# Delta ESR-48/60A A High-Power Telecom Switch-Mode Rectifier Module (-48V 60A 3200W)

RICEWIND · Delta

https://ricewind.com/en/products/delta-esr-48-60aa-rectifier-module

Model: ESR-48/60A A

The Delta ESR-48/60A A is a high-power switch-mode telecom rectifier module delivering nominal -48V DC, 60A maximum output current, and 3200W rated power, engineered for large switching centers and IDC facilities.

## What this product is

This unit populates large-scale Delta floor-standing power cabinets or modular subracks, paralleling to form systems delivering hundreds to thousands of amperes for core telecom infrastructure.

## What problem it solves

Meets demanding power requirements of modern 5G macro hubs and cloud data centers, reducing the slot count needed in power racks and optimizing spatial density.

## Who and where it is for

Engineered for central telecom switching offices, cloud computing DC power rows, 5G aggregation hubs, and heavy-duty industrial automation facilities.

## Core advantages

- Heavy-Duty Current Output: Single module delivers continuous 60A (up to 3200W), reducing the total number of rectifier units needed in a cabinet.
- Optimized Heavy-Load Thermal Design: Engineered airflow and dual low-loss heatsinks ensure low thermal stress and extended MTBF under full load.
- Autonomous Digital Load Sharing: True peer-to-peer current-share bus keeps inter-module imbalance under 3%, eliminating single-point controller vulnerabilities.
- Carrier-Grade EMI & Surge Immunity: Complies with rigorous international telecom standards for lightning surge resilience and low conducted electromagnetic noise.

## Applications

- Telecom 4G/5G macro cellular base stations and distributed remote power sites
- Enterprise-grade cloud data center mission-critical -48V DC power distribution lineups
- Utility power grid dispatch centers and high-voltage substation DC switchgear rooms
- Railway transit signaling, automated train control, and communications equipment rooms

## Technical specifications

- AC Input Voltage: 88V to 300V AC (Nominal 220V/230V)
- Cooling & Form Factor: Forced Air Cooling / Subrack Hot-Swap
- Rated Output VA / Wattage: 3200W
- Current Share Imbalance: \< 3% (50% to 100% load)
- Rated DC Output Current: -48VDC (-42V ~ -58V)
- Nominal DC Output Voltage: -48VDC (-42V ~ -58V)
- Overall System Efficiency: Up to 96.2% (Gold Standard)
- Acoustic Noise: ≤ 55 dBA (at 25°C ambient load)
- Ingress Protection Rating: IP20 (Indoor Dust & Finger Proof)
- Dielectric Withstand Voltage: 3000VAC Input to Ground (\< 5mA)

## Frequently asked questions

### How do I choose the right ESR-48/60A A for my system?

Verify host model, electrical ratings, interface types and protocol requirements. Share your system details with RICEWIND and we will compare compatible options across brands.

### Is ESR-48/60A A compatible with my existing equipment?

Compatibility depends on power input, pinout signals and rack mounting specifications. Our engineers can review interfaces and integration details before you order.

### Does RICEWIND provide international shipping for ESR-48/60A A?

Yes. RICEWIND ships worldwide; freight options depend on destination, weight and urgency. Contact us for a shipping quote to your site.

### What warranty and after-sales support are available for ESR-48/60A A?

Warranty follows the manufacturer policy for your region. RICEWIND provides technical documentation, firmware guidance and engineer-level assistance throughout the project.

### Does RICEWIND supply ESR-48/60A A?

Yes. RICEWIND supplies ESR-48/60A A with MOQ from 1 unit; in-stock items dispatch within 24-48 hours with worldwide shipping.

### Is there a cross-reference or equivalent for ESR-48/60A A?

RICEWIND maintains a cross-reference database covering leading telecom and energy infrastructure brands. Contact us for the direct equivalent of ESR-48/60A A.

### What high-current output capacity and grid tolerance does the Delta ESR-48/60A A offer?

The module is designed for high-capacity 60A operation (rated output power 3200W @ 53.5V). The AC input voltage range is 85VAC to 300VAC, and it can sustain full 60A continuous output from 176VAC upwards, making it widely used in large and medium telecom equipment rooms and datacenter header cabinets.

### What is the output over-voltage protection (OVP) trip logic and reset procedure of the ESR-48/60A A?

When the output voltage abnormally rises to the protection threshold (typically 58.5VDC to 60VDC) and stays there for more than 10ms, the dual hardware latch circuit instantaneously cuts off PWM output and lights the red LED to lock out. The fault does not auto-restart; the module must be fully de-energized by opening its AC input breaker, or removed and left for 10 seconds, before being reinserted to reset.

### What is the derating rule of the ESR-48/60A A under high ambient temperature and heavy load?

Between -40°C and +55°C ambient it delivers 100% full rated output of 3200W. From 55°C to 75°C, the internal microprocessor linearly reduces the maximum allowed output current based on the temperature sensor readings, derating to approximately 50% at 75°C to keep critical component junction temperatures within limits.

Content updated: 2026-09-17T17:42:50.632Z