# Delta ESR4850DE Industrial-Grade High-Reliability Telecom Rectifier Module (54V 50A 2900W)

RICEWIND · Delta

https://ricewind.com/en/products/delta-esr4850de-b29

Model: ESR4850DE

The Delta ESR4850DE is an industrial-grade, carrier-class telecom switch-mode rectifier module delivering a rated 54V DC (adjustable from 43V to 58V DC) output, 50A maximum output current, and 2900W of continuous output power. Engineered for mission-critical DC power plants, it operates over a wide single-phase AC input range of 80V AC to 300V AC.

## What this product is

The ESR4850DE integrates high-performance two-stage power conversion comprising an active boost PFC stage and an isolated DC-DC resonant topology. Supervised by a high-speed DSP/microcontroller, the unit incorporates active autonomous current sharing, dual closed-loop regulation, and compliance with stringent telecom safety and EMC standards including IEC/EN 62368 and ETSI EN 300 386.

## What problem it solves

This module mitigates field vulnerabilities caused by poor grid stability, severe voltage sags, power surges, and extreme ambient thermal variations that typically induce rectifier burnout or nuisance tripping. Its dynamic power derating and intelligent thermal throttling eliminate catastrophic shutdowns, while robust autonomous bus sharing prevents circulating currents in large parallel arrays.

## Who and where it is for

Ideal for 4G/5G macro and outdoor distributed base stations, telecom central offices, edge data center 48V DC buses, utility substation automation SCADA equipment, and industrial-grade battery backup charging systems.

## Core advantages

- Wide input voltage range (80V-300V AC) withstands weak grid fluctuations and surges
- Peak efficiency up to ≥95.5%, significantly reducing telecom base station energy consumption
- Supports -40°C to +75°C ultra-wide operating temp and smart dynamic derating for extreme environments
- Built-in CAN/RS485 bus and precise autonomous current sharing ensure reliable parallel redundancy

## Applications

- 4G/5G macro cell sites and harsh outdoor telecom enclosure systems
- Central office optical transmission and broadband access DC power plants
- Power utility substation protection and industrial SCADA automation systems
- Enterprise edge computing nodes and railway signaling power infrastructures

## Technical specifications

- AC Input Voltage: 80V AC ~ 300V AC
- Maximum Output Current: 50A
- Rated Output Power: 2900W
- Rated Output Voltage: -48VDC (-42V ~ -58V)
- Maximum Efficiency: ≥ 95.5%
- Operating Temperature Range: -40°C ~ +75°C
- Cooling System: Forced Air Cooling with Intelligent Speed Fan
- Hot-Swappable Support: Yes (Live Hot-Pluggable / Plug-and-Play without Power Interruption)

## Frequently asked questions

### How do I select ESR4850DE for my power system?

Check output voltage, module power rating, efficiency class and compatibility with your existing rectifier shelf or controller. RICEWIND can verify fitment and propose the right quantity.

### Is ESR4850DE compatible with my existing system?

Compatibility depends on the rectifier shelf, controller and communication protocol. Send your current system model to RICEWIND and our engineers will confirm which modules fit.

### Does RICEWIND provide international shipping for ESR4850DE?

Yes. Power modules and systems are packed in anti-static, export-standard crates and shipped worldwide. Delivery time and freight options depend on stock and destination — contact RICEWIND for quotes and lead times.

### What warranty and technical support apply to ESR4850DE?

Warranty follows the manufacturer's policy for the specific equipment. RICEWIND supports testing guidance, replacement requests, spare parts and technical coordination per order terms.

### Does RICEWIND supply ESR4850DE from stock?

Yes. RICEWIND supplies ESR4850DE from verified stock with MOQ from 1 piece; in-stock units dispatch within 24-48 hours with global express air and sea freight.

### Is there a cross-reference or equivalent for ESR4850DE?

RICEWIND maintains a comprehensive cross-reference chart covering Huawei, Vertiv (Emerson), Eltek, ZTE and Delta 48V telecom rectifiers. Contact us for the direct equivalent of ESR4850DE.

### Does the Delta ESR4850DE shut down when the AC input voltage drops below 150V AC?

No, it does not shut down. The ESR4850DE employs an intelligent input-voltage-dependent derating mechanism. While full 2900W power is sustained between 176V AC and 300V AC, the module dynamically scales down its maximum output power linearly within the 80V AC to 176V AC range to protect the input PFC stage from excessive RMS current, ensuring the DC bus stays continuously energized.

### What causes severe current unbalance among parallel ESR4850DE modules in a single rack?

Under normal operating conditions, current sharing deviation remains under ±5%. An unbalance where one module carries full load and another carries nearly zero is typically caused by poor backplane blind-mate connector engagement affecting the analog/CAN bus pins, differing internal firmware voltage calibrations, or a module operating in thermal derating due to fan clogging. Verify connector seating and clean communication pins.

### What primary hardware or environmental faults trigger the solid red Alarm/Fault LED?

A solid red fault LED indicates Output Over-Voltage Protection (OVP) latch-up, Over-Temperature Protection (OTP), or a cooling fan stall/failure. Troubleshoot by checking the fan for physical blockage and dust accumulation, ensuring ambient intake air does not exceed limits, and cycling the AC breaker to reset potential latching OVP circuits.

### What precautions should be taken when hot-swapping an ESR4850DE under live operating conditions?

Ensure the mechanical front-panel latch is fully disengaged before extraction to safely disconnect the signal pins before power pins. When inserting a replacement module, push it in smoothly along the guide rails without angular deflection to prevent damaging the high-current backplane connector pins, and immediately engage the locking screw/latch to establish a solid frame ground connection.

Content updated: 2026-09-16T11:25:55.988Z