# Eltek Flatpack 2880 48 Telecom Switch-Mode Rectifier Module (-48V 53.5A 2880W 1U Hot-Pluggable)

RICEWIND · Eltek

https://ricewind.com/en/products/eltek-flatpack-2880-48

Model: Flatpack 2880 48

The Eltek Flatpack 2880 48 is an industrial-grade telecom power infrastructure unit engineered for high-reliability base stations and mission-critical edge facilities.

## What this product is

A carrier-grade power unit designed by Eltek to deliver stable DC/AC electricity under demanding grid conditions and harsh outdoor environments.

## What problem it solves

Eliminates unexpected site downtime caused by AC utility voltage surges, severe brownouts, and load transient disruptions.

## Who and where it is for

Telecom macro sites, small cells, edge computing nodes, optical transport nodes, and railway signaling power systems.

## Core advantages

- Ultra-wide operating voltage tolerance for volatile utility grids
- Advanced digital control loop delivering exceptional peak efficiency
- Full hot-swappable architecture with integrated surge & over-current protection
- Industrial long-life components with superior MTBF reliability

## Applications

- Telecom carrier macro and micro BTS DC power distribution
- Edge computing data center infrastructure backup
- Industrial automation and communication transmission nodes

## Technical specifications

- Cooling Architecture: Forced Air Cooling with Internal Speed-Controlled Fan
- Rated Output Current: 53.5A Rated Output
- Rated Output Power: 2880W Rated Power
- AC Input Voltage Range: 185VAC ~ 275VAC (Nominal 230VAC)
- Wide Operating Temperature Range: -40°C ~ +65°C
- Form Factor & Mounting: 1U Hot-swappable Shelf Insertion
- Nominal DC Output Voltage: -48VDC (Adjustable -43.5VDC ~ -57.6VDC)
- Conversion efficiency: ≥92.0% High Efficiency

## Frequently asked questions

### How do I select Flatpack 2880 48 for my power system?

Check output voltage, module power rating, efficiency class and compatibility with your existing rectifier shelf or controller. RICEWIND can verify fitment and propose the right quantity.

### Is Flatpack 2880 48 compatible with my existing system?

Compatibility depends on the rectifier shelf, controller and communication protocol. Send your current system model to RICEWIND and our engineers will confirm which modules fit.

### Does RICEWIND provide international shipping for Flatpack 2880 48?

Yes. Power modules and systems are packed in anti-static, export-standard crates and shipped worldwide. Delivery time and freight options depend on stock and destination — contact RICEWIND for quotes and lead times.

### What warranty and technical support apply to Flatpack 2880 48?

Warranty follows the manufacturer's policy for the specific equipment. RICEWIND supports testing guidance, replacement requests, spare parts and technical coordination per order terms.

### Does RICEWIND supply Flatpack 2880 48 from stock?

Yes. RICEWIND supplies Flatpack 2880 48 from verified stock with MOQ from 1 piece; in-stock units dispatch within 24-48 hours with global express air and sea freight.

### Is there a cross-reference or equivalent for Flatpack 2880 48?

RICEWIND maintains a comprehensive cross-reference chart covering Huawei, Vertiv (Emerson), Eltek, ZTE and Delta 48V telecom rectifiers. Contact us for the direct equivalent of Flatpack 2880 48.

### How are the float and boost voltage levels calibrated on the Flatpack 2880 48?

The nominal output is -48VDC with a default float setting of -53.5VDC. Output can be software-adjusted between -43.5VDC and -57.6VDC via a system controller (e.g., Smartpack), or trimmed manually via internal potentiometers during standalone mode.

### What happens if internal cooling fans experience stall or speed degradation?

The module utilizes Hall-sensor tachometer feedback. If fan RPM drops below threshold, a minor alarm is flagged; if heatsink temperatures exceed 85°C, thermal shutdown engages automatically to prevent semiconductor burnout, auto-restarting upon cooldown.

### Can Flatpack 2880 coexist with older Flatpack 1500/2000 units on the same subrack shelf?

Yes, provided the backplane power connector pinouts and rail dimensions match. All modules share the common -48V DC bus seamlessly, provided the aggregate current remains within backplane copper busbar limits.

Content updated: 2026-09-25T09:17:11.032Z