# Vertiv BMK1115601-006 Subrack Telecom DC Power System (-48V 200A 3U)

RICEWIND · Vertiv

https://ricewind.com/en/products/bmk1115601-006

Model: BMK1115601-006

The Vertiv BMK1115601-006 is a telecom-grade -48VDC embedded switched-mode power supply (SMPS) subrack system integrating high-efficiency rectifiers, intelligent DC distribution, and supervisory control architecture.

## What this product is

Engineered as an integral component of the Vertiv NetSure power platform, this subrack integrates modular rectifier slots, advanced supervisory controller wiring, AC surge protection, and dual contactor-driven DC distribution panels. It delivers continuous, filtered -48V DC power directly to telecommunication transport nodes and wireless access networks.

## What problem it solves

Resolves erratic utility grid fluctuations and site blackout threats by pairing wide input tolerances with deterministic multi-stage battery management, preventing destructive battery deep-discharge events and uncoordinated network dropouts.

## Who and where it is for

Telecom operator 4G/5G macro sites, optical transport aggregate nodes, micro-datacenter DC distribution rows, tower shelter cabinets, and mission-critical SCADA networks.

## Core advantages

- Ultra-wide 85VAC to 300VAC input tolerance ensuring resilience against grid voltage sags and swells
- High electrical efficiency exceeding 96.0% with autonomous active current sharing across parallel rectifiers
- Integrated dual LVD contactors (LLVD and BLVD) for automated tiered shedding and battery cell protection
- Advanced NCU/M830B monitoring platform supporting secure SNMPv3, Modbus-TCP, and configurable relay contacts

## Applications

- Telecom 4G/5G macro cellular base stations and distributed remote power sites
- Enterprise-grade cloud data center mission-critical -48V DC power distribution lineups
- Utility power grid dispatch centers and high-voltage substation DC switchgear rooms
- Railway transit signaling, automated train control, and communications equipment rooms

## Technical specifications

- Cooling System Architecture: Front-to-rear forced air cooling
- AC Input Voltage: 85VAC ~ 300VAC (Nominal 220VAC) VAC
- Smart Monitoring Controller: M522B / M530B Monitoring Controller
- Nominal Output Voltage: -48VDC (-42V ~ -58V) VDC
- Rated DC Output Current: 200A (System Capacity 9.6kW)
- Managed Rectifier Capacity: 4-Slot Standard 50A Rectifier Subrack
- Peak Energy Efficiency: ≥95.5%
- Form Factor Dimensions (HxWxD): 133 (3U) × 482 × 320 mm
- Operating Temperature Range: -40°C ~ +70°C

## Frequently asked questions

### How should DC output and battery cable cross-sectional areas be calculated and selected for the BMK1115601-006 system?

Cable cross-sectional area must satisfy both ampacity and loop voltage drop constraints. The engineering formula is S = (2 × I\_max × L) / (γ × ΔV), where S is conductor area in mm², I\_max is maximum continuous current in Amperes, L is single-run cable length in meters, γ is copper conductivity (~57 m/(Ω·mm²)), and ΔV is allowable loop voltage drop (telecom standards typically limit total loop drop to ≤0.5V - 1.0V at full load). The calculated value must be rounded up to the nearest standard cross-section and verified against breaker terminal mechanical constraints and thermal ratings.

### What are the recommended engineering voltage thresholds for LLVD and BLVD in the controller configuration?

For standard 48V VRLA battery strings (24 cells @ 2V), the LLVD (Load Low Voltage Disconnect) threshold is typically configured at 44.0V to 45.0V (~1.83V–1.87V/cell) to shed non-critical auxiliary loads and prolong runtime for core telecom traffic. The BLVD (Battery Low Voltage Disconnect) threshold is configured at 43.2V (1.80V/cell) to prevent destructive deep discharge and plate sulfation. Reconnect thresholds upon AC restoration are generally configured at ≥48.0V to ensure system stability before contactor re-engagement.

### Why is battery temperature compensation required, and how should field engineers calibrate this parameter?

VRLA battery electrochemistry is highly temperature-dependent. Elevated temperatures under fixed float voltage cause excessive current and thermal runaway, while lower temperatures lead to undercharging and capacity loss. The supervisory controller monitors the battery probe and modulates float voltage according to the compensation slope: typically -3mV/°C/cell (-72mV/°C for a 48V string) referenced to 25°C. Field engineers must verify that the sensor is affixed to the center of the warmest battery block, and set both the slope and voltage clamping limits (e.g., 51.5V lower clamp, 56.5V upper clamp) according to the battery manufacturer datasheet.

### What is the systematic troubleshooting procedure when parallel rectifiers display active current-sharing unbalance (\>10%)?

1) Inspect CAN communication: Verify that all rectifier status LEDs show normal data transmission and that no CAN comms alarms exist, ensuring no module has defaulted to autonomous failsafe output; 2) Check mechanical connections and contact resistance: Reseat the deviating module and inspect the backplane blind-mate connectors for bent pins, debris, or arcing; 3) Verify firmware and rating parity: Ensure all parallel rectifiers share the same hardware revision, current limit settings, and firmware version; 4) Calibrate output reference: In autonomous current-sharing mode, isolate modules and verify no-load output voltage matching within ±50mV using a calibrated 4.5-digit multimeter; replace any unit with defective current-sharing control circuits.