occurs between 55°C and 75°C, followed by complete shutdown at \>75°C ambient. Verify external shelter HVAC/ventilation capacity.

Content updated: 2026-09-15T02:10:22.827Z