# DPC DUMC-4860 Subrack Telecom DC Power System (-48V 60A 2U)

RICEWIND · Dpc

https://ricewind.com/en/products/dumc-4860

Model: DUMC-4860

The DPC DUMC-4860 is a compact 2U 19-inch rack-mounted telecom DC power system converting utility AC to regulated -48VDC up to 60A continuous load for mission-critical telecom site infrastructure.

## What this product is

The DPC DUMC-4860 integrates a 19-inch subrack, hot-pluggable high-frequency switch-mode rectifiers, a DK04 central supervision unit, and unified DC distribution into a 2U footprint, engineered for network edge sites.

## What problem it solves

Eliminates operational disruptions caused by poor rural/suburban AC grid fluctuations, cabinet space constraints, and premature battery degradation via automated low-voltage cut-offs.

## Who and where it is for

Wireless macro baseband cabinets, microwave transmission repeater shelters, enterprise access nodes, and edge compute DC distribution setups.

## Core advantages

- Ultra-wide 85-300VAC input range easily withstands unstable grid fluctuations
- Compact 2U standard rack design perfectly solves space-constrained edge sites
- Advanced intelligent battery management prevents irreversible deep-discharge damage
- Industry-leading peak efficiency up to 95.8% significantly lowers operational power loss

## Applications

- Telecom 4G/5G macro cellular base stations and distributed remote power sites
- Enterprise-grade cloud data center mission-critical -48V DC power distribution lineups
- Utility power grid dispatch centers and high-voltage substation DC switchgear rooms
- Railway transit signaling, automated train control, and communications equipment rooms

## Technical specifications

- Smart Monitoring Controller: DK04 LCD Monitoring Unit
- Cooling System Architecture: Forced Air Cooling
- AC Input Voltage: 85VAC ~ 300VAC (Nominal 220VAC) VAC
- Nominal Output Voltage: -48VDC (-42V ~ -58V) VDC
- Managed Rectifier Capacity: 2-Slot Configuration
- Rated DC Output Current: 60A (System Capacity 3.48kW)
- Peak Energy Efficiency: ≥95.8%
- Form Factor Dimensions (HxWxD): 88 (2U) × 482 × 310 mm
- Operating Temperature Range: -30°C ~ +60°C

## Frequently asked questions

### How do I choose the right DUMC-4860 for my system?

Verify host model, electrical ratings, interface types and protocol requirements. Share your system details with RICEWIND and we will compare compatible options across brands.

### Is DUMC-4860 compatible with my existing equipment?

Compatibility depends on power input, pinout signals and rack mounting specifications. Our engineers can review interfaces and integration details before you order.

### Does RICEWIND provide international shipping for DUMC-4860?

Yes. RICEWIND ships worldwide; freight options depend on destination, weight and urgency. Contact us for a shipping quote to your site.

### What warranty and after-sales support are available for DUMC-4860?

Warranty follows the manufacturer policy for your region. RICEWIND provides technical documentation, firmware guidance and engineer-level assistance throughout the project.

### Does RICEWIND supply DUMC-4860?

Yes. RICEWIND supplies DUMC-4860 with MOQ from 1 unit; in-stock items dispatch within 24-48 hours with worldwide shipping.

### Is there a cross-reference or equivalent for DUMC-4860?

RICEWIND maintains a cross-reference database covering leading telecom and energy infrastructure brands. Contact us for the direct equivalent of DUMC-4860.

### How should DC cabling and busbar sizing be determined for the DUMC-4860 under full 60A rated output?

Sizing is based on the 60A continuous rating factored by a standard 1.25 design margin (75A capacity). To maintain a total circuit loop voltage drop below 0.5VDC, use minimum 16mm² (5 AWG) multi-strand copper cables for one-way runs under 5 meters. For runs exceeding 10 meters, increase sizing to 25mm² (3 AWG) or 35mm² (2 AWG). Terminate with tin-plated copper compression lugs onto M6 terminals torqued strictly to 4.5–5.0 N·m.

### How should LLVD and BLVD voltage disconnect thresholds be configured on the DUMC-4860, and what is the contactor sequencing logic?

For standard 48V VRLA battery strings (24 cells @ 2V), typical configuration via the DK04 controller sets LLVD (non-critical load shedding) at 44.0VDC (1.83V/cell) with a 10–60s delay to protect core backhaul. BLVD (battery disconnect to prevent cell reversal and deep discharge) is configured at 43.2VDC (1.80V/cell). Upon AC grid recovery and DC bus reaching 48.0VDC for a stable duration (e.g., 300s), the controller re-engages BLVD first, then LLVD safely.

### What is the function of the battery temperature compensation coefficient, and what is the standard setting for VRLA batteries?

Temperature compensation adjusts the rectifier float voltage based on real-time battery temperature captured via an external NTC sensor, counteracting thermal runaway at high temperatures and sulfation/undercharging at low temperatures. For 48V VRLA strings (24 cells) with a 25°C reference, the standard negative slope is configured to -72mV/°C (representing -3.0mV/°C/cell). If battery temperature reaches 35°C, float voltage drops from nominal 53.5V to 52.78V, preserving electrolyte and grid lifespan.

### How does the DUMC-4860 maintain autonomous parallel current sharing between rectifiers, and what imbalance threshold indicates a fault?

The system utilizes active autonomous digital CAN-bus or dedicated hardware share-bus signaling. Each rectifier's internal MCU compares its individual output against the system average and micro-adjusts its PWM duty cycle. In normal operation between 50% and 100% rated load, current sharing imbalance remains under ±3% (absolute deviation \<1.5A). If a module deviates by more than ±10% of its rated capacity, a current-sharing fault triggers, requiring inspection of backplane connector seating or internal current sense shunts.

Content updated: 2026-09-15T02:08:52.505Z