# Delta ESR-48/56AC High-Efficiency Switch-Mode Telecom Rectifier Module (-48V 56A 3000W)

RICEWIND · Delta

https://ricewind.com/en/products/delta-esr-48-56ac-rectifier-module

Model: ESR-48/56AC

The Delta ESR-48/56AC is a carrier-grade high-frequency switch-mode telecom rectifier module delivering nominal -48V DC, 56A maximum output current, and 3000W rated power across a wide AC input voltage range.

## What this product is

This module slots into Delta telecom DC power subracks, converting incoming single-phase utility or generator AC power into low-ripple -48V DC power to drive base station equipment and charge backup batteries.

## What problem it solves

Eliminates low power conversion efficiency, high input harmonic distortion, and nuisance tripping during utility voltage sags, ensuring high power factor and grid tolerance.

## Who and where it is for

Engineered for wireless macro cell sites, microwave transmission hubs, core switching offices, and industrial power distribution systems utilizing Delta subracks.

## Core advantages

- High-Efficiency Power Conversion: Typical efficiency exceeds 92%, substantially reducing site utility costs and cooling requirements.
- Ultra-Wide AC Input Range: Operates reliably across 88V to 300V AC, withstanding severe grid voltage drops in remote regions.
- Hitless Hot-Plug Maintenance: Supports live insertion and removal without interrupting continuous -48V DC bus power delivery.
- Active Digital Current Sharing: Autonomous load sharing across multiple parallel modules ensures uninterrupted N+1 redundancy.

## Applications

- Telecom 4G/5G macro cellular base stations and distributed remote power sites
- Enterprise-grade cloud data center mission-critical -48V DC power distribution lineups
- Utility power grid dispatch centers and high-voltage substation DC switchgear rooms
- Railway transit signaling, automated train control, and communications equipment rooms

## Technical specifications

- Operating Temperature Range: -25°C ~ +65°C
- Rated DC Output Current: -48VDC (-42V ~ -58V)
- Rated Output VA / Wattage: 3000W
- AC Input Voltage: 88V to 300V AC (Nominal 220V/230V)
- Cooling & Form Factor: Smart Fan Forced Air / Subrack Hot-Swap
- Nominal DC Output Voltage: -48VDC (-42V ~ -58V)
- Overall System Efficiency: Up to 96.2% (Gold Standard)
- Acoustic Noise: ≤ 55 dBA (at 25°C ambient load)
- Ingress Protection Rating: IP20 (Indoor Dust & Finger Proof)
- Dielectric Withstand Voltage: 3000VAC Input to Ground (\< 5mA)

## Frequently asked questions

### How do I choose the right ESR-48/56AC for my system?

Verify host model, electrical ratings, interface types and protocol requirements. Share your system details with RICEWIND and we will compare compatible options across brands.

### Is ESR-48/56AC compatible with my existing equipment?

Compatibility depends on power input, pinout signals and rack mounting specifications. Our engineers can review interfaces and integration details before you order.

### Does RICEWIND provide international shipping for ESR-48/56AC?

Yes. RICEWIND ships worldwide; freight options depend on destination, weight and urgency. Contact us for a shipping quote to your site.

### What warranty and after-sales support are available for ESR-48/56AC?

Warranty follows the manufacturer policy for your region. RICEWIND provides technical documentation, firmware guidance and engineer-level assistance throughout the project.

### Does RICEWIND supply ESR-48/56AC?

Yes. RICEWIND supplies ESR-48/56AC with MOQ from 1 unit; in-stock items dispatch within 24-48 hours with worldwide shipping.

### Is there a cross-reference or equivalent for ESR-48/56AC?

RICEWIND maintains a cross-reference database covering leading telecom and energy infrastructure brands. Contact us for the direct equivalent of ESR-48/56AC.

### What are the rated output and overload characteristics of the Delta ESR-48/56AC rectifier module?

The module has a rated operating voltage of -48VDC and delivers an output current of 56A (rated output power 2900W) at 220VAC nominal input. The AC input range is as wide as 80VAC to 300VAC, with intelligent linear derating when the input voltage drops to 80-176VAC, ensuring uninterrupted output under harsh grid conditions.

### What is the recovery strategy of the ESR-48/56AC after over-temperature protection (OTP) is triggered in the field?

When the internal power device or inductor temperature exceeds the safety threshold (typically internal \>105°C or intake \>75°C), the module automatically limits output power or shuts down for protection. Once airflow obstructions are cleared, ambient temperature recovers and internal temperature falls back to the safe range, the module automatically soft-starts and resumes rated supply without any manual hardware reset.

### How does the current-sharing mechanism of the ESR-48/56AC work during parallel operation?

The module incorporates autonomous current-sharing circuitry and a high-speed communication interface, achieving dynamic balancing of output currents across multiple modules without external controller intervention. Current-sharing imbalance is less than ±5% over the 50%-100% load range, effectively preventing long-term overload aging of any single module.

Content updated: 2026-09-17T17:42:23.745Z